Selector Switches - ABB SPAJ 111 C User Manual

Sensitive earth-fault relay.
Table of Contents

Advertisement

Settings

Selector switches

6
The setting values are shown by the three
rightmost digits of the display. An LED indica-
tor below each setting knob shows, when lit,
I
>/I
Start current of stage I
0
n
input. The setting range, i.e. 0,2...2 % x I
with switch SG1/2 and SG1/3.
t>
Operate time of stage I
characteristic (SG1/3 = 0). The setting range, i.e. 0.05...1.00 s, 0.5...10.0 s or 5...100 s, to
be selected with switch SG1/1 and SG1/2.
I
>>/I
Start current of stage I
0
n
input. The setting range, i.e. 1...8 % x I
with switch SG1/6 and SG1/7. Additionally, the setting infinite "∞" (displayed as - - -) can
be selected, rendering the stage I0>> inoperative.
t>>
The operate time of the I
or 0.5...10.0 s, is determined by the position of switch SG1/8.
Further, the checksum of switchgroup SG1 is
indicated on the display when the indicator
under the switchgroup is lit. In this way a check
can be carried out to prove that the switches
Additional functions required by individual
applications are selected by means of the pro-
gram selector switches of switchgroup SG1 lo-
Switch
Function
SG1/1
Selection of the setting range of the operate time t> of stage I
When SG1/1 = 0, the setting range of t> is 0.05...1.00 s
When SG1/1 = 1, the setting range of t> is 0.5...10.0 s.
SG1/2
Selection of the setting range of the low-set current stage I
SG1/3
SG1/2
SG1/3
0
1
0
1
SG1/4
Selection of the mode of operation of the operate signals TS1 and TS2.
When SG1/4 = 0, the operate signals return to the initial state (= the output relay
drops off), when the measuring signal causing the operation falls below the set start
level.
When SG1/4 = 1, the operate signals remain on (= the output relay operated),
although the measuring signal falls below the set start level. Resetting with command
V101 via the serial interface or by pressing the push-buttons STEP and RESET
simultaneously, which also erases the recorded information.
SG1/5
Not in use.
which setting value is currently being shown on
the display.
> as a multiple of the rated current of the used relay energizing
0
> , expressed in seconds, when the definite time operation
0
>> as a multiple of the rated current of the used relay energizing
0
, 5...40 % x I
n
>> stage, expressed in seconds. The setting range, 0.05...1.00 s
0
have been set as required and work properly. An
example of calculating the checksum is given in
the description "General characteristics of C-
type relay modules".
cated on the front panel. The numbering of the
switches, 1...8, as well as the switch positions 0
and 1 are marked on the front panel.
Setting range I
>
0
0
1...10 % x I
n
0
0,2...2 % x I
n
1
5...50 % x I
n
1
1...10 % x I
n
, 1...10 % x I
or 5...50 % x I
n
n
or 25...200 % x I
n
>
0
>
0
, to be selected
n
, to be selected
n