RC 195 Receiver-Controller Restrictor
and Connector Repair
Product Description
The Restrictor Kit contains three input restrictor
assemblies, one supply restrictor assembly and
seven gaskets.
The Connector Kit contains one supply connector
assembly and one input connector assembly.
Product Numbers
Restrictor Kit
Connector Kit for Multiple Input
Receiver-Controller
Connector Kit for Single Input
Receiver-Controller
Troubleshooting
Problem
Control pressure
Rotate setpoint
stays at
adjustment screw
approximately zero
counterclockwise
Control pressure
Rotate setpoint
stays at
adjustment screw
approximately
clockwise
supply pressure
Transmitter
Increase sensed
pressure stays at
medium to upper end
approximately zero
of transmitter range
Transmitter
Increase sensed
pressure will not
medium to upper end
build up to 15 psi
of transmitter range
(103 kPa)
Item Number 129-084, Rev. DA
195-066
195-067
195-114
Table 1. Troubleshooting Guide.
Check
Transmitter sensing medium
Pressure
which is above (R.A.) or below
increases
(D.A.) the proportional band
RC 195 out of calibration
Plugged supply restrictor
Pressure
Plug-in connector defective
remains
Receiver-controller is
unchanged
defective
Transmitter sensing medium
Pressure
which is above (D.A.) or below
decreases
(R.A.) the proportional band
RC 195 out of calibration
Pressure
Receiver-controller is
remains
defective
unchanged
Plugged input restrictor
Pressure
No restrictor supplying
remains
transmitter
unchanged
Defective transmitter
Leak at or defective plug-in
Pressure still will
connector
not build up to
Defective transmitter
15 psi (103 kPa)
Low supply pressure
Installation Instructions
Required Tools
Small, flat-blade screwdriver
NOTE: Normally, replacing restrictors or connectors
will not affect calibration.
Before troubleshooting (Table 1), ensure that:
1.
The supply pressure at the unit is constant
(± 2 psi) 22 psi (152 kPa).
2.
All transmitter inputs being used are between
3 and 15 psi (21 and 103 kPa).
3.
Only one restrictor (internal or external)
supplies each transmitter.
4.
The transmitter calibration is correct.
Probable Cause
Document No. 129-084
September 16, 2015
Corrective Action
None
Recalibrate
Replace supply restrictor
Replace plug-in connector
Replace receiver-controller
None
Recalibrate
Replace receiver-controller
Replace input restrictor
Place restrictor in the "in"'
position
Replace transmitter
Replace plug-in connector
Replace transmitter
Increase supply pressure
Page 1 of 3

Advertisement

loading

Summary of Contents for Siemens RC 195

  • Page 1 Transmitter sensing medium Pressure which is above (R.A.) or below None increases (D.A.) the proportional band Control pressure Rotate setpoint RC 195 out of calibration Recalibrate stays at adjustment screw Plugged supply restrictor Replace supply restrictor approximately zero counterclockwise Pressure...
  • Page 2 Plug-in connector replacement The transmitter plug-in connector has numbered ports molded on it. Figure 1. RC 195 Receiver-Controller. The supply and control pressure plug-in connector 3. Remove and replace the input restrictor has the letters "S" and "C" molded on it.
  • Page 3 Document No. 129-084 Installation Instructions September 16, 2015 Service References The RC 195 Receiver-Controller requires a clean, Operation and adjustment information oil-free, dry source of air. In-line filters are RC 195-1 155-036P25 recommended if there is any doubt about the quality...