Tasseron Q-Duct SAFE Installation Instructions page 2

Humidity sensors

Advertisement

Step 1 – Feed wires through hole in 
rear of sensor.   
 
 
 
 
 
 
 
Configuration Instructions for ALL Tasseron Humidity Sensors: 
For optional passive temperature sensor, connect one wire to each quick connect terminal labeled "TEMP" (non‐polar). 
Instructions for 4 to 20 mA Output                                                                          DIP Switch Configuration 
Terminal 
Function 
TEMP 
2‐pole connection for optional passive temperature sensor (no polarity)
VIN 
Main power – 24V DC power supply recommended
4‐20mA 
Current mode signal output 
COM 
(not used in current mode) 
VOUT 
(not used in current mode) 
 
Step 1 – Be sure the white Output mode DIP switches are in the proper configuration. For 4‐20mA output, DIP switch #2 
must be in the RIGHT position. Switch #1 has no function in this mode. 
Step 2 – Terminate control wires in quick connects as indicated in the table above. Only 2 wires are needed for 4‐20mA 
output mode; main power supply and signal output. These wires terminate at "VIN" and "4‐20mA".  
Step 3 – Power on control. 
Instructions for 0‐5V or 0‐10V Output                                                                     DIP Switch Configuration 
Terminal 
Function 
TEMP 
2‐pole connection for optional passive temperature sensor (no polarity) 
VIN 
Main power – 24V DC power supply recommended 
4‐20mA 
(not used in voltage mode) 
COM 
Common 
VOUT 
Voltage signal output 
                                                                                                 
Step 1 – Be sure the white Output mode DIP switch is in the proper configuration. For 0‐5V output, DIP switch #1 must be 
in the LEFT position and DIP switch #2 must be in the RIGHT position. For 0‐10V output, both #1 and #2 DIP switches must 
be in the RIGHT positions. 
Step 2 – Terminate control wires in quick connects as indicated in the table above. Three wires are needed for Voltage 
output mode; main power supply (VIN), Common (COM), and signal output (VOUT).  
Step 3 – Power on control. 
   Step 2 ‐  Mount with screws, then 
make connections. 
 
 
 
140 Choate Circle ▪ Montoursville, PA 17754 ▪ 570.601.1971 
sales@tasseronusa.com ▪ www.tasseronusa.com 
 
                                                  0‐5V Output                                    0‐10V Output 
 
Step 3 – Snap on cover. Depress 
hooks through vents with tool 
to remove. 
 