MAINTENANCE

With minimal but important maintenance, the F6-DP can provide many seasons of reliable
service� After each use, clean the F6-DP with a damp cloth to remove dirt and oils�
Do not use gasoline or other hazardous solvents to clean F6-DP; this can damage the
plastic enclosure� Standard household detergent or isopropyl alcohol may be used, but
do not allow liquid to penetrate the outer case�
Make sure the inlet and discharge ports are protected during transit and storage; keep the
inner diameter and the outer threads clear and clean�
NOTE: For best results, leave the filter connected to the inlet port,

TROUBLESHOOTING

PROBLEM
F6-DP will not turn
on; compressor does
not start
Compressor starts,
but falters within
minutes; pressure
indication on HP
gauge is high
Compressor stops
intermittently
F6-DP OPERATING MANUAL
and change the filter regularly�
CAUSE
1. Power cord is not attached
2. No voltage at receptacle
3. Circuit breaker has opened
4. Discharge pressure is too high;
HP switch has opened
5. Electronics failure in motor
1. Recovery tank valve is not open
2. Discharge hose blocked
3. Air in system/tank
1. Vapor pressure of refrigerant in
tank is close to HP trip point
2. Thermal overload switch in
compressor is activating
JB INDUSTRIES
ACTION
1. Attach power cord
2. Verify voltage at job site
3. Identify cause of breaker
activation, rectify and reset
4. Reduce pressure; rotate V2 to
Purge, then back to Recovery
5. Factory service required
1. Open tank valve
2. Check and clear blockage
3. Bleed air from system/tank
1. Reduce tank temperature
2. Reduce amount of liquid being
pumped; let machine cool
before proceeding
13