  • Page 1 Operating instructions Additional languages www.r-stahl.com Universal spotlight LED Series 6050/6...
  • Page 2: Table Of Contents

    Contents General Information ....................3 Manufacturer .......................3 Information regarding the operating instructions ..........3 Further documents ....................3 Conformity with standards and regulations ............3 Explanation of the symbols .................4 Symbols in these operating instructions .............4 Warning notes .....................4 Symbols on the device ..................5 Safety notes ......................5 Operating instructions storage ................5 Safe use ......................5...
  • Page 3: En En En

    • Data sheet For documents in additional languages, see www.r-stahl.com. Conformity with standards and regulations See certificates and EC Declaration of Conformity: www.r-stahl.com. The device has IECEx approval. For certificate please refer to the IECEx homepage: http://iecex.iec.ch/ Further national certificates can be downloaded via the following link: https://r-stahl.com/en/global/products/support/downloads/.
  • Page 4: Explanation Of The Symbols

    Explanation of the symbols Explanation of the symbols Symbols in these operating instructions Symbol Meaning Tips and recommendations on the use of the device General danger Danger due to explosive atmosphere Danger due to energised parts Warning notes Warnings must be observed under all circumstances, in order to minimize the risk due to construction and operation.
  • Page 5: Symbols On The Device

    • Use the device in accordance with its intended and approved purpose only. • Always consult R. STAHL Schaltgeräte GmbH if using the device under operating conditions which are not covered by the technical data. • We cannot be held liable for damage to the device caused by incorrect or unauthorised use or non-compliance with these operating instructions.
  • Page 6: En 3.3 Intended Use

    Function and device design Intended Use The luminaire 6050/6 is equipment • for lighting areas, work spaces and objects • can be used indoors and outdoors • for stationary mounting • for use in Zones 1, 21, 2, 22 and in the safe area Modifications and alterations DANGER Explosion hazard due to modifications and alterations to the device!
  • Page 7: Function

    Function and device design Function Application range The luminaire 6050/6 is equipment used for lighting areas, work equipment and objects. It can be used indoors and outdoors. The light fitting is approved for use in hazardous areas of Zones 1, 2, 21 and 22. Device design 20017E00 1 - Thread for M8 ring bolts...
  • Page 8: En En

    Technical data Technical data Explosion Protection Global (IECEx) Gas and dust IECEx EPS 17.0093 Ex db eb op is IIC T. Ex tb op is IIIC T...°C Europe (ATEX) Gas and dust EPS 17 ATEX 1 181 E II 2 G Ex db eb op is IIC T. E II 2 D Ex tb op is IIIC T...°C Variant Temperature class...
  • Page 9 Technical data Technical Data Luminous characteristics Neutral white Colour rendering [CRI] = )80 Colour temperature [K] = 5000 6050/60.-2..- 6050/60.-4..- 6050/60.-6..- …-…850-… …-…850-… …-…850-… Power consumption [W] 16.4 40.1 60.3 Clear glass Luminous flux [lm] 2,015 5,077 7,357 Luminaire efficacy 122.9 126.6 122.0...
  • Page 10 Technical data Technical Data Luminous flux at ambient temperature decrease 120 % 100 % 40 W Version 80 % 60 % 60 W Version 40 % 20 W Version 20 % 30 °C 35 °C 40 °C 45 °C 50 °C 55 °C 60 °C 20147E00...
  • Page 11: Transport And Storage

    Wire guard and can easily be mounted later using an M6 mounting screw external reflector For further technical data, see www.r-stahl.com. Transport and storage • Transport and store the device only in the original packaging. • Store the device in a dry place (no condensation) and vibration-free.
  • Page 12: En 7.1 Dimensions / Fastening Dimensions

    Mounting and installation Dimensions / fastening dimensions Dimensional drawings (all dimensions in mm [inches]) – Subject to modification 310 [12,20] 310 [12,20] 310 [12,20] 10 [0,39] 100 [3,94] 10 [0,39] 10 [0,39] 290 [11,42] 290 [11,42] 290 [11,42] 20079E00 20076E00 20078E00 without wire guard with wire guard...
  • Page 13: Mounting / Dismounting, Operating Position

    Mounting and installation Mounting / dismounting, operating position 7.2.1 Wire Guard Assembly 20001E00 • Insert the wire guard into the intended slots (1) of the light fitting. • Tighten the screws (2). The wire guard is installed. 7.2.2 Assembly of the External Reflector 20002E00 •...
  • Page 14 Mounting and installation 7.2.3 Assembly of the Holding Bracket The retaining bracket can be used for wall or ceiling installation. Thanks to the raster's adjustment option, the light fitting can be adjusted in steps of 10° to a maximum of 40°. 20006E00 •...
  • Page 15: Installation

    Mounting and installation Installation DANGER Explosion hazard due to opening the enclosure cover! Non-compliance results in severe or fatal injuries. • It is prohibited to open the enclosure cover of the luminaire. 7.3.1 Electrical connections DANGER Explosion hazard due to faulty installation! Non-compliance results in severe or fatal injuries.
  • Page 16: Commissioning

    Commissioning 7.3.2 Cable entries The luminaire 6050/6 is equipped with 2 entries, a cable entry and a stopping plug. The electrical connection into the EX d chamber is implemented with a hermetically sealed M 16 x 1.5 conductor bushing size. To install additional permitted screw connections, proceed as follows: •...
  • Page 17: Maintenance, Overhaul, Repair

    Maintenance, Overhaul, Repair Maintenance, Overhaul, Repair CAUTION Risk of electric shock or malfunction of the device due to unauthorized work! Non-compliance can result in light injuries! • Before carrying out work on the device, switch off voltage supply. • Work performed on the device must only be carried out by authorized and appropriately trained qualified electricians.
  • Page 18: Repair

    • Only return or package the devices after consulting R. STAHL! Contact the responsible representative from R. STAHL. R. STAHL's customer service is available to handle returns if repair or service is required. • Contact customer service personally. • Go to the www.r-stahl.com website.
  • Page 19: Disposal

    Malfunction or damage to the device due to the use of non-original components. Non-compliance can result in material damage. • Use only original accessories and spare parts from R. STAHL Schaltgeräte GmbH. For accessories and spare parts, see data sheet on our homepage www.r-stahl.com.