GE ADTGC-HDVM Installation Sheet page 2

Advertisement

Figure 2: Horn and strobe settings
1.
JP1: Horn signal jumper: Cut to change from temporal to steady
2.
JP2: Strobe signal output: Cut to change from 1 flash per second
(public mode) to temporal (private mode)
3.
JP3: Horn sound output: Cut to change from high dB to low dB
Note: If the strobe is set to temporal (private mode), this device is
no longer UL 1971 or ULC-S526 Listed or FM Approved but is
UL 1638 Listed.
Figure 3: UL 1971 minimum light output (% of rating vs. angle)
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
1.
Angle
2.
Percentage of rated output
Note: Horizontal and vertical outputs have the same pattern
2 of 4
1
-5
0
5 10
15
20
25
30
35
40
45
50
2
Wiring
Figure 4: Wiring Diagram
1.
From NAC output
2.
To next NAC output
Note: Signal polarity is shown in the alarm condition.
Figure 5: Mounting diagram
55
60
65
70
75
80
85
90
Table 3: Strobe operating current in RMS (A)
VDC
VFWR
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Operating currents shown above were measured by UL at 16 VDC and 16
VFWR.
+
1
-
15 cd
30 cd
75 cd
0.147
0.190
0.316
0.189
0.253
0.417
P/N 3100616 • REV 4.0 • ISS 30SEP09
2
95 cd
0.372
0.451