„Master / Slave function„ 8
Der Bewegungsschalter kann als MASTER oder als SLAVE
eingestellt werden (siehe Schaltung Seite 6).
If the SLAVE function is desired, set the rotary switch 8
D
to the SLAVE position.
In addition, connect the terminals P 5 of the motion
sensors with each other.
Up to 10 SLAVE motion sensor can be connected to one
GB
MASTER.
The maximum cable length may not exceed 100 m.
The motion sensor with MASTER function controls the
NL
values twilight threshold (brightness) and duty cycle
(shut-down time delay).
Slave function
F
For the motion detector that shall act as the SLAVE, set
the adjustment screw 8 to the SLAVE position.
Switch-off warning
I
Press button  1x. A brief tone sounds.
Deactivate switch-off warning:
P
Press button  again 1x. Two brief tones sound.
When the switch-off warning is activated, a short acou-
stic signal is emitted immediately before the consumers
are switched off with different numbers of tones:
24
Function test
Set the adjustment screw 9 to „shortest duty cycle"
and twilight threshold 8 to „day operation".
Pass through the detection range transversally 2 .
The connected load, e.g. lamp should switch on.
After expiration of the set duty cycle, the lamp should
switch off again.
After a successful function test, set the desired parame-
ters (twilight threshold 8 , duty cycle 9 ) for constant
operation.
Manual ON (button activation)
For this, connect one or more buttons to the normally
open contact on the T 5 terminal of the motion sensor.
Press the button (normally open contact) and switch
the motion sensor ON (regardless of the set twilight
threshold).
The motion detector switches off again in accordance
with the set duty cycle.