WARNING: Electrical Device
In order to ensure proper operation and prevent shock
or fire, all products must be installed correctly. Read all
warnings and follow all installation instructions.
Ground-fault equipment protection must be used to
minimize the danger of fire from sustained electrical
arcing if the heating cable is damaged or improperly
installed and to comply with Nuheat requirements,
agency certifications and national electrical codes.
Conventional circuit breakers may not stop arcing.
Do not substitute parts or use electrical tape.
Component approvals and performance characteristics
are based on Nuheat specific parts only. Substitution
will void approvals, warranties and performance claims.
The heating cable core is conductive and can short if
not properly insulated and kept dry.
Heating cable core bus wires can overheat and short
when damaged. When cutting the cable jacket or core,
do not break bus wire strands.
Component and heating cable ends must be kept dry
before and during installation.
Fire-resistant thermal insulation materials should be used.
For use with Nuheat R8P5, R13P8 and 13FP cables.
Rated: 277 V; Max: 50A
Maximum continuous exposure temperature: 65˚C (149˚F)
BEFORE YOU START:
• Read through entire installation instructions prior to
beginning installation.
• All instructions available at www.nuheat.com
• DO NOT install Nuheat Freeze Protection products in
direct contact with combustible surfaces or materials.
• DO NOT rest a hot heat gun on any Nuheat Freeze
Protection Products.
• DO NOT make any modifications to Nuheat Freeze
Protection Products while connected to power.
• THIS HEATING PRODUCT SHOULD ONLY BE
INSTALLED BY QUALIFIED PERSONNEL WHO ARE
FAMILIAR WITH THE CONSTRUCTION AND OPERATION
OF THE APPARATUS AND RISKS INVOLVED.
• THE INSTALLATION OF THIS HEATING PRODUCT
SHALL BE IN ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS AND REGULATIONS
OF THE AUTHORITY HAVING JURISDICTION.
Nuheat Freeze
Protection Products
Assembled in Canada

Advertisement

loading
Need help?

Need help?

Do you have a question about the RPST and is the answer not in the manual?

Questions and answers

Summary of Contents for Nuheat RPST

  • Page 1 • All instructions available at www.nuheat.com • DO NOT install Nuheat Freeze Protection products in direct contact with combustible surfaces or materials. • DO NOT rest a hot heat gun on any Nuheat Freeze Protection Products. • DO NOT make any modifications to Nuheat Freeze Protection Products while connected to power.
  • Page 2 1 ¼" 1" 8. Using scissors, cut down the middle of the conductive Splice/Tee Kit core lengthwise to separate into two parts. Do not cut Model #: RPST into the inner jacket that remains. 3 /4" 3 /4" EQUIPMENT REQUIRED: 9.
  • Page 3 Use the 14AWG slot on the crimp tool (Tyco 3" AD1522 or equivalent) to crimp the metal crimp sleeve. 7" NOTE: Nuheat recommends conducting continuity 2" 3" testing at this point of the installation. 4. Twist the braid into a pigtail.
  • Page 4 1¼" 15. Ensure the exposed bus wires are inside the metal NOTE: Nuheat recommends conducting continuity 1" testing at this point of the installation. crimp portion of the blue heat shrinks. 16. Using crimp tool, crimp the blue heat shrinks down so 1¼"...
  • Page 5 Shrink tube. Hold for 15 seconds. 3 /8" Nuheat Freeze Protection Products toll free 1.800.778.WARM ( 9276 ) fax 604.529.4404 www.nuheat.com info@nuheat.com Nuheat™ is the registered Trademark of Nuheat Industries Ltd. Printed in Canada April 2013 3 "...