SolvisDirekt Operation for System Operators and – Installers SolvisStrato with hot water station WWS-xx Hot water flow rates 24 and 36 l/min Operating system: A2.08EN Subject to technical changes Item no.: 22844 P 32-EN 04.11 / 22844-3...
Page 2
Starting on page 24, you will find additional information need on how to use the SolvisControl system controller to for the installation technician about starting up the Solvis- operate your heating system safely. If you have any ques- Control system controller and further setting options.
Contents Contents Section A: Instructions for System Operators (Operating Mode: Client) ....3 1 Safety Notes ..............4 2 Information about the System .
• The operating element of the SolvisControl system controller must be protected from direct sunlight. Solvis heating systems use state-of-the-art technology and meet all relevant safety requirements. They are designed with particular emphasis on safety. But improper operation may result in hazards or damages.
Information about the system 2 Information about the System Congratulations on your purchase of the SolvisDirekt system. The main feature of this system is the central, hygienic and economic water heating. General functional description (Figure on right) The hot water station WWS-36 as part of the SolvisDirekt system consists of components (1) and (2).
Page 6
The SolvisStrato stratified buffer tank was designed espe- cially for use in solar systems. It is the core element of your heating system. In the Low-Flow System from Solvis, your SolvisStrato can be used with all collector surfaces up to 40 m².
Page 7
Information about the system 2.2 Hot water station WWS-xx The hot water station WWS-xx is as described in section 2 the core element of the SolvisDirekt system. It includes all components required for heating drinking water to the desired temperature. The hot water station consists of a plate heat exchanger (PHE) as well as a buffer charging station and it has an integrated volume flow encoder to control the heating of...
Page 8
(by means of two hydraulically separate circuits). The Solvis- Control system controller regulates the solar circuit and buffer circuit pumps. It also controls the speed of each pump.
Switching on the system 3 Switching on the System Start-up: Your heating contractor has installed and started up your system. S/he should also have explained to you how to operate the system. Resuming operation: If you want to start up the heating system after an extended period of standstill, observe the following instructions: 1.
Operating the System Controller 4 Operating the System Controller 4.1 Information about SolvisControl Some concise information on controlling your solar power that this output is switched “ON”. A hand symbol indicates and heating system: that this output is being operated manually. Your heating and solar power system is controlled by Basic operating method: Step 1: Turn the rotary wheel: Go to menu item...
Page 11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Sa. 20. 08. 2005 SOLVIS Return temp. HEAT CIR.1 Summertime: 12:39 Mo Tu We Th Fr Sa Su —...
Operating the System Controller 4.2 Basic settings You can adjust the factory settings to suit your individual Function overview: requirements. 2 3 4 5 6 7 8 9 10 11 12 13 14 If you want to adjust a value, use the rotary wheel to Operat.Syst: A2.08EN position the pointer directly on the value and then MESSAGE...
Page 13
Operating the System Controller “HEAT. REQ.”: Setting the heating requirement: — — — — — — — — — — — Here you can set the “ECO mode”. The boiler will HEAT. REQ F:21 remain off for a limited time, even though the room —...
Operating the System Controller 4.3 Accessories • Temperature sensor SolvisControl TF-SC as flow sensor for heat circuit 1 (S12), heat circuit 2 (S13) , as circulation sensor (S11) or as hot water return sensor lets you control the hot water circulation with SolvisControl.
Operating the System Controller 4.4 Using the room sensor (accessory) You use the room sensor to conveniently set the room temperature and heating program (figure on right) without • Changing the room temperature having to go to the heating system. by plus/minus 5°C If it is too cold, for example, even when the radiator valves are open, you can increase the room temperature by...
Operating the System Controller 4.5 Overview of time programs Use the following tables to plan the heating of rooms to a The following tables give an overview of the heating times, target temperature, the times for auxiliary heating of the hot water times and circulation times that have been set.
Page 17
Operating the System Controller Valid days of the week for the time block Heating time 1 Heating time 2 Heating time 3 from till from till from till Time block 1 Factory setting 00:10 00:00 00:00 00:00 00:00 00:00 Own setting Time block 2 Factory setting –...
Maintenance and Care 5 Maintenance and Care Wipe off any dirt from the SolvisStrato using a damp cloth. Do not use any solvents to clean the SolvisStrato. Heating systems must be maintained regularly according to the German Energy Conservation regulations (EnEV). We recommend that you have your local local specialist perform maintenance annualy.
