Peter electronic VersiSafe Assembly And Commissioning Instructions

Safety standstill monitor

Advertisement

Quick Links

e l e c t r o n i c
Assembly- and Commissioning Instructions
Safety Standstill Monitor
VersiSafe
Quality is our Drive.

Advertisement

Table of Contents
loading

Summary of Contents for Peter electronic VersiSafe

  • Page 1 Assembly- and Commissioning Instructions Safety Standstill Monitor VersiSafe Quality is our Drive.
  • Page 2: Table Of Contents

    VersiSafe as per 09/18 17800.10001 Table of Contents Page Safety remarks Conformity EC Declaration of Conformity Function General description Applications Features Funtion Functional diagram Functional description Technical data Input (L1 - L2 - L3) Output General data Dimensions Characteristics Commissioning...
  • Page 3 VersiSafe These commissioning instructions were prepared with great care. Nevertheless, PETER electronic GmbH & Co. KG does not assume liability for damage resulting from mistakes possibly contained in this manual. Technical changes that serve to improve the product are subject to change without notice.
  • Page 4: Safety Remarks

    This manual must be read and understood before installation and setup. The VersiSafe is suitable to operate as a part in safety circuits of a plant or machine. Usually also other components are part of these circuits. It is the liability of the builder of the plant or machine to guarantee the complete safety function by selecting the correct components, wiring and operation.
  • Page 5: Ec Declaration Of Conformity

    (authorized representatives of the manufacturer / companies placing the product on the market that are established within the Community) Name / Address: PETER electronic GmbH & Co. KG Bruckäcker 9 92348 Berg hereby declares that the following product (device, component, unit) in the version as supplied...
  • Page 6: Function

    VersiSafe Function The VersiSafe is connected to the motor terminals and measures the induced back emf voltage of a freewheeling motor. 2 redundant measuring channels are used (L2-L1 and L3 L1). If the back emf voltage drops to 0 simultaneously in both channels this indicates standstill and the output relay is energised.
  • Page 7: General Description

    • Width 45 mm Funtion The VersiSafe can be used for standstill detection on all 3-phase, single phase and DC motors, that generate a voltage caused by remanence when freewheeling. As the voltage level Uan for standstill monitoring and the time delay t , after detection of standstill until the safety relays are switched on, are adjustable, the function can be adopted to different motors and applications.
  • Page 8 VersiSafe Terminals and settings L1 - L2 - L3: connection to monitored motor 11 - 12: safety contacts (NO) 23 - 24, 33 - 34, 43 - 44: safety contacts (NC) 53 - 54: monitoring contact (C/O) X1 - X2:...
  • Page 9: Functional Diagram

    If semiconductor monitoring outputs are used, their supply voltage must be connected to A3(+)- A motor connected to the terminals L1-L2-L3 of the VersiSafe generates a voltage when running down (motor is switched off). The voltage is proportional to the speed and caused by residual magnetism (remanence).
  • Page 10: Technical Data

    This is done with the feed back circuit (terminals X1-X2) to which the NC contacts of the contactors/components must be connected. (see also wiring diagrams). The VersiSafe will only enable its safety output if the feedback loop X1-X2 is closed while stand- still is detected, i.e. the external contactors/components are in initial state (NC contacts are closed).
  • Page 11: Output

    U at standstill: 0,4 ... 0,8 s + adjustable t Output Contacts (saftey contacts) VersiSafe 230VAC: 3 NO contacts, 1 NC contact The NC contacts 11-12 can only be used for monitoring. relay, positive guide Contact type: Nominal output voltage: AC 250 V 5 A (bis 40°C)
  • Page 12 VersiSafe Contacts 11/12, 23/24, 33/34, 43/44 against each others: 4 kV / 2 Indicator contact 53/54 against all others: 4 kV / 2 Semiconductor outputs A3+/ ON / ERR / A4 against all others: 6 kV / 2 Auxiliary voltage A1 / A2...
  • Page 13 VersiSafe Safety related data Values according to EN ISO 13849-1: Category: MTTF 99,0 d/a (days/year) h/d (hours/day) 28,8E+03 s/Zyklus Zyklus /8 h (hours) Values according to IEC EN 62061 / IEC EN 61508 / IEC EN 61511: SIL CL: IEC EN 62061...
  • Page 14 VersiSafe UL -Data The safety functions were not evaluated by UL. Listing is accomplished according to requirements of Standard UL 508, „general use apllications“. Measuring-/Motor voltage: max. AC 600V Ambient temperature: -25 ... +60°C, (+40°C with max. contact current, see Derating)
  • Page 15: Dimensions

