Manual Neon 3000 Family Neon Remote Loggers (NRL) This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules in the U.S.A. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Page 2
Manual – 3000 NRL Family Revision History Checkeda File name/Revision Date Author & Change Details pproved Unidata Manual - 30xxA NRL Family - 14 06 2017.docx 14 06 17 IM - draft Unidata Manual - 30xxA NRL Family - 16 06 2017.docx 16 06 17 RS&IM adding specs &...
Manual – 3000 NRL Family TABLE OF CONTENTS Neon Technology and System Overview ................ 4 Neon Remote Loggers ......................6 Typical Neon Measurement System ................... 6 The NRL Stand Alone Data logger Implementation ............7 The NRL Full Protocol Implementation - Internet Connection Required ......7 The NRL Message Based Implementation- LoRa LPWAN &...
Manual – 3000 NRL Family References This manual should be read in conjunction with the associated Starlog 4 User Manual Management Software for Loggers and Neon Terminals and Loggers Manual Neon Server Applications Software Documentation which is available on help screens on any Neon Installation and in PDF form from the main Unidata web site This manual and the StarlogV4 User Manual and the Neon Server User &...
Page 5
Manual – 3000 NRL Family Overview of the Neon System Unidata Manual - 3000 NRL Family - 06 08 2019.docx Page 5...
Manual – 3000 NRL Family Neon Remote Loggers There are many different models of Neon Remote Loggers available. While the models may be different, and the interfaces available in various models are different, the basic operation of all Neon Remote Loggers is the same. Typical Neon Measurement System Typical Neon Measurement System The figure above is an example of a Neon installation showing an NRL connected to a Modbus sensor.
Manual – 3000 NRL Family The NRL Stand Alone Data logger Implementation The NRL can be programmed with a program (scheme) in the factory or in a remote office and then transported to the field to work as a stand-alone system, without the need to have an internet connection. For this operation method the program (scheme) is downloaded to the NRL using the Starlog 4 Logger configuration software.
Manual – 3000 NRL Family NRL Internal Architecture The NRL Internal architecture is shown below. It contains two discrete sections: 1. A LOGGER section where the terminal connects to the field transducers and the logging scheme, scan rates and diagnostics are managed. The StarlogV4 support software allows a user to generate a logger program (called a scheme) which defines transducer information, logging scan rates, logger interval etc and various engineering unit definitions.
Manual – 3000 NRL Family NRL Models The NRLs come in different sizes and configurations, and while the software architecture remains the same with all models, the larger models have more connectivity and more input channels than the lower models. There are three main groups: 1.
Manual – 3000 NRL Family 1.10.3 USB Thumbdrive Not currently available, but future updates to NRLs will add support for USB thumbdrives with the same functionality intended for MMC/SD cards. NRL LED INDICATORS 3016, 3008, 3004 “High End” These loggers have six bi-colour (red/green) LEDs: Label Description Power...
Manual – 3000 NRL Family Normal Scheme Indication In normal operation the Power/PWR LED comes on first, quickly followed by the Scheme/SCHM LED, then both turning off. This occurs at regular scan intervals as specified by the scheme, which can range from one second to many minutes.
Page 12
Manual – 3000 NRL Family Parameter Details Logger Name NRTID NRT ID number. SER# Logger serial number. Time / Date Current logger time & date. MAIN Main power supply input voltage. Auxiliary power supply input voltage. RTCC Internal Real Time Clock battery voltage. Temp Current logger internal temperature.
Manual – 3000 NRL Family Logger Status Screen Navigation The Logger Status screen has two pages that can be scrolled using the UP & DOWN keys. Pressing the LOGGER STATUS button on the LCD screen will toggle between the two pages. Press ENTER. NeonRemoteLogger Baro 14.1degC...
Manual – 3000 NRL Family A12: 908.852mV Logger A13: 915.399mV Status A14: 913.413mV Scheme A15: 766.925mV Status C0 : Configure C1 : Logger C2 : C3 : ▼ DOWN/UP▲ C0 : Logger C1 : Status C2 : Scheme C3 : Status C4 : Configure...
