Strobes and horn/strobes for fire protective signaling systems

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SS12/24ADA* Series Strobes and
MASS12/24ADA* Series Horn/Strobes
for Fire Protective Signaling Systems
*ULC models add suffix "A"; strobes and sounder/strobes available in 24VDC,
15cd only
Table 1. SS12/24ADA Series electrical ratings:
Model
Supply
Operating Current from Regulated Supply
Voltage
Range
Average
Operating
Current
SS24110ADA
20-30V
210
SS24110ADAB
SS2475ADA
20-30V
170
SS2475ADAB
SS2415ADA
20-30V
75
SS2415ADAB
SS1215ADA
10.5-17V
170
SS1215ADAB
SS241575ADA
20-30V
93
SS241575ADAB
SS121575ADA
10.5-17V
225
SS121575ADAB
20-30V
175
SS2415ADAA
General Description
The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the listed appliances. It is recommended that the
installer be familiar with these requirements, local codes,
and any special requirements of the local fire authority hav-
ing jurisdiction.
The Multi-Alert sounder and signaling strobe are intended
to be connected to the alarm indicating circuit of a UL-
listed fire alarm control panel. Both are compatible with DC
line supervision. The electronic sounder can be connected
Table 2. Sound Output and Current Ratings for the MA12/24D:
Sound (Hz)
Slow Whoop
800 Continuous
800/1000 Alternating
2400 Interrupted
2400 Continuous
1200 Interrupted
Swept Frequency
Fast Warble
Note 1:
See Figure 2 for tab clip removal & storage.
Note 2:
All models can be powered using full wave rectified unfiltered
supplies.
Under
MASS24ADA series devices input voltage exceed 33 VDC or be
less than 16 VDC (16-33Vrms for full-wave rectified, unfiltered
supplies).
Under no circumstances can the MA12/24D input
D900-01-00
Technical Manuals Online! - http://www.tech-man.com
Operating Current from Full-Wave Rectified Unfiltered
Peak
Peak
Inrush
Average
Peak Current
Current
Current
Current
Operating
(mA)
(mA)
(mA in
Current
20/30V
10.5V/17V
access of
(mArms)
Peak)
470/500
-
0
245
385/400
-
0
200
160/180
-
0
90
-
360/380
0
200
210/220
--
0
120
--
510/560
0
270
360/380
--
0
200
Clips on Tabs
( Note 1)
ABC
BC
AC
AB
C
B
A
NONE
no
circumstances
can
SS24ADA
Supply
Peak Current
Inrush Current
(mA)
(mA)
(Amps in excess
20Vrms/
10.5Vrms/
of Peak)
30Vrms
17Vrms
400/500
-
.080
320/370
-
.040
275/290
-
.020
-
330/380
.020
275/290
--
1.0
--
500/530
.020
330/380
--
.020
to either 12 or 24 VDC panels. Models SS2415ADA,
SS2475ADA, SS24110ADA, SS241575ADA, and combina-
tion models incorporating these strobes, require 24 volt
panels.
MASS1215ADA , and MASS121575ADA require 12 volt pan-
els. Panels may have full-wave rectified, unfiltered power
supplies. The strobes produce one flash per second (nomi-
nal) with continuous nominal voltage applied.
The MA12/24D is suitable for outdoor applications (-35° to
66° C) when it is used with a WBB Weatherproof Back Box.
The signaling strobe is rated for 0° to 49° C and is NOT
Current (ma)
Output (dBA)
DC Regulated/
FWR Unfiltered
12V
24V
30V
12V
21/40 38/56 46/72
15/24 28/45 35/55
17/32 34/46 43/58
19/23 35/56 43/64
21/31 38/59 46/73
13/19 23/33 27/41
17/24 34/47 43/60
15/27 30/47 38/59
voltage exceed 33 VDC or be less than 9.6 VDC. Under no cir-
cumstances can a SS12ADA or MASS12ADA series device input
or
voltage exceed 18.7 VDC or be less than 9.6 VDC (9.6 -
18.7Vrms for full-wave rectified, unfiltered supplies).
Note 3:
Measured at 10 feet in an anechoic chamber.
Note 4:
Measured in a UL reverberant room.
1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTE: Inrush current du-
ration is less than
20
(.00002 seconds).
Models
SS1215ADA,
UL (dBA)
(Note 3)
Ratings
(Note 4)
24V
12V
24V
85
92
79
85
87
93
79
85
85
92
79
85
89
90
79
85
85
94
79
85
85
91
75
82
85
92
79
85
85
92
79
85
A Division of Pittway
microseconds
SS121575ADA,
I56-650-16