    VersiSafe Dimensions All dimensions in mm. Standard type VersiSafe AC 230 V 50/60 Hz Article number: 27800.69000 • Safety output: 3 NO contacts, 1 NC contact • Auxiliary voltage U AC 230 V • Response value U 20 ... 400 mV •...
  • Page 16: Characteristics

    Derating curve for contact currents of safety contacts Commissioning Terminal connections The VersiSafe has to be connected according to connection examples or in a similar way. The connection of DC- motors is made as with single phase AC-motors. L1 - L2 - L3...
  • Page 17: Setup And Setting

    VersiSafe A 1 - A2 Connection of the auxiliary supply, recommended fuse : 2A. A3+ / A4 DC 24 V supply (12 … 30 V) for the semiconductor monitoring outputs „ON“ and „ERR“, if these are used. 11-12, 23-24, 33-34, 43-44 Safety output contacts, connection according to the connection examples or similar.
  • Page 18: Special Applications And Operation Notes

    An open connection will result in broken wire indication and disable the safety contacts. When connecting the VersiSafe to a 3-phase motor with star delta starter the star contactor must be energised while the motor is switched off, in order to achieve closed circuits between L1-L2-L3...
  • Page 19 If it is not possible to switch in the star contactor after the motor is switched off, the measuring inputs of the VersiSafe have to be connected like a single phase connection. L2-L3 are bridged and connected to one end of a motor winding and L1 to the other end of the same winding.
  • Page 20: Failure Monitoring

    Failure monitoring Types of error The VersiSafe includes a number of facilities to to detect failures that could influence the safety function of the module. The failure check is carried out on power up of the unit and in cycles during normal operation.
  • Page 21: Failure Indication

    VersiSafe Potentiometer error To achieve the required safety when adjusting the voltage threshold for standstill detection, ech setting function is realised with 2 potentiometers having one common setting knob. If on 2 corres- ponding potentiometers a different setting is detected the potentiometer error U or t displayed.
  • Page 22: Failure Treatment

    VersiSafe undervoltage at U wire-break/offset on L2 wire-break/offset on L3 failure in feedback circuit X1-X2 simultaneity failure signal L2/L3 potentiometer error potentiometer error M9648_c Failure treatment Failure: The unit enables the safety outputs while the motor is still turning (LED OUT“ lights green).
  • Page 23 VersiSafe 1. LED „UH“ lights green? If yes, go to 2. If no, U has undervoltage or the unit has an internal device failure. (Internal failures can occur in the case of undervoltage, welded safety output contacts or seldom because of interference) switch supply voltage off and on.
  • Page 24 LED flashes code 3 the unit has detected broken wire or DC voltage offset on measuring input L3 In the 2 last cases the wiring between VersiSafe terminals L1-L2-L3 and the motor terminals has to be checked on interruption. Possibly the interruption comes from disre- garding the operating remarks for motors with switchable windings (see remarks).
  • Page 25: Connection Diagramm

    VersiSafe Connection diagramm with 3-phase motor suitable up to SIL3, Performance Level e, Cat. 4 PE L1 L2 L3 motor contactor A3+ A4 LH5946 ON ERR M9649_b with single-phase motor suitable up to SIL3, Performance Level e, Cat. 4 PE N...
  • Page 26: Typical Connection Combination With E-Stop

    VersiSafe Typical connection combination with E-Stop suitable up to SIL3, Performance Level e, Cat. 4 Entriegelung Unlock Déverrouillage Open Ouvert Not-Aus E-Stop Arrêt d'urgence S11 S12 S22 13 Not-Aus-Modul Stillstandswächter E-Stop-Modul Stand-Still-Monitor Module d'arrêt d'urgence Détecteur de vitesse zéro LG5925...
  • Page 27: Typical Connection Combination With Star Delta Timer, 2-Channel Connection Of The Measuring Inputs

    VersiSafe Typical connection combination with star delta timer, 2-channel connection of the measuring inputs suitable up to SIL3, Performance Level e, Cat. 4 fuse main switch BC7936N LH5946 M9967_a d = star delta timer N = mains contactor = star-contactor...
  • Page 28: Typical Connection Combination With Star Delta Timer, 3-Channel Connection Of The Measuring Inputs

    VersiSafe Typical connection combination with star delta timer, 3-channel connection of the measuring inputs suitable up to SIL3, Performance Level e, Cat. 4 fuse main switch LH5946 M9969_a d = star delta timer With “3-phase” connection of LH5946 the star contactor ( ) N = mains contactor has to be closed after the motor is switched off to detect standstill.
  • Page 29 VersiSafe...

Table of Contents