Advertisement

Quick Links

Quick Start Guide
autaniNet/EnOcean Bridge
© 2019 Autani, All Rights Reserved.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EnergyCenter autaniNet/EnOcean Bridge and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Autani EnergyCenter autaniNet/EnOcean Bridge

  • Page 1 Quick Start Guide autaniNet/EnOcean Bridge © 2019 Autani, All Rights Reserved.
  • Page 2: Table Of Contents

    General Application ........................ 23 This document contains the Proprietary and Confidential Information of Autani, LLC. Any use of this information without the expressed written consent of Autani, LLC is prohibited. Copyright Autani, LLC, 2010-2019. All rights reserved. Please refer to www.autani.com/legal...
  • Page 3: Introduction

    Parallel to the above bridging process, the EnOcean Bridge will also allow the devices to be connected to the Autani Manager’s EnergyCenter® Software, via the AutaniNet wireless network. The software can commission the remote sensors and also generate reports for all the devices.
  • Page 4: System Overview

    System Overview Page | 4...
  • Page 5 Page | 5...
  • Page 6: Specifications

    Specifications 3.1. EnOcean Bridge Electrical Radio Network (EnOcean) Physical Input Voltage: 12-24V AC/DC EnOcean 902 MHz Dimensions (HxWxD): 2.56 x 1.5 x 0.85 in Environmental Regulatory Approvals Operating Temperature: 0° to 60°C Module 1: Storage Temperature: -25° to 80°C FCC ID: V8NWAT1000153 and SZVSTM300U IC: 7737A-WAT1000153 and 5713A-STM300U Range Module 2:...
  • Page 7: Mounting The Enocean Bridge

    Mounting the EnOcean Bridge 1. Mount the EnOcean Bridge in a convenient location at a desired distance from the ground, and within a range of 80- 100 ft to the remote sensors. 2. There are two mounting holes provided on the EnOcean Bridge. Locate a place to mount the EnOcean Bridge, mark the holes to be drilled, and drill two holes on the wall.
  • Page 8: Mounting The Thermostats

    This Quick Start Guide will not cover mounting instructions for the thermostat. For instructions on thermostat installation, please refer to the installation manual of respective thermostat on the Autani web portal. NOTE: The brown and white Resistive Output wires MUST be shielded from the 24V wire run, using dedicated conduit and shielding as needed.
  • Page 9: Connect Enocean Bridge To Remote Sensors

    Connect EnOcean Bridge to Remote Sensors The EnOcean Bridge can pair with the sensors locally or be commissioned remotely through the EnergyCenter® software. 6.1. Pairing Locally 1. Put the EnOcean Bridge into Learning Mode a. Insert a pin into the TCM-LRN (learn) button. b.
  • Page 10 b. Press the Learn Button on the sensor housing. If a message is sent, the Red LED will flash on the sensor. If the Bridge has received the message, its LED will briefly turn Green. 3. Pair the EnOcean Temp + Humidity Combo Sensor to the EnOcean Bridge a.
  • Page 11 b. Press the Learn Button on the sensor housing. If a message is sent, the Red LED will flash on the sensor. If the Bridge has received the message, its LED will briefly turn Green. NOTE: WAIT AT LEAST 30 SECONDS FOR LEARN MODE TO EXIT. 5.
  • Page 12: Commissioning Remotely

    6.2. Commissioning Remotely The EnOcean Bridge and the remote sensors can also be paired and commissioned through the Autani Manager’s EnergyCenter® Software. 1. Login to the Autani web portal using the credentials provided. 2. By default the browser will load the Device page with the Dashboard data. (For more information on the User Interface, please refer to the Help section of EnergyCenter.)
  • Page 13 2. The Add Device(s) page loads. Select the EnOcean Bridge from the list of devices and click Next. NOTE: The system may need a moment to search for and list nearby devices. 3. Review the selected device and click Next. 4.
  • Page 14 Pass-through feature of EnOcean Bridge. Here the user can choose to limit the amount of EnOcean messages sent to Autani Manager. 8. Select the option “All - all EnOcean messages are forwarded...” to forward all the messages. Save & Apply.
  • Page 15: Commissioning Remote Sensors

    6.2.2. Commissioning Remote Sensors 1. Click on the Sensors tab, which will allow the user to commission the sensors. The tab should have already listed the sensors added during Learning Mode, or the user can add them directly to the list and set the type of sensing. •...
  • Page 16 3. Start adding the sensors to the EnergyCenter® system. Click Settings > Device Setup > EnOcean Device Management. 4. The EnOcean Device Management page, lists all the EnOcean devices within the range of EnOcean Bridge. Page | 16...
  • Page 17 5. Search/find a Temp Sensor in the list using Serial Number/Address. Select the desired sensor and click on Set Device Type to set the type of sensor. NOTE: The user can skip setting the device type if the sensor is already set with a device type while pairing locally, or if it is set inside the Sensor tab.
  • Page 18 7. With the Temp Sensor still selected, click Add Device(s) button to add the Temp Sensor to EnergyCenter System. NOTE: If the sensor is added, the check box in the Added column should be in checked state, or else click the Refresh button for the checked state to appear, confirming the addition of sensor to the system.
  • Page 19: Commissioning Thermostats

    6.2.3. Commissioning Thermostats 1. The temperature readings from the sensors are averaged, which can be verified against the thermostat value. Click on the Thermostat tab and verify the average temperature displayed in the respective thermostat. 2. If the EnOcean Bridge is connected to a SMT-131 Thermostat, the remote sensor inside the Thermostat Configuration is set to Data Only (use on-board sensors) by default.
  • Page 20 5. If the EnOcean Bridge is connected to a T-32-P Thermostat, the remote sensor inside the Thermostat Configuration is set to Indoor Sensor by default. If it is not, change it to Indoor Sensor. 6. Select the T-32-P Thermostat from the list of thermostats, and click the Setup button. 7.
  • Page 21: Mounting The Enocean Remote Sensors

    Mounting the EnOcean Remote Sensors The below procedures are common to both the EnOcean Temperature Sensor and Temperature + Humidity Combo Sensor. The EnOcean remote sensors should be wall mounted in a convenient location at a desired distance from the ground •...
  • Page 22: Mounting The Pressac Remote Sensor

    5. Connect EnOcean Bridge to Remote Sensors” section.) 6. Install the sensor housing onto the base plate. Start by inserting the groove on top of the sensor housing into the slot provided on the base plate, and then completely insert the bottom of the sensor housing into the base plate. 7.
  • Page 23: General Application

    5. Connect EnOcean Bridge to Remote Sensors” section.) 6. Install the sensor housing onto the base plate. Start by inserting the bottom of the sensor housing into the groove on the base plate, and then completely insert the top of the sensor housing into the top of the base plate. 7.

Table of Contents