Page 15
Manual – 3000 NRL Family 3.3.1 General Configuration Parameters Config General Logger ...press Down Status Scheme Status Configure Logger Notes Parameter Enter PIN # Enter the current 4 digit PIN # Change PIN # Change the PIN # Turn display off Forces the screen to turn off immediately Reset logger Reconfigures the logger to factory defaults...
Manual – 3000 NRL Family 3.3.2 Communication Parameters Config Comms Logger ...press Down Status Scheme Status Configure Logger Parameter Notes Force a communications cycle to occur immediately instead of at the Force Neon comms scheduled time. Connects to the Neon Server, downloads the scheme for the configured Initialise NRL NRT ID, and starts logging.
Manual – 3000 NRL Family 3016 Neon Remote Logger – 16 Analogue Channels The 3016 Neon Remote Logger (NRL) is self-contained data logger / rtu with 16 high resolution analog channels in a compact case which connects to sensors in the field, collects readings from those sensors and transmits the collected data to a central Neon server, or it can be set up to operate as a stand-alone datalogger / rtu.
Manual – 3000 NRL Family Data Interface: USB B Port and SD Micro Card Ethernet Port: 10/100 Mbit LCD Display: 320 x 240, Colour, Resistive Touch Panel Keypad: 5 button membrane keypad Accelerometer: Senses changes in logger orientation Barometer: 260-1260hPa Absolute Digital Output Integrated Logger Specifications Storage memory: 7.5Mbytes Flash (non-volatile), up to 3.75 Million log data points...
Manual – 3000 NRL Family RTC Backup Battery: 3.6V Li Coin Cell (5 year life) Instrument Power 5V regulated, 100mA fused 4 Single ended (max) or 2 Differential (max) Analog Channels 3004: 24 bit resolution, 4 user selectable gain ranges, 0 to 5000mV (gain=1) to 0 to 39mV (gain=128) 6 Single ended (max) or 3 Differential (max) Analog Channels 3006: 24 bit resolution, 4 user selectable gain ranges, 0 to 5000mV (gain=1) to 0 to 39mV (gain=128)
Page 21
Manual – 3000 NRL Family 4.4.1 3004-MC/E/H/I/L Specifications Physical specifications Material: Polycarbonate Size: 190mm x 80mm x 55mm (LxWxH) Weight: 300 grams Operating Temp: -20°C to 60°C. Not affected by humidity Antennae: Model dependent, external stub/whip/satellite antenna Electrical Specifications External Power: 9 to 30V DC (provision for dual power inputs) Current Draw: <50μA Standby...
Manual – 3000 NRL Family 3004/6 – M Product Options Series Model Description 3004-M000 4 Channel NRL No Modem No Batteries 3004-M0B0 4 Channel NRL No Modem with Lithium Battery 3006-M000 6 Channel NRL No Modem No Batteries 3006-M0B0 6 Channel NRL No Modem with Lithium Battery 3004-MC00 4 Channel NRL 3G/4G Modem No Batteries 3004-MCB0...
Page 23
Manual – 3000 NRL Family 4.5.1 3001- MC/H/I/L Specifications Physical specifications Material: Polycarbonate Size: 190mm x 80mm x 55mm (LxWxH) Weight: 300 grams Operating Temp: -20°C to 60°C. Not affected by humidity Antennae: Model dependent, external stub/whip/satellite antenna Electrical Specifications External Power: 9 to 30V DC (provision for dual power inputs) Current Draw:...
Manual – 3000 NRL Family CONNECTIONS This section provides brief descriptions of available connections/terminations for all 3000 range loggers. The tables below list each termination with a brief description. 3016 Neon Remote Logger – Connections/Terminations Unidata Manual - 3000 NRL Family - 06 08 2019.docx Page 24...
Page 25
Manual – 3000 NRL Family Terminal Connection Description SAT MODEM Globalstar Satellite Connection AUX+ External 9V to 30VDC Power Supply + POWER 9-30VDC AUX- External 9V to 30VDC Power Supply - MAIN+ External 9V to 30VDC Power Supply + POWER 9-30VDC MAIN- External 9V to 30VDC Power Supply - CONFIGURATION...
