CLA-VAL X117E Installation Operation & Maintenance

Contact-less valve position transmitter

Advertisement

Quick Links

X117E Contact-Less Valve Position Transmitter
Thank you for purchasing a Cla-Val Model X117E Contact-less
Valve Position Transmitter. With proper maintenance, the X117E
will perform indefinitely and provide very accurate and reliable
valve control. It is built with the latest technology utilizing the high-
est quality components. The X117E is a unique electronic contact-
less valve positon indicator. Its software allows easy programma-
ble control features. The graphic interface is user friendly and
offers an easy way to calibrate your automatic control valves.
Wiring Diagram
X117E Contact-Less Valve Position Transmitter
Terminal strip not
supplied for
Illustration
purpose only
Installation / OPERATION / MAINTENANCE
MODEL
Technical Data
Sensor:
Contact-less magnet sensor
24 VDC +/- 10%, min. 20 mA, normal 40
Power:
mA, max. 60 mA
4-20 ma, not isolated, protected, same com-
(*)Outputs
mon, output charge ≤ 500 Ω
Accuracy:
< 1% Full scale
Operating range: (-20˚C to +65˚C)
Protection:
IP68
Interface:
Plug & Play / NT / 2000 / XP / Vista
Consumption:
6 Watt maximum
(*) The input dry contact and analogue output has the same
common or earth but are not individually isolated.
The X117E uses a magnetic sensor, take care to keep the installa-
tion free of any magnetic fields (transformers, motors, high
power supply, ect...)
Connection
output
Power Supply 24 VDC
+ 24V
0
V
Black Red
Output
Charge
Max. 500

Installation Instructions

1) All installation, adjustment and maintenance should be
carried out by a competent electrician.
2) Do not exceed the maximum ratings given in the
specifications and printed on label.
3) The electrical connections should be made as described in
the userʼs manual.
4) Before any maintenance operation the main power should
be turned off
Do not attempt to open the product
as this will invalidate the warranty!
X117E

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the X117E and is the answer not in the manual?

Questions and answers

Summary of Contents for CLA-VAL X117E

  • Page 1 (*) The input dry contact and analogue output has the same common or earth but are not individually isolated. The X117E uses a magnetic sensor, take care to keep the installa- tion free of any magnetic fields (transformers, motors, high power supply, ect...)
  • Page 2 Before the Firmware update, save your program to your PC. 1) Connect the USB cable to the USB connection of your PC. 2) Connect the X117E to the USB cable. 3) Select “Read Parameters” to read X117E settings and record output parameters. 4) Select “Firmware update” in “Parameters”.
  • Page 3 Installation If connected to one or more X117E or another e-line product, click on "View All" and select the e-Lift you would like to commu- nicate with from the list (see picture below) then click once on left mouse button.
  • Page 4 Connect to 24 VDC power supply. Connect the USB cable to your PC. Connect your PC to the X117E with the USB cable. Start the X117E Cla-Val software. Enter the valve’s lift, and then click on "Lift". The valve opening information is now ready in inches or mm.
  • Page 5 Click on "Valve open". Click on "Read parameters". Calibration is done. Adjustment of Alarms The X117E incorporates two adjustable lift level alarms and a hysteresis alarm level. Enter the requested percentage for the alarms and hysteresis, click on "Program" (1). “High Level”...
  • Page 6 Reading Parameters "Read parameters" (1) to see the valve position. Click on This mode displays how the valve was Calibrated. Dynamic Reading click on "Dynamic Update" to enable, and click once more to disable. This mode displays the dynamic valve position, Page 6...
  • Page 7 Calibration without a PC Calibration ou can also calibrate the e-Lift, without a computer either using the CLA-VAL magnetic screwdriver or a low power magnet without affecting the signal position sensor. 1- Close the valve. 2- Put the magnet on the top of the e-Lift (see photo below).
  • Page 8: Troubleshooting

    If the X117E LED is off, the magnet is out of the sensor zone. b. If the X117E LED is green, the magnet is in the 1st magnet sensor zone. c. If the X117E LED is red, the magnet is in the 2nd magnet sensor zone.

Table of Contents