Troubleshooting 6 Troubleshooting If the boiler does not start up, check that there is a 1 2 3 4 5 6 7 8 9 10 heating requirement (see page 9). If there is no heating requirement but you believe that there should be one, Operat.Syst: Ax make sure that the time is set correctly (page 12).
Troubleshooting 6.1 Problems with the room temperature Problem Cause Remedy Switch the main switch at the control console to on, if necessary. Switch the heating emergency switch to on, Controller is switched off if necessary. Check the main fuse for the heating system. Resume external burner operation.
Troubleshooting 6.2 Setting the heat curve To save energy, the heating curve can be set exactly with All corrections require a certain amount of time to the aid of the rules in the table below. Corrections should take effect. For this reason, wait at least one day only be made in small steps.
SolvisControl System Controller Messages “MESSAGE Excess Temp.” The “WW buffer temp. (S1)” sensor at the top of the tank 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 is monitored for safety reasons. If the temperature is Operat.Syst: Ax.xxEN greater than 98°C at this point, the solar pump and burner are switched off.
Page 24
Contents Section B Instructions for the Installer (please change to user mode: Technician) 8 Setting the Controller and Start-up ..........25 8.1 Safety notes .
Setting the controller and start-up 8 Setting the Controller and Start-up 8.1 Safety notes Operate according to the recognised technical regulations. Observe the accident prevention regulations of the Acci- In case of danger: dent Prevention and Insurance Association. Incorrect use •...
Setting the controller and start-up 8.5 Start-up and sensor installation Make a backup copy at the SolvisControl after com- Follow the instructions in the three sections of start-up. All pleting any adjustments to the settings. hydraulic circuits in the system must be professionally prior to start-up.
Page 28
“SM 1” or “SM 2”, swap the “op” and wheel at the pointer position (switch to “cl” connections (s. section “Wiring diagram Solvis- “HAND” before) Control control board”, p. 66). Switch the outputs from “HAND” back to “AUTO”...
Page 29
Setting the controller and start-up b) Circulation (optional): If the maximum flow temperature is 35°C, for example, • Always leave control mode of circulation pump on in the heating circuit controller menu to which the “Time” ......page 46 underfloor heating is connected, you must reduce “T.PRE.MAX”...
The volume flow measuring unit from Solvis (item no.: 09499, order separately) has a quantity of 0.5 l per 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 impulse (factory setting at controller).
Setting the controller and start-up 8.8 Connecting the swimming pool sensor (optional) A swimming pool should be heated as shown in the dia- grams on pages 67f. Install sensor S16 as an immersion sensor in the swimming pool discharge to the filter. If the controller is used for swimming pool heating, After connecting the sensor and pump, you must: you can no longer connect a room sensor because...
“Functions” Menu Overview 9 “Functions” Menu Overview All functions are briefly explained on page 62f. Menu Status diagnosis at the controller overviews of the most important functions are reproduced When the controller is in the “Technician” operating in the following sub-sections. From the function overview, mode, you can easily troubleshoot in the individual (page 11) you receive the menu of the individual functions functionsusing the “Function status”...
“Functions” Menu Overview 9.2 Heating circuit control function “HEAT CIR.1” 9.2.1 Menu item description Description: This function controls the heating circuit pump Menu, plain text Factory and the heating inflow mixer. setting Setting • “OPERAT.”: You can set the heating programs in the 1 2 3 4 5 6 7 8 9 10 11 12 13 14 “OPERAT.”...
Page 34
“Functions” Menu Overview 9.2.2 Possible settings 1. Setting the heating program: 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 Various operating modes can be set for each heating Operat.Syst: Ax.xxEN circuit: HEAT CIR.1 F:17...
Page 35
“Functions” Menu Overview e) “LEAVE” (figure on right) The heating circuit is switched to lowering 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 mode until the end of the day (midnight) Operat.Syst: Ax.xxEN on the specified date.
Page 36
“Functions” Menu Overview 3. Setting the heat curve: Menu, plain text Factory setting Setting Call: “HEAT CURVE”: in the menu section “HEAT CIR.1” 1 2 3 4 5 6 7 8 9 10 11 12 13 14 of the function overview. HEAT CURVE A systematic procedure is required to precisely set the HEAT CIR.1...
Page 37
“Functions” Menu Overview a) Setting the lowered temperature: 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 In the function overview, turn the rotary wheel until HEAT CIRC.CONT “HEAT CIR.1 F:16” is selected with the pointer. Press the rotary wheel.
Page 38
“Functions” Menu Overview Setting the heating curve in “Temp.” mode. The “Temp.” mode is used in the same manner as the heating curves. The heating curves are selected using a target flow (“pre-run”) temperature of 20°C and outdoor temperature of 20°C and adjustable target Slope 20°C flow (“pre-run”) temperature of -20°C (figure on right).
