Step 1 – Feed wires through hole in
rear of sensor.
Configuration Instructions for ALL Tasseron Humidity Sensors:
For optional passive temperature sensor, connect one wire to each quick connect terminal labeled "TEMP" (non‐polar).
Instructions for 4 to 20 mA Output DIP Switch Configuration
Terminal
Function
TEMP
2‐pole connection for optional passive temperature sensor (no polarity)
VIN
Main power – 24V DC power supply recommended
4‐20mA
Current mode signal output
COM
(not used in current mode)
VOUT
(not used in current mode)
Step 1 – Be sure the white Output mode DIP switches are in the proper configuration. For 4‐20mA output, DIP switch #2
must be in the RIGHT position. Switch #1 has no function in this mode.
Step 2 – Terminate control wires in quick connects as indicated in the table above. Only 2 wires are needed for 4‐20mA
output mode; main power supply and signal output. These wires terminate at "VIN" and "4‐20mA".
Step 3 – Power on control.
Instructions for 0‐5V or 0‐10V Output DIP Switch Configuration
Terminal
Function
TEMP
2‐pole connection for optional passive temperature sensor (no polarity)
VIN
Main power – 24V DC power supply recommended
4‐20mA
(not used in voltage mode)
COM
Common
VOUT
Voltage signal output
Step 1 – Be sure the white Output mode DIP switch is in the proper configuration. For 0‐5V output, DIP switch #1 must be
in the LEFT position and DIP switch #2 must be in the RIGHT position. For 0‐10V output, both #1 and #2 DIP switches must
be in the RIGHT positions.
Step 2 – Terminate control wires in quick connects as indicated in the table above. Three wires are needed for Voltage
output mode; main power supply (VIN), Common (COM), and signal output (VOUT).
Step 3 – Power on control.
Step 2 ‐ Mount with screws, then
make connections.