Installation and Adjustment Instructions
Please read carefully!
No iabiIity can be accepted for damage
caused by improper use of the captor!
4.0 Adjustment Procedure
4.1 Zero point adjustment in stationary
medium:
Adjust
potentiometer
5 minutes so that Ia = 4 mA.
i.e. if Ia > 4 mA turn pot. P2 slowly to the left
if Ia < 4 mA turn pot. P2 sowIy to the right.
4.2 Adjustment of measurement range at the max. flow rate
which is to correspond to 20 mA output: After 3 minutes at max. flow-rate turn
pot. P1 until Ia = 20 mA.
i.e. if Ia > 20 mA turn pot. Pl slowly to the right
if: Ia < 20 mA turn pot. P1 slowly to the left.
4.3 Check Zero Point and Range
Check zero and range adjustments as in points 4.1 and 4.2 and correct any
discrepancies as necessary.
4.4 LED indicates operation within measurement range, and switches oft when
flow speed is out ot the adjusted range (Ia>2OmA).
S e n s o r s L t d . · S t r o h d e i c h 3 2 · D - 2 5 3 7 7
K o l l m a r
P2
after
T e l . : + 4 9 4 1 2 8 - 5 9 1
Technical data subject to alteration! Rev. AB / 20.08.15
vent-captor
Typ 3202.30 (3205.30)
Installation and Adjustment Instructions
Please read carefully!
No iabiIity can be accepted for damage
caused by improper use of the captor!
S e n s o r s L t d . · S t r o h d e i c h 3 2 · D - 2 5 3 7 7
K o l l m a r
T e l . : + 4 9 4 1 2 8 - 5 9 1
Technical data subject to alteration! Rev. AB / 20.08.15

Advertisement

loading

Summary of Contents for CAPTOR vent-captor 3202.30

  • Page 1 No iabiIity can be accepted for damage Please read carefully! No iabiIity can be accepted for damage caused by improper use of the captor! caused by improper use of the captor! 4.0 Adjustment Procedure 4.1 Zero point adjustment in stationary...
  • Page 2 2.5 Installation of Type 3205.30 1.0 vent-captor Type Number Fit the 0-ring over the front of the vent-captor and push back to the flange. 1.1Type 3202.30: type number printed on housng lnsert the vent-captor into the previously mounted 1“-flifing and secure with the 1.2 Type 3205.30: type number indicated on adhesive label...