Page 39
“Functions” Menu Overview Setting the calculated flow (“pre-run”) temperature 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 The SolvisControl lets you manipulate the type and manner of the calculation for the flow temperature. HEAT CURVE There are two modes for this: “Fixed value”...
Page 40
“Functions” Menu Overview Menu, plain text Factory 4. “SWITCH-OFF COND.:” settings setting Setting You can determine when the heating circuit pump is to 1 2 3 4 5 6 7 8 9 10 11 12 13 14 SWITCH-OFF COND. be switched off in the switch-off condition menu (figure HEAT CIR.1 on right).
“Functions” Menu Overview 5. “FROST PROTECTION” submenu: Menu, plain text Factory This function is used for frost protection when the setting Setting system is switched to “Standby” (page 35). The con- 1 2 3 4 5 6 7 8 9 10 11 12 13 14 FROST PROTECTION troller must be in the “Technician”...
“Functions” Menu Overview 9.4 Hot water requirement function “WW_REQ.1” Description: This function controls the hot water heating of Menu, plain text Factory your system. All factory settings enable convenient water setting Setting heating according to the hygienic continuous flow principle. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 WW REQUIREMENT •...
Page 43
“Functions” Menu Overview • Setting the hot water buffer auxiliary heating times: You can change the time windows for water heating to 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 meet your needs: TIME PROG.
“Functions” Menu Overview 9.5 Hot water requirement function “WW_REQ.2” Description: Use this function to enlarge the hot water Menu, plain text Factory buffer so that more hot water is produced during times setting Setting of increased demand. The buffer is enlarged by using 1 2 3 4 5 6 7 8 9 10 11 12 13 14 a sensor at a lower level of the stratified buffer tank WW REQUIREMENT...
“Functions” Menu Overview 9.6 Hot water requirement function “WW_REQ.3” (swimming pool heating) Description: This function heats up the water in the Menu, plain text Factory swimming pool if the heating times were set under setting Setting “TIME PROG”. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 WW REQUIREMENT The heating takes place outside the auxiliary heating times DES.: WW_REQ.3...
“Functions” Menu Overview 9.7 Circulation control function “CIRCU” Description: When you have long hot water pipes, the Menu, plain text Factory water needs to run for a while before it comes out hot setting Setting at the tap. This wastes precious drinking water. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 CIRCULATION You can remedy the situation with an additional water pipe,...
“Functions” Menu Overview 9.8 Heat quantities counting functions Solar circuit “HQC SOLAR”: Call up: “F:30” in the Function overview menu. Menu, plain text Description: This function helps you to check your solar system and shows how much solar energy it has collected. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 HEAT QUANT.
“Functions” Menu Overview 9.9 REQ. HEATING function Menu, plain text When necessary, the function “REQ. HEATING” will send a requirement signal to the automatic firing system of the 1 2 3 4 5 6 7 8 9 10 11 12 13 14 boiler.
Additional Information for Installers 10 Additional Information for Installers 10.1 Checking functions 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 You can check functions quickly with the “FUNCTION STATUS” subfunction that is available at the start of most HEAT CIRC.CONT function menus (figure on right).
Additional Information for Installers 10.2 Frequently asked questions about SolvisControl 10.2.1 How are the solar pumps controlled? When does the primary solar circuit pump switch on? How is the secondary solar circuit pump controlled ? Whenever the collector temperature (“T.Collector”, input 8) The pump in the secondary solar circuit is switched on is higher than the temperature in the lower part of the when the pump of the primary circuit switches on and the...
Page 51
Additional Information for Installers 10.2.2 How is the hot water pump controlled? Hot water is produced in accordance with the continuous When you open the hot water tap, the control switches on flow principle using an external plate heat exchanger the hot water pump at output A2 (PHE).
Additional Information for Installers 10.3 Overview of other SolvisControl parameters 10.3.1 The “DATA ADMINISTRATION” menu Displaying the designation of a function data set 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 The “DATA ADMINISTRATION”...
Page 53
Additional Information for Installers Updating software/configuration You can use the bootloader (item no. 10452) to update configurations or the entire software. For example, you can download data from our web site and use the “Memory- Manager” software to install it on the bootloader. You can only update controller data in the “Expert”...
Additional Information for Installers 10.3.2 Solar control function “SOLAR 1” Menu, plain text Factory setting 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Open: In the Functions menu, function “2: SOLAR SOLAR CONTROL CONTROL” DES.: SOLAR 1 Description: This function controls the solar circuit of your FUNCTION STATUS:...
