Auto Configure
Auto configure is the first step to take after the panel is initially energized. This function recognizes
the electrical system, then automatically sets all the system parameters: system voltage, frequency,
and phase sequence. Follow the steps in the figure on the HMI to run auto configure. The ATS must
have at least one source available to complete this step.
G
60s
11:06
System Overview
S1
Ok
Not Ok
S2
S1 Connected to Load
Load Current
393 A
Override S1 Fail
TruONE ATS
Operation
Parameters
Measurements
Settings
Test
About
TruONE ATS
Figure 5