PAG. 4/24 DESCRIPTION The CE100 gas Central System is realized for DIN rail mounting and it can be connected up to six 4÷20mA remote sensors. It represents a useful instrument for monitoring and controlling areas where there might be the presence of flammable, toxic gases or oxygen.
For each sensor, the display shows the measured value and also its status: FAULT< (<1mA) PRE1, PRE2, ALL, FAULT> (over 24 mA). details”). (See explaination in the chapter “Sensor TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
FAULT> (above 24 mA) ..The sensor is measuring a gas concentration beyond all limits, or is broken or disconnected. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
NOTE: This control acts only on the 3th alarm level, and then the valve must be connected to relay ALL. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
(3) with a suitable size. C. The wiring diagrams on the following pages, for simplicity are always shown with all the sensors. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
"Negative logic" (the contact will be NO) or "Positive logic" (the contact will be NC). (See fig. 5, fig. 7 and the NOTE on page 12). TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
- Detectors with “Replaceable Cartridge Sensor” using electrochemical cells: for toxic gases TS220E (IP65) or TS293E (Ex-d) series and for oxygen TS220EO e TS293EO (Ex-d) series with 0÷25%O range. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
Always refer to specific instructions attached to them. Please note that all WARNING documentation attached to the products "Central Unit and Gas Detectors" must be read and kept. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
"Short Circuit", but should not be connected loads that exceed the indicated current capacity, or which may generate noise on power supply. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
YES and to confirm. If you leave NO the operation will be cancel (please see chapter then "DELETION SENSORS"). TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
Page 14
IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 14/24 Table 1 - Pre-configured parameters of the detectors (sensors) To simplify setup, the models indicated in the table are pre-configured with default settings; you can use in common situations. The detectors into brackets has operational characteristics identical to the first highlighted in bold, the only difference is the type of protection custody. If necessary you can also configure other detectors, selecting the "Generic"...
TIME ON (in seconds) for all relays K1, K2, K3 and K4 is= 0. This parameter should only be used and as indicated in "Change Sensor" on page TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 16/24 Setup SENSORS COPY Sensor choice From the MAIN MENU , with key select the sub- Sensor Copy “2-Sensor copy” menu “Setup”. Press , select with Sensor delete then press to confirm. Sensor cop y...
Page 17
YES and then press Model : TS292KM CONFIRM ? NO confirm, and then press to return to the MAIN MENU. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
0123456789#$%&- Then enter the New Code , scroll the numbers with keys Code and confirm with NEW CODE 2 0123456789#$%&- TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
AL101 or AL102. Do not leave this test active for more than a minute. During the test is activated, the "load" to the internal CE100, consisting of power resistors which obviously will become hot. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
If the battery voltage gets down under 10VDC, it is automatically disconnected to avoid damages. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
About 40 minutes ( with 6 sensors series TS293P and a 12Vdc/12W Gas Valve ). Batterie life Dimensions (l x h x p) 90x60x52 Weight About 300 grams TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
500 up to 1000 meters 3x2,5 mm Shielded single point of "GROUND". TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...
ATTENTION: we suggest writing (max. 4 numbers) and storing the code in a safety place. In case the Code gets lost, contact our Service Dept. That will give an emergency Code. TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734...