Download Print this page

Siemens 7SA513BB Series Service Information page 7

Firmware update to v3.31 eprom exchange

Advertisement

15.
Carefully re-connect the ribbon cables which connect the DVH-module (see fig. 1, pos (2) on
page 12) with the other modules.
Then re-connect the ribbon cables from the front panel; take care for correct polarity:
-
from the operational interface
-
from the LCD-display
-
from the membrane keyboard
16.
The update should now also be indicated externally by the appropriate label on the inner side of
the door of the housing. Use the supplied new label to replace the previous invalidated label.
If the firmware is updated from V2.** to version V3.**, the MLFB-code on the nameplate
(underneath the operator panel) should be modified. Correct the 11th position of the MLFB code
in accordance with the newly installed version V3 (using a water-resistant pen):
- for Version V3.** ---> 11th MLFB position = 2 :
17.
Close the front door of the relay.
18.
The two screws of the front door have to be fixed (see No. 6).
19.
Switch on the device.
After switching on the DC power supply, there are two possibilities of response:
20.
Possibility 1: The device switches into monitor mode (after 30 sec. max.).
Display:
Continue with No. 22
21.
Possibility 2: Start-up of device:
Press:
Display:
Press:
Display:
Press:
Display:
Press:
Display:
Press:
1H firmware
26.06.01
1G firmware
11.04.01
1D firmware
22.04.99
1C firmware
07.01.99
1B
firmware
07.01.99
1A
first issue
06.01.99
Iss.
Type of notice
Date
SIEMENS AG
Alle Rechte vorbehalten
ë
MONITOR-EINSTIEG
FEHLERREAKTION
CW
CODEWORTEINGABE:
333333
@@@@@@
E
CW AKZEPTIERT
DA
DIREKTE ADRESSE
9802
22.04.1999
Date
Röse
Name
ZC
Claus
Tested
ZC
Stand.
(readme_EPROM_BB_EE.doc)
S I E M E N S A G
P T D P A D S I
Power Transmission
and Distribution
Name
Proprietary data, confidential
ë
7SA513*-***2*-****
MONITOR-START
ORIG. START NEC.
CW
ENTER CODEWORD
333333
@@@@@@
E
CW ACCEPTED
DA
DIRECT ADDRESS
9802
Service-Information
7SA513 /BB.../EE V1/V2/V3.XX --> V3.31
Firmware update via EPROM exchange
C53000-A1000-X015-1H-7620
All rights reserved
ë
Page
7 / 13

Advertisement

loading

This manual is also suitable for:

7sa513ee series7sa513 series