Advertisement

loading
Need help?

Need help?

Do you have a question about the SS12/24ADA Series and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor SS12/24ADA Series

  • Page 1 Fire Protective Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 *ULC models add suffix “A”; strobes and sounder/strobes available in 24VDC, 15cd only Table 1. SS12/24ADA Series electrical ratings: Model Supply Operating Current from Regulated Supply Operating Current from Full-Wave Rectified Unfiltered...
  • Page 2 System Sensor recommends that the Multi-Alert Sounder and Signal hearing the alarm. The Sounder may not be heard by persons who are Strobe always be used in combination so that the risks from any of the hearing impaired.
  • Page 3 Figure 1. Vertical and horizontal light distribution: Degrees % of Rating 0˚ 5 - 25 30 - 45 45˚ –45˚ LIGHT 90˚ –90˚ Figure 2: Figure 3. Multi-alert sounder: To Next COVER SLOT - VDC TONE SELECTION TABS Device TAB A + VDC TAB B TAB C...
  • Page 4 5. Fill remaining holes with screw B. MP-F MA 12/24 1. Screw sounder to plate. 2. Complete field wiring. 3. Screw plate sounder to box Standard Backbox Plaster with screw F. Ring MP-SF A78-1137-08 A78-1137-11 D900-01-00 I56-650-16 Technical Manuals Online! - http://www.tech-man.com © System Sensor 1996...
  • Page 5: Installation And Maintenance Instructions

