olympia electronics GR-24/12-1 Manual

Stabilized power supply 12v dc

Advertisement

Quick Links

GR-24/12-1
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
SEALED LEAD ACID BATTERIES (Pb)
OUTPUT
BATTERY PROTECTION
INDICATIONS LED's
CHARGING TIME
AUTONOMY (with maximum Load)
REMOTE INPUT VOLTAGE RANGE
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Thank you for purchasing this product of
O l y m p i a E l e c t r o n i c s . A E u r o p e a n
manufacturer.
GENERAL
The GR-24/12-1 is a stabilized power supply
continuous operation that provides a voltage of
12V DC to independent devices (according to
the device). The output network is stabilized to
the 13,5 V DC with a maximum current 4Α.
It provides continuous power to the external
devices, with the incorporated power supply as
long as the mains power supply does not fail.
In case of mains failure the device gives power
to the external devices from the included
battery.
In fire detection systems it is used when the
detector's power consumption is greater than
the maximum panel that the panel can provide.
It is also used to power any other device that
require 12 V DC and autonomous operation.
The device includes the SW1 switch which
activates or deactivates the output as long as
you desire.
The green indication LED indicates the output
status. The jumper LOCAL/REMOTE is also
used according to the input REMOTE in the
respective terminal blocks and concerns the
output status. If no external device to control
the GR-24/24-1 output is connected then the
jumper must be placed in pins 1-2 and the
output control can be done with the switch
SW1. If you want to control the output from an
external device,
then the jumper must be placed in pins 2-3,
Page 1 from 2
High Quality European based Manufacturers
STABILIZED POWER SUPPLY 12V DC
TECHNICAL CHARACTERISTICS
Network: 13.5V/ 4A (max.) / Battery : 12V / 4 A (max.)
Mains/battery charging red LED, output activation green LED
EN 55015, EN 61547, EN 60950-1, EN 61000-3-2, EN 61000-3-3
Bayblend FR3010, transparent polycarbonate
the switch SW1 in the ON position and the
control signal must be connected to the
REMOTE terminal blocks. In the input, when
the voltage exceeds 6V, then the GR-24/12-1
output is active and when the voltage remains
under 6V the output remains deactivated.
Autonomy calculation example
The autonomy of the device is proportional to
the battery (i.e 7Ah for GR-24/12-1 and
inversely proportional to the consumption of
the number of detectors. If you want to connect
10 devices that consume 200mA from the GR-
2 4 / 1 2 - 1 , t h e n t h e a u t o n o m y w i l l b e
approximately 6 hours, and if we want to
connect 20 devices, the autonomy will be
approximately 3 hours. In this way we can
calculate how many detectors will connect to
the power supply and how much autonomy we
have. The device has an electronic fuse that
protects its output from short circuits that could
cause serious problems.
electronic safety output is disconnected
permanently and for restoring the functioning of
the device will be restored in a shortcircuit and
to disconnect the network and the battery for a
few seconds.Immediately after can function
normally.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the
total amount of the line's power load.
85-265V AC/50-60Hz
163 VA
2x12V/7Ah (not included)
From overcharge and full discharge
24 h
3 h
6-30V DC / 1.5mA (maximum)
IP 42
o
0 to 40 C
Up to 95%
300 x 95 x 230 mm
5150gr.
3 years (1 year for the battery)
When activated the
923024005_23_006

Advertisement

loading

Summary of Contents for olympia electronics GR-24/12-1

  • Page 1 REMOTE terminal blocks. In the input, when GENERAL the voltage exceeds 6V, then the GR-24/12-1 The GR-24/12-1 is a stabilized power supply output is active and when the voltage remains continuous operation that provides a voltage of under 6V the output remains deactivated.
  • Page 2: Installation Instructions

    3. I s not allowed to discard batteries in to after the mains interruption. common trash bins, they must be 1. Follow the step 1 of the installation discarded only in battery recycling procedure. 2. Disconnect the cables and points. Do not incinerate. remove the old battery.