INSTALLATION GUIDE AT THE
SEASIDE
CAUTION
!
• Air conditioners should not be installed in areas where
corrosive gases, such as acid or alkaline gas, are produced.
• Do not install the product where it could be exposed to sea
wind (salty wind) directly. It can result corrosion on the
product. Corrosion, particularly on the condenser and
evaporator fins, could cause product malfunction or inefficient
performance.
• If outdoor unit is installed close to the seaside, it should avoid
direct exposure to the sea wind. Otherwise it needs additional
anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
If the outdoor unit is to be installed close to the seaside, direct expo-
sure to the sea wind should be avoided. Install the outdoor unit on the
opposite side of the sea wind direction.
Sea wind
Sea wind
In case, to install the outdoor unit on the seaside, set up a windbreak
not to be exposed to the sea wind.
Windbreak
Sea wind
- It should be strong enough like concrete to prevent the sea wind
from the sea.
- The height and width should be more than 150% of the outdoor unit.
- It should be keep more than 70 cm of space between outdoor unit
and the windbreak for easy air flow.
Select a well-drained place.
• If you can't meet above guide line in the seaside installation,
please contact LG Electronics for the additional anticorrosion
treatment.
• Periodic ( more than once/year ) cleaning of the dust or salt
particles stuck on the heat exchanger by using water
The below Installation guide is limited applicable only for model
ARUN60GS2A
Installation Guide for EN 61000-3-12:2005
This equipment complies with IEC 61000-3-12 provided that the
short-circuit power Ssc is greater than or equal to 910 kVA at the
interface point between the user's supply and the public system. It
is the responsibility of the installer or user of the equipment to en-
sure, by consultation with the distribution network operator if nec-
essary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to 910 kVA."
The below Installation guide is limited applicable only for model
ARUN50GS2A
Installation Guide for EN 61000-3-12:2005
This equipment complies with IEC 61000-3-12 provided that the
short-circuit power Ssc is greater than or equal to 1497 kVA at the
interface point between the user's supply and the public system. It
is the responsibility of the installer or user of the equipment to en-
sure, by consultation with the distribution network operator if nec-
essary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to 1497 kVA."
The below Installation guide is limited applicable only for model
Model : ARUN40GS2A
Installation Guide for EN 61000-3-12:2005
This equipment complies with IEC 61000-3-12 provided that the
short-circuit power Ssc is greater than or equal to 1354 kVA at the
interface point between the user's supply and the public system. It
is the responsibility of the installer or user of the equipment to en-
sure, by consultation with the distribution network operator if nec-
essary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to 1354 kVA."