Allen-Bradley Kinetix 5100 AC 2198-DB111-F Installation Instructions Manual page 3

Table of Contents

Advertisement

Wiring Examples for the AC Line Filter
Protection
Mains AC Input
Bonded Cabinet
Ground Bar
Protection
Mains AC Input
Bonded Cabinet
Ground Bar
Three-Phase Wiring Specifications
Line Filter
Cat. No.
2198-DB310-F
2198-DB324-F
2198-DB335-F
2198-DB356-F
(1) The actual gauge of the input power wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local
codes.
Single-Phase Wiring Specifications
Line Filter
Cat. No.
2198-DB111-F
2198-DB127-F
(1) The actual gauge of the input power wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local
codes.
Circuit
230V
L1
L2
2198-DB -F
L3
AC Line Filter
Line
Circuit
120/230V
L1
L2
2198-DB1 F
AC Line Filter
Line
Recommended
Connects to
Wire Size
Terminals
2
mm
(AWG)
L1
0.8...8.4 (18...8)
L2
L3
2.5...33.6 (14...3)
Recommended
Connects to
Wire Size
Terminals
2
mm
(AWG)
L1
L2
0.8...8.4 (18...8)
Rockwell Automation Publication 2198-IN017A-EN-P - July 2019
Circuit
Protection
L1C
L2C
L1'
L1
L2'
L2
L3'
L3
Load
Circuit
Protection
L1C
L2C
Load
(1)
AC Line Filter
Strip Length
mm (in.)
11.0 (0.43)
15.0 (0.59)
(1)
AC Line Filter
Strip Length
mm (in.)
11.0 (0.43)
Kinetix 5100 AC Line Filter
Kinetix 5100 drive input
power connections for
three-phase operation.
Kinetix 5100 drive input
L1
power connections for
L2
single-phase operation.
L3
Terminal
Torque Values
N•m (lb•in)
1.8 (15.58)
3.4 (30.1)
Terminal
Torque Values
N•m (lb•in)
1.8 (15.58)
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kinetix 5100 ac 2198-db127-fKinetix 5100 ac 2198-db310-fKinetix 5100 ac 2198-db324-fKinetix 5100 ac 2198-db335-fKinetix 5100 ac 2198-db356-f

Table of Contents