Important Notes Usage for the intended purpose The logic unit SRL 63-a may be used in steam boiler plants only in conjunction with external low-level alarms or high-level alarms for monitoring the separate flushing of the connecting lines to the measuring pot.
Explanatory Notes Scope of supply SRL 63-a 1 Logic unit for monitoring, in a field case for wall mounting 1 Installation manual Description For the installation of low-level limiters of “high-integrity design” in measuring pots mounted outside of the boiler, it is imperative that the periodic purging of the connecting lines to the boiler be monitored properly.
Explanatory Notes – continued – Function – continued – The logic unit monitors the following times: Interval time: This is the time interval at which, depending on the mode (24h / 72h operation), the connecting lines have to be purged. Standby period: The purging process must be initiated during this time.
Technical Data SRL 63-a Inputs 5 volt-free contacts from the limit switches of the valves 1 volt-free contact from a second SRL which may be mounted at the same boiler (interlock) 1 volt-free contact from the low-level limiter Outputs 2 volt-free change-over contacts each for bypassing/deactivating the safety circuit Thermal current I : 4 A, switching capacity acc.
Technical Data – continued – Name plate / marking – Designation SRL 63-a Mains voltage / Safety note – Power consumption / – 230 V 50 / 60 Hz 26 W IP 65 Protection – Range of application Tamb = 55 °C ( 131°F) Safety circuit –...
Installation Installing the logic unit SRL 63-a The case of the logic unit is intended for wall mounting; it should be installed near the external measuring pot. Functional Elements SRL 63-a Interval: Control panel Remaining: Fig. 4...
Electrical Connection Connecting the terminal strips Connect the terminal strips as shown in the wiring diagram. The measuring pot is provided with three shut-off valves. Valves D and E are each equipped with two limit switches, for the “OPEN” position (D1 / E1) and for the “CLOSED” position (D2 / E2). The drain valve F is only fitted with one limit switch, for the “CLOSED”...
Basic Setting Factory setting Logic unit SRL 63-a The logic unit for monitoring is delivered with the following factory settings: Interval time: 24 hours Standby period: 1 hour Purging time: 5 minutes Voltage of safety circuit: 230 V AC Start-up, Operation, Alarms and Testing...
Page 13
Start-up, Operation, Alarms and Testing – continued – SRL 63-a – continued – Operation Interval time is running. No pilot lamp is alight. Trouble-free operation Interval time expires and Green pilot lamp “Standby” is Standby period is running. begins again.
Cursor picture in the PLC display Danger The terminal strips of the logic unit SRL 63-a are electrically live during operation! This presents the danger of electric shock. Before working on the terminal strips (assembly, disassembly, connecting the cables),...
Page 15
Remedy: Switch on the mains voltage and resume the purging process. Decommissioning SRL 63-a Cut off the power supply to the logic unit, undo all the electrical connections and pull the cables out of the glands. Remove the logic unit.
Page 20
Agencies all over the world: www.gestra.de GESTRA AG Münchener Straße 77 28215 Bremen Germany Telefon +49 421 3503-0 Telefax +49 421 3503-393 E-mail info@de.gestra.com www.gestra.de 818588-04/06-2016cm (808615-07) · GESTRA AG · Bremen · Printed in Germany...