J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-)4 to 20 mA Current Loop Output
to RTU Open
To wire return air enthalpy
Connect the 4-20 mA In terminal on the enthalpy switch/
receiver to the 4-20 mA Out terminal on the return air
enthalpy sensor. Connect the 24-36 VDC Out terminal on
the enthalpy switch/receiver to the 24-36 VDC In terminal
on the return air enthalpy sensor. (See Fig 10.)

Fire Shutdown

The fire shutdown input is provided for unit shutdown in
response to a fire alarm or smoke detector. The fire
shutdown input is dedicated to input 5 and tells the RTU
Open when to shutdown due to smoke detection or fire
alarm system. The normal condition for fire shutdown is
there is no fire alarm. The unit may have factory installed
smoke detector(s); refer to the base unit installation
instructions for details on any adjustments required during
unit installation. Fire shutdown is always factory
configured for a normally open smoke detector.
For field installation of a smoke detector see instructions
for that
specific accessory.
troubleshooting section for wiring at the unit's Central
Terminal Board (CTB).
S CTB - UNIT SHUTDOWN - 24v OUT = 24 VAC
source
S CTB - UNIT SHUTDOWN - Smoke Alarm = Signal
input to RTU Open
NOTE: Input 5 can also be wired into J5- 3.
Fig. 9 - Duct Relative Humidity Sensor Typical Wiring
sensor:--MP
See below and the
SPAN
ZERO
4-20
VAC
GND 0-5V
mA
or
or
VDC
0-10V

Filter Status

The filter status accessory is a field-installed accessory.
This accessory detects plugged filters. When installing
this accessory, the unit must have a free input (input 3, 5,
8, or 9). One of the dedicated functions (Humidistat, Fire
shutdown, Enthalpy, or Compressor safety) must not be in
use to configure Filter Status. Refer to the configuration
section for details on configuring inputs for specific
functions and state. Refer to Fig. 1 for wire terminations
at J5.

Fan Status

The fan status accessory is a field-installed accessory.
This accessory detects when the indoor fan is moving air.
When installing this accessory, the unit must have a free
input (input 3, 5, 8, or 9). One of the dedicated functions
(Humidistat, Fire shutdown, Enthalpy, or Compressor
safety) must not be in use to configure Fan Status. Refer
to the configuration section for details on configuring
inputs for specific functions and state. Refer to Fig. 1 for
wire terminations at J5.

Remote Occupancy

The remote occupancy accessory is a field-installed
accessory. This accessory provides an input to change the
units occupancy status. When installing this accessory, the
unit must have a free input (input 3, 5, 8, or 9). One of the
dedicated functions (Humidistat, Fire shutdown, Enthalpy,
or Compressor safety) must not be in use to configure
remote occupancy. Refer to the configuration section for
details on configuring inputs for specific functions and
state. Refer to Fig. 1 for wire terminations at J5.