I NSPECTION

At the time of i n sta l l ati on, the relay should be i nspected for ta rn ished contacts, l oose
screws, or other i m perfections. If any trouble is fou nd, it sho u ld be corrected in the m a n n e r
d escri bed u nd e r
MAI NTE NANCE .

LOCATION

The l ocatio n should be clean and d ry, free from d ust and excessive vibrati on, and wel l
l i g hted to faci l itate i nspection and testing .

M O U NTING

The relay sho u l d be m o u nted on a verti cal s u rface.
d i m e nsions a re shown i n Fig u re 1 9 for relay Types IAV5 1 A, IAV52A and IAV53C. Fig u re 2 0
shows outl i n e and p a n e l d ri l l i ng for relay Types IAV53A, IAV53B and IAV53 D. Fig u re 2 1
shows the outl i n e and panel d ri l l i ng for re lay Types IAV5 3 K, IAV5 3 L, IAV53 M a n d IAV53 N .

CON N ECTI ONS

I ntern a l con n ections a re shown i n Fi g u res 1 to 8 for the va rious relays.

G RO U N D CO N N ECTIONS

One of the mounting studs or screws sho u ld be perma nently g ro u n d ed by a con d u cto r n ot
less than No. 1 2 B&S gage copper wire or its eq u ivale nt.
FI E LD I N STA LLATI ON TESTS
B efore the relay is put i n servi ce, the pickup voltage and ti me/voltage tests d escri bed in
ACC E PTA N C E T E ST S
adj ustments have not been d istu rbed .
The relay may be tested w h i l e mou nted on the panel, either from its own or a nother so u rce
of powe r, by i n serti ng a sepa rate testing p l u g i n pl ace of the co n necti ng p l u g . Or, the
cra d le ca n be d rawn out and repl aced by a noth er that has been l a boratory tested .
In view of the vital role of protective relays in the operatio n of a power syste m it i s
i m po rta nt that a period i c test progra m be fo l l owed .
between peri od ic ch ecks wi l l vary depend i n g u pon environ ment, ty pe o f relay a nd u se r's
experi ence with period ic test i n g . U ntil the user has accu m u l ated e n o u g h experi e n ce to
select the test i nterva l best suited to h is i nd ivid ual req u i rements, it is suggested that the
poi nts l isted u nder

I N STALLATION

DISK AND B EARI NGS

The lower jewel may be tested fo r cracks by explori ng its su rface with the p o i nt of a fi n e
n eed l e . If i t is necessary to replace the jewel, the j ewel shou ld then b e tu rned u p u ntil the
d isk is centered i n the air g a p, after wh ich it should be locked i n positi on by the set screw
p rovided for the pu rpose.
G E H- 1 8 1 4
I N STALLATION
Check t h e nameplate fo r mod el n u mber a n d rati n g .
( E L E CT R I CA L T E STS) s h o u l d be m a d e , to d et e r m i n e t h a t t h e
P E R I O DIC C H E CKS AND ROUTI N E MAINTENANCE
be ch ecked eve ry six months.
The outl i n e and p a n e l -d ri l l i n g
It is recog n i zed that the i nterva l
1 1