  • Page 1 Operating Instructions Clock Thermostat Type TTE-30AC...
  • Page 2: Table Of Contents

    Installation and commissioning guide ......14 Contens 7. Fields of application ............. 14 Chapter 8. Assembly and installation..........14 Exclusion of liability............3 8.1 Assembly..............14 8.2 Assembly steps............. 15 Safety information ............... 3 8.3 Connection diagram ............15 Transport, storage .............. 4 8.4 Range limitation ............
  • Page 3: Exclusion Of Liability

    Exclusion of liability The device is designed for connection to permanent wiring To allow for future developments, construction methods and in closed dry rooms. technical data given are subject to alteration. We do not accept any liability for possible errors or omissions in the information Inspect electrical equipment periodically: retighten loose contained in data, illustrations or drawings provided.
  • Page 4: Transport, Storage

    • Party key that allows for an unscheduled increase of the temperature to a comfortable level for one, two, three or • Ziehl-Abegg controllers are suitably packed at the factory to four hours. comply with the requirements of the mode of transport •...
  • Page 5: Controls And Display

    2. Controls and display The bar at the upper display edge (1) displays the weekday. The temperature (or the time) is displayed here (2). The arrow (3) indicates the active operating mode (heating cooling The bar at the lower display edge (4) indicates the time range for the comfort temperature of the associated day.
  • Page 6: General Function

    3. General function refer to the diagram below). The frostprevention temperature (without coupling to the comfort temperature) is also set from 3.1 Setting the temperature the program menu. The automatic control device operates with three different set Note: The energy saving temperature is always automatically temperature levels (comfort...
  • Page 7: Functions In The Normal Display

    4. Functions in the normal display Pressing the PROG key causes a premature return to the time program. 4.1 Party function (extend the heating phase) 4.2.2 Switching to the energy saving temperature for a If required, the comfort temperature can be extended or long time activated.
  • Page 8: Locking The Keyboard

    4.4 Locking the keyboard This is permanently indicated with the arrow at the left display edge (heating , cooling , in die operation mode OFF The keys can be locked to prevent unauthorized operation. nothing is displayed). To do this, press the – and SET keys If the mode OFF, the energy saving output and the control simultaneously for 5 seconds.
  • Page 9: Setting Temperature Levels - Temp Menu Item

    The + or the – key can now be used to set the hour. The display automatically returns to the (Clock) program menu. After the hours have been confirmed, the minutes start to flash. The program menu is exited by pressing the PROG key. These are now set in the same way with the + and –...
  • Page 10 This value can now be changed in 10-minute intervals with the Note: The time programm heating can be changed in the + and – keys, and confirmed with the SET key. operation mode heating (HEAt), and the time programm cooling can be changed in the operation mode cooling The same procedure is used for the day selection and for the (COOL).
  • Page 11 5.3.5 Adding a new switching time 5.3.7 Special programming cases After selecting the empty switching time, press the SET key. No empty switching time will be offered if no further switching time is available. The hour display flashes and can be changed with the + and –...
  • Page 12: Vacation Function

    5.4 Vacation function After confirming the month with SET, the day of the vacation end can be The device provides with the UrLb menu item a vacation changed similarly. function. This allows the time program to be suspended for a Press SET again to set similarly the maximum period of one year.
  • Page 13: Failure Causes And Their Rectification

    6 Failure causes and their rectification 6.4 Output is not triggered If the output is not triggered as expected, this can have 6.1 No display several causes. A set minimum switching time, a set upper or Should a power failure occur, to save energy, although the lower limit temperature may still be acting.
  • Page 14: Installation And Commissioning Guide

    Dimensions (mm): guide 7. Fields of application The TTE-30AC clock thermostat is used to control the temperature for single rooms in residential or office buildings. The relay output can be used to directly trigger actuators. The device has an output that can be used to bring automatic control devices that do not have a clock into an energy saving mode.
  • Page 15: Assembly Steps

    8.2 Assembly steps Connection diagram 1. Connect the wires to the terminals in the recessed part (observe the connection diagram in Section 8.3). 2. Install and screw the recessed part in the flush-type box (note the installation direction, terminals at the top). 3.
  • Page 16: Range Limitation

    8.4 Range limitation 9. Commissioning If the complete setpoint adjustment range of the rotary button During the commissioning and after a reset, the device should not be used, this range can be limited mechanically. automatically begins with the clock setting because the clock has not yet been set.
  • Page 17: Initial Settings In The Parameter Menu

    10. Initial settings in the parameter menu The following parameters can be set or displayed: Software version Note: Because under some circumstances incorrect settings will no longer permit any proper control operation, changes in n (normal) Normal display (desired temperature, this menu should only be made by specialists.
  • Page 18: Software Version (=)

    10.1 Software version (=) Reference Opera- Floor Actuator Display variable ting temperatur This menu item can be used to fetch the currently installed mode limit software version. Internal sensor Heating — de-energized I.c* Note: For technical problems, always specify the version of closed the software installed in the automatic control device.
  • Page 19: Switching Difference (D)

    10.4 Switching difference (d) external sensor exceeds the temperature set here. The possible setting range is +25° C to +50° C. This parameter defines the switching difference (hysteresis) of the control function. If the current actual temperature lies The factory setting for the upper limit temperature is 50° C. above the desired temperature by the value set here, the The limit function does not have any switching difference, i.e.
  • Page 20: Temperature At The External Sensor (S)

    10.8 Temperature at the external sensor (S) 10.10 Sensor compensation (A) If an operating mode that requires an external sensor is This parameter can be used to move the measured actual selected, the current temperature value will be displayed with temperature by ±3.0 Kelvin.
  • Page 21: Gradient Of The Initial Heating Optimization (R)

    10.12 Gradient of the initial heating optimization (r) Note: If the daylight saving function is deactivated (OFF), the clock time will not be changed automatically. In this This menu item can be used to check the current gradient used case, the clock time must be changed manually. to calculate the lead time.
  • Page 22 - 22 -...
  • Page 23: Technical Data

    Max. permitted switching 10A, 230V AC, (cos ϕ=1) current 4A, 230V AC, (cos ϕ=0,6) Electric live min. 3 x 10 4 operations Typ TTE-30AC 325003 Energy saving output Optocoupler, potential Temperature ranges +5 ... +30° C (comfort- und energy applied with L saving temperature) 30 mA, 230V AC, (cos ϕ=1)
  • Page 24: Maintenance, Service

    Download -Ventilation Technology - Topic: Control Engineerin - If you have any questions concerning the use of our products or plan special uses, please contact: Document type: General documents. Ziehl-Abegg AG Heinz-Ziehl-Straße 74653 Künzelsau Telefon +49 (0) 7940 16-0 Telefax +49 (0) 7940 16-504 info@ziehl-abegg.de...