06: Reserved
Interface
07: Reserved
Interface
08: Bypass mode setting
Interface
09: Battery maximum discharge time setting
Interface
10: Reserved
Interface
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
49
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 03 16 AA 59 203 26
Setting
Reserved
Setting
Reserved
Setting
Parameter 2:
OPN: Bypass allowed. When selected, the UPS will run in Bypass
mode depending on bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it is prohibited to runn
in Bypass mode under any circumstances.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass
means users manually operate the UPS for Bypass mode. For
example, pressing the OFF button in AC mode to switch to
Bypass mode.
Setting
Parameter 3:
000~999: Set the maximum backup time from 0min to 999min.
UPS will shut down to protect battery after backup time runs out.
The default value is 990min.
DIS: Disable battery discharge protection and backup time will
depend on battery capacity.
Setting
Reserved