    INSTALLATION AND MAINTENANCE INSTRUCTIONS SP100ADA Series Dual-transformer Speaker/Strobes for Fire Protective A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Specifications Mechanical Input Terminals: 12 to 18 AWG (3.31 to 0.82 mm Speaker Size: 4 inches (101 mm) Grille Size: 5"...
  • Page 6 For example, Table 1 shows that to select a 1/4 Watt in- Table 1: put when a 25 volt amplifier is being used, slide the blue 1/2 W 1/4 W 1/8 W lead onto post 3 and slide the yellow lead onto post B. Similarly, to select a 4 Watt input with a 70.7 volt ampli- 25 V fier, slide the blue and yellow leads onto posts 2 and A,...
  • Page 7 NOTE: The light output at 0° viewing angle for Strobe Light Ratings The signaling strobe is rated for 0° to 49° C and is not suit- SP1*241575ADA is 75 cd (See Figure 3). able for outdoor use. R = Red The rated light output of the SP1 2415ADA and W = White...
  • Page 8 System Sensor makes no other The Company shall not be obligated to repair or replace units which are express warranty for this speaker/strobe.
  • Page 9 INSTALLATION AND MAINTENANCE INSTRUCTIONS V4R24ADA Series Speaker/Strobes A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 for Fire Protective Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Specifications Speaker Frequency Range: 400 Hz to 4000Hz Supervision: Capacitive input for supervisory DC voltage Mounting: Standard 4"...
  • Page 10 Figure 1. Vertical and horizontal light distribution: Degrees % of Rating 0˚ 5 - 25 30 - 45 45˚ –45˚ LIGHT 90˚ –90˚ The light output rating of the Model V4R24110ADA is 110 2. See Figure 2. The speaker is equipped with five posts cd;...
  • Page 11 C. Semiflush Wall Mount Figure 2: (a) System Sensor semiflush mounting plates are shipped with #8 nuts already installed from the 1/4W back. 1/2W (b) Attach the semiflush mounting plate to a standard 4- inch square electrical box using the two 8-32 X 5/8"...
  • Page 12 System Sensor makes no other The Company shall not be obligated to repair or replace units which are express warranty for this speaker/strobe.
  • Page 13 INSTALLATION AND MAINTENANCE INSTRUCTIONS RK24ADA Series Retrofit Strobes A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 for Fire Protective Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Table 1. RK24ADA Series Electrical Ratings: Model Supply Operating Current from Operating Current from Full-Wave Voltage Regulated Supply Rectified Unfiltered Supply...
  • Page 14 Note : All models can be powered using full wave recti- Mounting Location (per NFPA 72) fied unfiltered supplies. Under no circumstances Sleeping: 110 cd if bottom of appliance is greater than 24" can RK24ADA series devices input voltage exceed below the ceiling, 177 cd if the bottom of the appliance is 33 VDC or be less than 16 VDC (16-33Vrms for full- less than 24"...
  • Page 15 Figure 2. Sounder and strobe operating Figure 3. Sounder and strobe operating in tandem: independently: To Next Caution: Break off P.C.B. Tabs – VDC Non- – VDC To Next Coded STROBE Device + VDC Supply + VDC Device – VDC or EOL Can Be Coded...
  • Page 16 System Sensor recommends that the Multi-Alert Sounder and Signal hearing the alarm. The Sounder may not be heard by persons who are Strobe always be used in combination so that the risks from any of the hearing impaired.
  • Page 17 INSTALLATION AND MAINTENANCE INSTRUCTIONS PS12/24ADA Series Strobes with Mini-sounder for Fire Protective A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Table 1. PS12/24ADA Series Electrical Ratings Operating Current from Regulated Supply Operating Current from NOTE: In-rush current du- Model Supply...
  • Page 18 Greater than 90 dBA measured in anechoic room at 10 feet, Figure 2: 24 volts (see Figure 2 for other voltages); 79 dBA minimum measured in UL reverberant room @ 12V and 82 dBA @ 24V. NOTE: All models can be powered using full wave recti- fied unfiltered supplies.
  • Page 19 Screw types used in Figures 5 – 8 below: A=#6-32x1-1/2" Phillips Oval Head B=#8-32x5/8" Slotted Pan Head C=#6-32x5/8" Slotted Pan Head D=#8 Phillips Oval Head Sheet Metal Figure 5. Sur face mount to single gang box: Figure 6. Semi-flush mount to single gang box: A78-2602-00 A78-2604-00 1) Complete Field Wiring (see Figure 3)
  • Page 20 The visual warning signal is suitable for direct viewing and Three-Year Limited Warranty System Sensor warrants its sounder/strobe to be free from defects in mate- ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please rials and workmanship under normal use and service for a period of three include a note describing the malfunction and suspected cause of failure.
  • Page 21 INSTALLATION AND MAINTENANCE INSTRUCTIONS RP12/24ADA Series Retrofit Strobes for Fire Protective A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 Signaling Systems 1-800-SENSOR2, FAX: 630-377-6495 Table 1. RP12/24ADA Series electrical ratings: NOTE: In-rush current du- Model Supply Operating Current from Regulated Supply Operating Current from Full-Wave Rectified Unfiltered Voltage Supply...
  • Page 22 System Sensor makes no The Company shall not be obligated to repair or replace units which are other express warranty for this sounder/strobe.
  • Page 23 Figure 2. Independent horn/strobe wiring: Figure 3. Combination horn/srtrobe wiring: (-)IN (-)OUT (+)IN (+)OUT – VDC STROBE NON-CODED SUPPLY To Next + VDC To Next Device – VDC Device SOUNDER CAN BE – VDC or EOL CODED + VDC SUPPLY or EOL + VDC From...
  • Page 24: Label Placement