Page 55
Additional Information for Installers Collector maximum temperature This function protects the solar system components by preventing the solar pump from restarting when steam 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 has formed in the collector.
Page 56
Install the sensors as described in the installation instruction for the solar heat transfer station (Solvis document no.: P 40 or P 42). Set the speed control on both solar pumps to level three and open the adjusting valve in the primary circuit com- pletely (delivery state).
Page 57
Additional Information for Installers Setting the secondary circuit: 1 2 3 4 5 6 8 9 1 0 1 1 1 2 1 3 1 4 • Determine the minimum speed of the solar pump in the secondary circuit as follows: OUTPUTS - Calculating the minimum volume flow: 7: Solar Pump2...
Page 58
Additional Information for Installers 10.3.4 “START FUNCTION” Auxiliary start function for evacuated tube collectors Activate this function only when use evacuated tube collec- 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 tors from SolvisLuna.
Page 59
Additional Information for Installers 10.3.5 “Floor dry” function Open: In the Function overview, turn the rotary wheel until 1 2 3 4 5 6 7 8 9 10 11 12 13 14 the pointer is behind “Floor Dry F:22”, and press the rotary Operat.Syst: A2.08EN wheel.
Appendix: Information on SolvisControl system controller 11 Appendix 11.1 Information on SolvisControl system controller 11.1.1 “Inputs” menu item The sensors on the inputs are described here. The posi- tions of the sensors are shown in the system diagrams in the Appendix (p. 67f). The following measured quanti- ties (“display name”/sensor designation) are displayed: 1: Hot water buffer temperature (“T.WW.Buffer”/S1) 9: Lower heating buffer (“T.H.Buffer U”/S9)
Page 61
Appendix: Information on SolvisControl system controller 11.1.2 “Outputs” menu item The following lists the designations, switch states, pump speeds and mixer states as displayed at the outputs. You can set the switch states (“HAND/ON” – “HAND/OFF” – “AUTO/...” -), where the respective state is indicated by “AUTO/OFF”...
Page 62
Appendix: Information on SolvisControl system controller 11.1.3 Overview of functions Fct.- Function Description COMPARISON Enable for solar circuit. Prevents steam from forming in the secondary circuit. COMP . SOLAR CONTROL Enables switch-on of solar pump in primary circuit, temperature comparisons, SOLAR1 maximum temperatures (page 54).
Page 63
Appendix: Information on SolvisControl system controller Fct.- Function Description COMPARISON Enables swimming pool pumps only if “T.swimming pool” is 1 K less than target DIFF. FUNCT.5 temperature. Setting the target temperature: “WW_REQ.3” on page 13 LOGIC FUNCTION Switches on swimming pool pump if “DIFF.FUNCT.1” to “DIFF.FUNCT.5” are met AND 1 (= only with stored solar heat).
Appendix: Information on SolvisControl system controller 11.1.4 Technical data Electrical connection Mains voltage 230 V/50-60 Hz Microfuse 6.3 A/230 V fast-acting Ambient temperature 0 to 45°C Power consumption Approx. 5 W (in slumber mode, without pumps) Timer function without power supply Approx.
Appendix 11.5 System diagrams SolvisDirekt system with SolvisControl system controller, two storage tanks, two mixed heating circuits and optional swimming pool P32-EN – Subject to technical changes 04.11...
Page 68
Appendix System diagram SolvisDirekt system with SolvisControl system controller, two mixed heating circuits with optional swimming pool P32-EN – Subject to technical changes 04.11...
Appendix 11.6 Circuitry of the burner requirement 1. Version Auxiliary heating contact on boiler requires 230 V Control board voltage signal: In this case, you have to put a wire jumper between the Boiler or “L” and “T1” contacts on output 12 of the SolvisControl sensor switch REQ.
Appendix Transfer of the boiler flow temperature to modulating boilers The required boiler flow temperature is output as an Standard boiler scaling analogue voltage signal (0 to 10 volts) with function 39 via analogue output A15 to a modulating boiler. Analogue output 15 must be set with the corresponding scaling in the “Outputs”...
Page 71
Index 12 Index Heating system ......36 Room influence factor ....15 Heating times......16 Room sensor RAS ....14, 34 Accessories.........14 Hot water buffer layer .....6 Room temperature ....20, 33 Analogue output ......61 Hot water control function Auxiliary heating ......51 “WW_REG” ....42, 44, 45 Auxiliary heating contact....69 Hot water heating ......51 Auxiliary start function....57...