Page 26
Manual – 3000 NRL Family Terminal Connection Description AGND Analog Ground A7/D3- A7 +ve single (D3 -ve differential) A6/D3+ A6 +ve single (D3 +ve differential) AGND Analog Ground ANALOG INPUTS AGND Analog Ground A5/D2- A5 +ve single (D2 -ve differential) A4/D2+ A4 +ve single (D2 +ve differential) AGND...
Page 28
Manual – 3000 NRL Family Terminal Connection Description SAT MODEM Globalstar Satellite Connection AUX+ External 9V to 30VDC Power Supply + POWER 9-30VDC AUX- External 9V to 30VDC Power Supply - MAIN+ External 9V to 30VDC Power Supply + POWER 9-30VDC MAIN- External 9V to 30VDC Power Supply - INSTRUMENT...
Page 30
Manual – 3000 NRL Family Terminal Connection Description AUX+ External 9V to 30VDC Power Supply + POWER 9-30VDC AUX- External 9V to 30VDC Power Supply - MAIN+ External 9V to 30VDC Power Supply + POWER 9-30VDC MAIN- External 9V to 30VDC Power Supply - Ground MODBUS MODBUS MODBUS A-...
Manual – 3000 NRL Family 3004-M000 – Connections/Terminations Terminal Connection Description OUT0 Digital Output0 Open Drain FET 30V DC,, 250mA max Ground SDI-1 SDI-12 Signal SDI-12 Ground External Power Supply - EXT PWR PEXT External Power Supply + (9V to 30V) MODBUS Channel 1 B+ MODBUS MODBUS Channel 1 A-...
Page 32
Manual – 3000 NRL Family Terminal Connection Description A3/C4 Analog A3 +ve single (or Optional Counter C4) A2/C5 Analog A2 +ve single (or Optional Counter C5) A1/C6 Analog A1 +ve single (or Optional Counter C6) A0/C7 Analog A0 +ve single (or Optional Counter C7) CN13 AGND Analog Ground...
Manual – 3000 NRL Family 3001-M0 Neon Remote Nano Logger – Connections/Terminations 5.5.1 Option 1 SDI-12 INSITU Sensor JP Config Connection Description Cable Colour P8 C0 P1 SDI SDI-12 Signal White JP1 – CLOSED P9 GND (if needed, to supply power to sensor) P2 MB+ Ground...
Page 34
Manual – 3000 NRL Family 5.5.3 Option 3 4-20mA INSITU Current Loop Sensor JP Config Connection Description Cable Colour P8 C0 P1 SDI JP1 – OPEN P9 GND JP2 RIGHT (linking pins 1&2 to supply P2 MB+ loop power to sensor) P3 MB- JP3 LEFT (linking pins 2&3 to feed return...
Page 35
Manual – 3000 NRL Family 5.5.5 Option 5 SQL SDI-12 Sensor JP Config Connection Description Cable Colour SDI-12 Signal White JP1 – CLOSED (if needed, to supply power to sensor) JP2 – OPEN JP3 RIGHT (linking pins 1&2 to ground black wire) JP4 - OPEN Sensor Power...
Page 36
Manual – 3000 NRL Family 5.5.7 Option 7 SQL 3 wire 4-20mA sensor JP Config Connection Description Cable Colour JP1 – CLOSED (as needed, to supply power to sensor) JP2 LEFT (linking pins 2&3 ) JP3 RIGHT (linking pins 1&2 to ground black wire) 4-20mA Input Brown...
Page 37
Manual – 3000 NRL Family 5.5.9 Option 9 SQL Counter Input JP Config Connection Description Cable Colour Counter Input Purple JP1 – CLOSED (if needed, to supply power to sensor) JP2 – OPEN JP3 RIGHT (linking pins 1&2 to ground black wire) JP4 - OPEN Sensor Power...
Page 38
Manual – 3000 NRL Family 5.5.11 SQL Signal 7 Pin Input Connector Pinout Pin No. Wire Colour Pad No. Signal Name White Sdi-12 Blue RS485 + Green RS485- Brown A0 or 4-20mA Loop Send Sensor Power (Out) Purple Black GND or 4-20mA Loop Return 5.5.12 Insitu Signal 6 Pin Input Connector Pinout Wire Colour...
Page 39
Manual – 3000 NRL Family Unidata Manual - 3000 NRL Family - 06 08 2019.docx Page 39...