1. In order to remove the front cover, unscrew the 4 retaining screws.
2. Mark the 4 points in the installation area. After installing the plastic plugs in the wall mount
the luminaire with the mounting screws.
3. Make sure that the battery's cables are connected to the respective poles. Black cable to (-)
pole and red cable to (+) pole.
4. Always use in any case round mains cable, with diameter of 6-9mm (H05RN-F
type 3x1mm² or any other type, at least equal to it's mechanical and electrical
properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is
important to ensure the tightness isolation IP 65). Install the cable gland, pass the round
cable through and tighten it all the way.
5. Connect the wires to the terminal blocks L for live wire, Ν for neutral and
ground.
6. Battery protection fuses. When the spot lights are not functional in emergency mode, check
these fuses and replace them if necessary (one fuse corresponds to each spot light).
7. Refit with care the front cover, by fastening the 4 retaining screws (tightening torque 1Nm).
Front cover retaining screw
mains' power
supply cable
entry
Page 3 from 4
INSTALLATION INSTRUCTIONS
4
retaining
front cover
Minimum distance from lighted objects.
Rubber
washer
Mettalic
washer
1
screws
1
for the
Mounting screw
TEST button
and
charge indication
926021003_09_004