Motion & Light Sensor Kit HBAS47
Installation Instructions
For Round High Bay Fixtures
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION
Motion Sensor_Installation Instructions_v1.indd 1
2/16/2018 8:37:35 AM

Advertisement

loading

Summary of Contents for LITETRONICS HBAS47

  • Page 1 Motion & Light Sensor Kit HBAS47 Installation Instructions For Round High Bay Fixtures PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION Motion Sensor_Installation Instructions_v1.indd 1 2/16/2018 8:37:35 AM...
  • Page 2: Safety Instructions And Warnings

    SAFETY INSTRUCTIONS AND WARNINGS WARNING: READ CAREFULLY BEFORE INSTALLING RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE. Sensor must be wired in accordance with the National Electrical Code and all applicable local codes. Risk of fire or electric shock. Sensor installation requires knowledge of luminaire electrical systems. If not qualified, do not attempt installation.
  • Page 3: What Comes In The Box

    Motion Sensor base product comes with following standard parts: Adjustable Hinge Bracket Sensor Motion and Light Sensor Kit HBAS47 PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION (2) Self-tapping screws (1) Installation Instructions Before Installation, carefully remove all parts from the packaging.
  • Page 4 MOTION SENSOR INSTALLATION Turn off power to fixture. Look for 2 holes on curved surface of housing where bracket of sensor will be installed. Install bracket with help of 2 self- tapping screws. Remove pre-connected input cable with 3 stripped wires by twisting connector counter clockwise.
  • Page 5 MOTION SENSOR INSTALLATION Mate male connector of sensor and pre-connected input cable (removed in step 3) or any chosen Litetronics cable accessory by twisting clockwise. Connect 0-10V gray and purple wire of High Bay and sensor with help of wire nuts (waterproof) provided with High Bay.
  • Page 6: Motion Sensor

    MOTION SENSOR MOTION SENSOR INSTALLATION INSTALLATION MC031V SENSOR SETTINGS By selecting the combination on the DIP switch, sensor data can be precisely set for each specific application. Detection area Detection area can be reduced by selecting the appropriate 100% combination on the DIP switches. —...
  • Page 7: Troubleshooting

    MOTION SENSOR MOTION SENSOR INSTALLATION INSTALLATION TROUBLESHOOTING REASON CAUSE REMEDY The load will not Incorrect daylight sensor setting selected. Adjust setting. illuminate Load had failed. Replace load. Power is switched off. Switch on. The load is permanently Continuous movement in the detection area. Check detection area setting.