    Label placement WIRE STRIP GAGE Note: Proper lens orientation. Figure 7. Snap strobe back into place: Figure 8. Final inverted unit: IN ( ) IN ( WIRE STRIP GAGE D900-09-00 I56-757-02 Technical Manuals Online! - http://www.tech-man.com © System Sensor 1996...
  • Page 25 INSTALLATION AND MAINTENANCE INSTRUCTIONS SS24ADAS Series Strobes and MASS24ADAS Series Synchronized A Division of Pittway Horn/Strobes for Fire Protective 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Signaling Systems Table 1. SS24ADAS Series Electrical Ratings: NOTE: In-rush current du- Model Supply Operating Current from...
  • Page 26 System Sensor recommends that the Multi-Alert Sounder and Signal far away to be heard over the ambient noise such as traffic, air condition-...
  • Page 27 Figure 1. Vertical and horizontal light distribution: Percent of Degrees Rating 5 - 25 0˚ 30 - 45 45˚ –45˚ LIGHT 90˚ –90˚ NOTE: ALL STROBES THAT ARE TO BE IN SYNC MUST BE ON THE SAME POWER CIRCUIT. Figure 2: Figure 3.
  • Page 28 5. Fill remaining holes with screw B. MP-F MA 12/24 Standard Backbox Plaster 1. Complete field wiring. Ring 2. Screw plate sounder to Box MP-SF with screw F. A78-1137-08 A78-1137-11 D900-06-00 I56-750-57 Technical Manuals Online! - http://www.tech-man.com © System Sensor 1996...
  • Page 29 INSTALLATION AND MAINTENANCE INSTRUCTIONS SS24ADAS Series Strobes and MAEH24ADAS Series Synchronized A Division of Pittway Electromechanical Horn/Strobes for 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Fire Protective Signaling Systems Table 1. SS24ADAS Series Electrical Ratings: NOTE: In-rush current du- Model Supply Operating Current from...
  • Page 30 System Sensor recommends that the Multi-Alert Sounder and Signal far away to be heard over the ambient noise such as traffic, air condition-...
  • Page 31 Figure 1. Vertical and horizontal light distribution: Percent of Degrees Rating 5 - 25 0˚ 30 - 45 45˚ –45˚ LIGHT 90˚ –90˚ NOTE: ALL STROBES THAT ARE TO BE IN SYNC MUST BE ON THE SAME POWER CIRCUIT. Figure 2: Figure 3.
  • Page 32 5. Fill remaining holes with screw B. MP-F MA12/24EH Standard Backbox Plaster 1. Complete field wiring. Ring 2. Screw plate sounder to box MP-SF with screw F. A78-1137-30 A78-1137-31 D900-12-00 I56-933-05 Technical Manuals Online! - http://www.tech-man.com © System Sensor 1996...
  • Page 33 INSTALLATION AND MAINTENANCE INSTRUCTIONS SpectrAlert Horns, Strobes, and Horn/Strobes A Division of Pittway For use with the following models: 3825 Ohio Avenue, St. Charles, Illinois 60174 Horns: 12/24 volt: H12/24*, H12/24W* 1-800-SENSOR2, FAX: 630-377-6495 Strobes: 12 volt: S1215, S121575, S1215W, S121575W 24 volt: S2415*, S241575*, S2475*, S24110*, S2415W*, S241575W*, S2475W*, S24110W*...
  • Page 34 Strobe Only: AVERAGE CURRENT (mA) PEAK CURRENT (mA) IN RUSH CURRENT (mA) 12V Models 24V Models 12V Models 24V Models 12V Models 24V Models 10.5V 10.5V 10.5V Candela 133 159 114 157 81 128 79 460 460 450 460 420 480 150 270 150 270 140 250 80 108 92 124 140 190 170 230 220 280 270 370 15/75...
  • Page 35 The strobe must have an unin- alarm. The horn may not be heard by persons who are hearing impaired. terrupted source of power in order to operate correctly. System Sensor rec- ommends that the horn and signal strobe always be used in combination The signal strobe may not be seen.
  • Page 36 3. Insert locking rib into slot on plate. 2. Complete field wiring. 4. Push into recessed area. 3. Mount unit to back box with screws B. 5. Secure unit to skirt with screw D. D900-13-00 I56-982-02 Technical Manuals Online! - http://www.tech-man.com © System Sensor 1996...