Page 1
OPERATION AND INSTALLATION MANUAL SMC SERIES AIR COOLED PORTABLE WATER CHILLERS IMPORTANT: PLEASE READ CAREFULLY BEFORE ATTEMPTING TO INSTALL OR OPERATE EQUIPMENT...
Safety Considerations Sterling, Inc. SMC Series Chillers are designed to provide safe and reliable operation when installed and operated within design specifications, following national and local safety codes. To avoid possible personnel injury or equipment damage when installing, operating or maintaining this equipment, use good judgment and follow these safe practices: Follow all SAFETY CODES.
Table of Contents General Information ... 7 Introduction Necessary Documents Models Covered Available Options Uncrating Your New Chiller In the Event of Shipping Damages If the Shipment is Not Complete If the Shipment is Incorrect Returns Chiller Installation ... 13 Electrical Connections Process Water Connections SMC Condenser Air Supply...
Page 5
Startup Checklists ... 23 Introduction SMC Pre-Startup Checklist SMC Startup Checklist SMC Water Circuit Pressure Drop Table Microprocessor Control... 25 Introduction Setting the Process Water Temperature LED Indicators Temperature Controller Keys Auto-Tuning SMC Series Chillers Optional Communications Optional Graphic Panel... 30 Indicator Lights Switches Routine Maintenance ...
Page 6
Charts and Figures Figure 1: SMC050 Process Pump Curves... 11 Figure 2: SMC100 Process Pump Curves... 11 Figure 3: PCA150 Process Pump Curves ... 11 Figure 4: SMC Cast Iron Centrifugal Pump Curve 1/3 hp (0.249 kW)... 12 Figure 5: SMC Series Chiller Specifications ... 13 Figure 6: Ethylene Glycol Curve ...
Introduction Sterling, Inc.'s SMC Series Water Chillers are reliable, accurate, and easy-to-use air cooled chillers designed for use with water/glycol. Standard range of operation is 30°F (-1°C) to 65°F (18°C) for applications using glycol and 45ºF (7ºC) to 65°F (18°C) for water-only applications.
Available Options SMC Series Chillers are available with options that tailor the unit to your requirements. Some are factory installed, some can be retrofitted in the field. Consult your local Sterling, Inc. Sales Representative. Some of these options are: Special Pumps Special pump options are available for greater pressure and flow rates.
In the Event of Shipping Damages According to the contract terms and conditions of the Carrier, the responsibility of the shipper ends at the time and place of shipment. The Carrier then assumes full responsibility of the shipment. Notify the transportation company's local agent. Hold the damaged goods and packing material for the examining agent's inspection.
Returns IMPORTANT! Do not return any damaged or incorrect items until you receive shipping instructions from STERLING, Inc. Page 10 SMC Series Chillers...
Figure 5: SMC Series Chiller Specifications Optional gauge package Optional gauge package PUMP PRESSURE Mini Chiller PC Series Portable Chiller No Flow indicator HIGH PUMP COMPRESSOR REFRIGERANT REFRIGERANT PRESSURE PRESSURE POWER (for pumpless A0537868 units only) NO FLOW Application Engineering 20"...
Electrical Connections Check serial tag voltage and amperage requirements and make sure your electrical service conforms. See Figure 5 on page 13 for total running amps. Bring properly sized power leads and ground from a fused disconnect (installed by your electrician) to the main power terminal in the chiller's electrical enclosure.
Process Water Bypass All SMC chillers have an internal bypass device (patent pending). If the process flow becomes blocked during chiller operation, this component allows water to flow through the chiller. This protects the chiller from freeze-up, excessive pressures, and pump damage, and allows other safety features to remain effective.
A corrosion inhibitor suitable for the materials in the system should be added to the glycol/water solution. If straight water use is desired, contact the Sterling, Inc. Engineering Department. The six gallon (23 liter) reservoir is not designed to withstand water pressure above 5 psi (34 kPa).
Overhead Process Considerations If your application has chilled water or process piping above the reservoir fill and vent level, install a standpipe to a point 1’ (30 cm) above the highest point in the system. In applications where the process or its piping is 15 feet (4.6 m) or more above the reservoir, you must take steps to prevent over-pressurization of the reservoir.
• The SMC unit has a leaving water temperature range of 30°F (-1°C) to 65°F (18°C). Do not attempt to run the SMC unit outside this temperature range or damage to the unit may occur. • When operating the SMC unit between 30°F (-1°C) and 40°F (5°C), you must use a solution of 75% water and 25% industrial-grade ethylene glycol with a suitable corrosion inhibitor to protect the SMC unit from freeze-up.
