Page 2
IF THIS LINK IS USED THEN TERMINAL 5 CAN NOT BE USED AS AN ALARM FACILITY TEV LTD recommend that personnel working on this equipment be skilled and fully conversant with the appropriate Refrigeration and Electrical practices and have sound knowledge of current Industrial Safe Working practices.
Page 4
PERFORMANCE DATA MRC+ 15 – 180 CAPACITIES – 1 & 3 Phase (Return gas temperature 20°C, 0°K sub cooling) R407A EVAPORATING TEMPERATURE °C Ambient MODEL Temp °C COOLING CAPACITY AND POWER INPUT kW CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP.
Page 5
EVAPORATING TEMPERATURE °C Ambient MODEL Temp °C COOLING CAPACITY AND POWER INPUT kW CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER 7.74 3.34 9.64 3.44 11.43 3.56 13.38 3.74 15.51 3.97 16.30 4.08 17.68 4.20 7.46 3.57...
Page 6
PERFORMANCE DATA MRC+ 15 – 180 CAPACITIES – 1 & 3 Phase (Return gas temperature 20°C, 0°K sub cooling) R407F EVAPORATING TEMPERATURE °C Ambient MODEL Temp °C COOLING CAPACITY AND POWER INPUT kW CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP.
Page 7
EVAPORATING TEMPERATURE °C Ambient MODEL Temp °C COOLING CAPACITY AND POWER INPUT kW CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER 7.62 3.78 9.53 3.83 11.32 3.92 13.54 4.00 15.57 4.31 16.46 4.41 17.95 4.55 7.31 4.05...
PERFORMANCE DATA MRC+ 15 – 180 CAPACITIES – 1 & 3 Phase (Return gas temperature 20°C, 0°K sub cooling) R404A EVAPORATING TEMPERATURE °C Ambient MODEL Temp °C COOLING CAPACITY AND POWER INPUT kW CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP.
Page 9
EVAPORATING TEMPERATURE °C Ambient MODEL Temp °C COOLING CAPACITY AND POWER INPUT kW CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER 8.15 3.94 9.84 3.97 11.32 4.02 13.06 4.13 14.82 4.31 15.56 4.38 16.73 4.46 7.82 4.17...
PERFORMANCE DATA MRC+ 15 – 180 CAPACITIES – 1 & 3 Phase (Return gas temperature 20°C, 0°K sub cooling) R448A – R449A EVAPORATING TEMPERATURE °C Ambient MODEL Temp °C COOLING CAPACITY AND POWER INPUT kW CAP. POWER CAP. POWER CAP. POWER CAP.
Page 11
EVAPORATING TEMPERATURE °C Ambient MODEL Temp °C COOLING CAPACITY AND POWER INPUT kW CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER CAP. POWER 7.61 3.59 9.40 3.62 11.02 3.69 12.96 3.84 15.07 4.05 16.01 4.15 17.42 4.27 7.35 3.83...
Page 12
MOUNTING MRC+ These units are designed to stand on a flat surface. If the unit is to be wall mounted the following kits are available. MRC+ 15-80 MRC+ 90-180 Mounting Bracket 55021100 55021101 Whether floor or wall mounted, it is essential that the mounting surface is capable of supporting the unit weight.
PIPE SIZES MAXIMUM LENGTH OF EQUIVALENT LIQUID LINE UNIT SUCTION LINE PIPE SIZES (m) SIZE ⅜ ⅝ ⅞ 1⅛ 1⅜ ⅜ ⅝ ½ ¾ ½ ¾ CONNECTING THE UNITS Connecting the pipework: a. Remove the flare nuts from the service valves and release the nitrogen holding charge by slowly opening the valves using a 5mm or 8mm allen key.
Page 15
The ratings are for the outdoor unit only. Currents for the indoor units including heaters if applicable should be noted and the fuse size increased pro-rata. CONNECTION OF MAINS SUPPLY: 1. Ensure the isolator switch is in the OFF position. 2.
Page 16
8. Route incoming mains cable through the knockout hole and wire to the required terminals and replace lower protective cover. 9. Replace main isolator back into the switch and lock into place by sliding the red lever upwards. 10. Replace covers. 16/27 55008351-23...
R404A REFRIGERANT Charging the System: Evacuate the system and interconnecting pipework as page 8 ensuring the service valves are fully open. Allow the evacuated system to draw in the majority of the refrigerant charge. The final charge should be adjusted with the system running. All units are fitted with head pressure control.
Page 18
Min fan speed (0 rpm) and fan cut in pressure 200 psig (13.8 barg) are factory set and not adjustable. NOTE: The condenser fan may stop if the operating pressure drops below 200 psig (13.8 barg) R404A: 210-220 psig (14.5-15.2barg) to achieve this remove sealing plug and insert 2mm or 5/64” allen key into setting screw.
ROTA-LOCKED VALVES FITTED TO RECIEVER POSITION SPINDLE FUNCTION OUT CLOSED ALL OPEN P1 CLOSED Pay attention - P1, P2: optional gages ports. - The positions IN - OUT could be inverted according to the employment of client. - The spindle must be positioned in the position B when the valve will be connected to the unit.