Capability Setting; Control Item; Appendix; Apéndice - Tripp Lite MODBUSCARDSV Operation Manual

Programmable modbus card for sv, svx, s3mx 100-200k 3-phase ups systems
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1
Operation

2. Capability Setting

Holding Register (Range 0x000E - 0x000F, Read Function 0x03, Write Function 0x10)
Addresses start at 0 and are numbered 1-16 address as 0-15.
The Write function writes to ENABLE/DISABLE in a remote device. A specified constant in the data field requests the ENABLE/
DISABLE state.
Address
Hex
Decimal
Description
Bit15 = Enable/disable audible alarm
Bit10 = Enable/disable auto-Restart
Bit7 = Enable/disable code start
0x000E
14
Bit6 = Enable/disable bypass forbidding
Bit3 = Enable/disable bypass when device turn off
Bit1 = Enable/disable high efficiency mode
Bit15-Bit 13 = Reservation
Bit12 = Enable/disable converter mode
0x000F
15
Bit11-Bit8 = Reservation
Bit7 = Enable/disable period self test Z
Bit0-Bit5 = Reservation

3. Control Item

Holding Register (Read Function 0x03, Write Function 0x10)
Addresses start at 0 and are numbered 1-16 address as 0-15.
The Write function writes to ENABLE/DISABLE in a remote device. A specified constant in the data field requests the ENABLE/
DISABLE state.
Address
Hex
Decimal
Description
Bit15 = Silence buzzer beep (audible alarm)
Bit14 = buzzer beep open (audible alarm)
Bit13 = Test until battery low
Bit12 = Remote turn off UPS
0x001A
26
Bit11 = Remote turn on UPS
Bit10 = Cancel shutdown
Bit9 = Cancel test
Bit8 = 10 second test
Bit3-Bit 0 = Reservation
Bit5-Bit 11 = Reservation
0x001B
27
Bit10 = UPS turn to bypass
Bit15 = EPO function open
Bit14 = EPO function close
Bit13 = Mode output frequency 50 Hz
Bit12 = Mode output frequency 60 Hz
0x0422
1058
Bit11 = Charger On
Bit10 = Charger Off
Bit9 = Enable independent battery
Bit8 = Disable independent battery
Value 0/Value 1
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
N/A
0:FALSE/1:TRUE
N/A
0:FALSE/1:TRUE
N/A
Value 0/Value 1
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
N/A
N/A
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
0:FALSE/1:TRUE
3
Register Value
E:8000 / D:7FFF
E:4000 / D:BFFF
E:200 / D:FDFF
E:100 / D:FEFF
E:40 / D:FFBF
E:10 / D:FFEF
E:8 / D:FFF7
E:4 / D:FFFB
E:2 / D:FFFD
E:1000 / D:EFFF
N/A
Alarm Description
Y:8000
Y:4000
Y:2000
Y:1000
Y:800
Y:400
Y:200
Y:100
N/A
N/A
Y:0400
Y:8000
Y:4000
Y:2000
Y:1000
Y:0800
Y:0400
Y:0200
Y:0100

Advertisement

Table of Contents
loading