High Pressure Cutout The high pressure cutout is an electro-mechanical safety feature that opens the control circuit if the system condensing pressure exceeds a safe level. The chiller will automatically restart when the pressure drops back to an acceptable level. Model SMC050 SMC100...
Introduction Follow the check lists below for the startup of your new chiller. These lists assume the installation information elsewhere in this manual has been read and followed. New chillers should be started up and checked by a qualified refrigeration service technician. SMC Pre-Startup Checklist 1.
Introduction Standard SMC Series chillers use a microprocessor-based PID controller. The controller is a modular, self-contained unit that can slide from its mounting housing. It is factory set and adjusted; no field adjustment to the internal controls is necessary. Standard models 30°F to 65°F (-1ºC to 18ºC) Setting the Process Water Temperature To change the process water temperature set point: LED Indicators...
Figure 12: Typical SMC Series E5CK Microprocessor Controller OUT1 OUT2 MANU STOP RMT OMRON OUT2 LED The orange energizes whenever the process temperature is two degrees (2°F/ºC) OUT2 or more above the To Process set point. The compressor then comes on and runs until the temperature at the To Process thermocouple is two degrees (2°F/ºC) below the set point.
RMT LED The orange AT LED The orange SUB1 LED The orange SUB1 degrees (2°F/ºC) or more below the To Process set point. The compressor then shuts down by means of a latching circuit, and does not run again until the temperature at the To Process thermocouple is two degrees (2°F/ºC) above the set point.
Do not change any of the control settings without consulting the Sterling Service Department. The AEC, Inc. warranty does not cover chiller failures from tampering with controller settings! Down Key Each press of the the values or settings on the Up Key Each press of the the values or settings on the...
5-6 Optional Communications Standard Omron Protocol The communications function allows you to monitor and set E5CK parameters by a program prepared and running on a host computer connected to the E5CK controller. When using the communications function, you must add on the unit for RS-232C or RS-485 communications.
Indicator Lights PUMP ON (green) This indicator lights when the pump is running. COMPRESSOR ON (green) This indicator lights when the compressor is operating. HIGH REFRIGERANT PRESSURE (red) This indicator lights if the condensing pressure exceeds a safe level. The chiller goes to Idle mode until the high refrigerant pressure cutout resets.
Figure 13: Optional Graphic Panel PC Series Portable Chiller HIGH PUMP COMPRESSOR REFRIGERANT REFRIGERANT PRESSURE PRESSURE POWER E5CS O RO A0537868 Page 32 SMC Series Chillers...
Lubrication Every three months, grease all fan motors and pump motors that do not have permanently sealed bearings. Remove grease relief plug (motors only) before adding grease. Failure to do so may result in dislodging the bearing grease retainer, eventually causing bearing failure.
Figure 16: SMC Wiring Schematic for Chillers with No Pump or Reservoir Remote Earth interlock ground by others 230V Control power ON/OFF Jumper 1S-1LT 115V "No Flow" 1FLS 1FLS Jumper 1CNTL Type K thermocouple SMC Series Chillers "Low Refrig "High Refrig Pres"...
Problem Chiller will not run. Pump runs, compressor cycles at short intervals. The leaving water temperature is too high. Pump pressure is low (see pump curves). Pump pressure is too high. SMC Series Chillers Troubleshooting Guide Cause Check main disconnect No power.
Page 38
Refrigerant high pressure Check for dirty condenser. cutout switch contacts are Check for condenser air open. obstruction. Defective fan motor. Repair or replace. Check for high/low voltage. Must be within plus or Compressor internal minus 10% of the overload is open. Allow nameplate rating.
Page 39
PCA Unit Parts List Part Number A0537868 SMC Graphic A0537899 BZ Pressure Gauge A0534584 Red Neon Graphic Light * A0534586 Green Neon Graphic Light * A0500857 2” Swivel Casters A0534269 1/16 DIN Digital Temperature Controller A0537955 Process Water Flow Switch A0533873 Thermocouple, 8’...
Parts Department Call toll-free 7am - 5pm CST [800] 423-3183 Or call [262] 641-8610, Fax [262] 641-8653 The Parts Department at AEC, Inc. is ready to provide the parts to keep your systems up and running. AEC replacement parts ensure operation at design specifications. Please have the model and serial number of your equipment when you call.