Technische Daten - Airflow PT-LE Operating Instructions Manual

Differential pressure transducer
Table of Contents

Advertisement

10.

Technische Daten

Linearity:
t.c. offset:
t.c. span:
Accuracy:
Measuring ranges:
Min. response time:
Pressure ports:
Output signals:
Switching contact (optional): max. 230 VAC, 6 A; min. 500 mW
Display (optional):
Overload range:
Storage temperature:
Working temperature:
Supply voltage:
Power consumption:
Operating position:
Housing:
Protection class:
Installation:
Testing:
10
2.0 % of the measuring range limiting value
+/- 0.1 %/°C
+/- 0.1 %/°C
2.0 % of the measuring range limiting value
+/-2.5 kPa (+/-250 Pa...2.5 kPa)
+/-10 kPa (+/-5.0 kPa...10 kPa)
+/-100 kPa (+/-20 kPa...100 kPa)
As an option, the customer can use a DIP-switch to select 4
pre-set measuring ranges.
20 ms
Nominal 4 or 6 mm width for hose
0/2...10 V or. (RL> 50 k Ohm)
0/4...20 mA (RL< = 500 Ohm)
4...20 mA (two-wire 17...32 V,RL< = 500 Ohm)
3½-digit LCD
from 2.5 kPa
50 kPa
2.5 kPa ... 10 kPa
> 10 kPa
200 kPa
-20°C...+70°C
-20°C...+60°C, with Display 0°C...50°C
24 VDC/VAC +/-15 % (no galvanic isolation)
15 ... 32 VDC (two-wire) (no relay output)
approx. 1 W
vertical preference
see drawing
IP 65
The appliance can be installed either on a top-hat rail or on a
wall with fastening holes
EN 61000-4-2, EN 61000-4-3...-6,
EN 61000-4-11, EN V50204
Operating Instructions PT-LE