Veeder-Root QuickServer Startup Manual
Veeder-Root QuickServer Startup Manual

Veeder-Root QuickServer Startup Manual

Industrial protocol gateway
Table of Contents

Advertisement

Quick Links

Manual No: 577014-367
Revision: D
QuickServer Industrial Protocol Gateway
Startup Guide

Advertisement

Table of Contents
loading

Summary of Contents for Veeder-Root QuickServer

  • Page 1 • Manual No: 577014-367 Revision: D QuickServer Industrial Protocol Gateway Startup Guide...
  • Page 2 If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking fee. Veeder-Root will NOT be responsible for any compensation when a customer chooses their own carrier.
  • Page 3: Table Of Contents

    Setup For QuickServer Record Identification Data ....................5 Point Count Capacity And Registers Per Device ..............5 Input COM Settings on the device connected to the QuickServer ........6 Selecting The Desired Protocol Configuration ..............6 BMS Network Settings: MAC Address Node-ID And Baud Rate ........7 BACnet MS/TP: Setting The MAC Address For BMS Network ........7...
  • Page 4 And Modbus ..................B-2 Table B-5. Input Veeder-Root Interface To BACnet And Modbus ......B-3 Table B-6. Type A Sensor Veeder-Root Interface To BACnet And Modbus ..B-3 Table B-7. Type B Sensor Veeder-Root Interface To BACnet And Modbus ..B-3 Table B-8.
  • Page 5 Table B-9. Groundwater Sensor Veeder-Root Interface To BACnet And Modbus ..................B-3 Table B-10. MAG Sensor Veeder-Root Interface To BACnet And Modbus ....B-4 Table B-11. Smart Sensor Veeder-Root Interface To BACnet And Modbus .... B-4 Table B-12. PLLD Veeder-Root Interface To BACnet And Modbus ......B-4 Table C-1.
  • Page 6: Contractor Certification Requirements

    Veeder-Root’s products (hereafter called “device”) connected to the QuickServer and automatically configures them for BACnet MS/TP, BACnet/IP, Modbus RTU and Modbus TCP/IP. It is not necessary to download any configuration files to support the required applications. The QuickServer is pre-loaded with tested profiles/configurations for the supported devices.
  • Page 7: Safety Warnings

    Introduction Safety Warnings READ ALL RELATED MANUALS Indicates a hazardous situation which, if not avoided, Knowledge of all related procedures before you begin WARNING could result in death or serious injury. work is important. Read and understand all manuals thor- oughly.
  • Page 8: Quickserver Gateway

    Introduction QuickServer Gateway. QuickServer Gateway. Figure 1. QuickServer ProtoNode Connectivity Diagram (TLS450PLUS Shown)
  • Page 9: Quick Start Guide

    1. Record the information about the unit. ( page 5) 2. Set the device’s COM settings for each of the devices that are to connect to the QuickServer. ( page 6) 3. Select the protocol configuration on the S Bank DIP switches. ( page 6) 4.
  • Page 10: Setup For Quickserver

    Setup For QuickServer Record Identification Data The QuickServer has a unique part number located on the side or the back of the unit. This number should be recorded, as it may be required for technical support. The numbers are as follows: Table 1.
  • Page 11: Input Com Settings On The Device Connected To The Quickserver

    Parity Data Bits Stop Bits Selecting The Desired Protocol Configuration QuickServer ProtoNode units use the ‘S’ bank of DIP switches (S0 - S3) to select the protocol configuration (see Figure 2). NOTICE When setting DIP switches, ensure that power to the board is OFF.
  • Page 12: Bms Network Settings: Mac Address Node-Id And Baud Rate

    Addresses from 128 to 255 are Slave Addresses and can not be discovered by BMS front ends that support Auto-Discovery of BACnet MS/TP devices. • Set “A” bank DIP switches A0 – A7 to assign a MAC Address to the QuickServer for BACnet MS/TP (see Figure 3). NOTICE...
  • Page 13: Bacnet Ms/Tp Or Modbus Rtu: Setting The Baud Rate For Bms Network

    BACNET MS/TP OR MODBUS RTU: SETTING THE BAUD RATE FOR BMS NETWORK DIP switches B0 – B3 can be used to set the field baud rate of the QuickServer to match the baud rate required by the BMS for BACnet MS/TP (see Figure 4).
  • Page 14: Interfacing Quickserver To Devices

    Pins 1 - 3 are for Veeder-Root ATG input (see Figure 6). • Pins 4 - 6 are for QuickServer power. QuickServer accepts either 9-30V DC or 12-24V AC on pins 4 and 5. Do not power up QuickServer at this time.
  • Page 15: Serial Network Wiring Field Port To Rs-485 Network

    • If the QuickServer is the last device on the trunk, then the End-Of-Line Termination Switch needs to be set to the On position (the EOL Termination default setting is Off). If necessary, set the switch to the On position (see Figure 8).
  • Page 16: Power Up Quickserver

    These values are ‘nominal’ and a safety margin should be added to the power supply of the host system. A safety margin of 25% is recommended. After verifying power source and with frame ground connected as shown in Figure 6. apply power to QuickServer.
  • Page 17: Using Quickserver Web Configurator To Setup The Gateway

    The Default IP Address of QuickServer is 192.168.1.24, subnet mask is 255.255.255.0. If the PC and QuickServer are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network: For Windows 10, Right click on hen click on Network Connections>Change Adapter Options.
  • Page 18: Connecting To Quickserver Web Configurator

    Connecting to QuickServer Web Configurator After setting a local PC on the same subnet as the QuickServer (refer to above paragraph), open a web browser on the PC and enter the IP Address of the QuickServer (the default address is 192.168.1.24).
  • Page 19: Figure 10. Web Configurator Showing No Active Profiles

    Using QuickServer Web Configurator To Setup The Gateway Selecting Profiles for Devices Connected to QuickServer Figure 10. Web Configurator Showing No Active Profiles Figure 11. Web Configurator Showing Available Profiles For Selection...
  • Page 20: Setting Bacnet Parameters

    Fill in the parameter values as needed (see Figure 13). Enter the Veeder-Root PLC Type, COM settings and BACnet settings (Bac_device_id) See See “Input COM Settings on the device connected to the QuickServer” on page 6. NOTICE for correct COM settings per PLC Type.
  • Page 21: Figure 13. Web Configurator With Protocol Set To Bacnet

    Using QuickServer Web Configurator To Setup The Gateway Setting BACnet Parameters Figure 13. Web Configurator with Protocol Set to BACnet...
  • Page 22: Ethernet Network - Setting Ip Address For Field Network

    After setting a local PC to the same subnet as the QuickServer (See “Connect The PC To QuickServer Via The Ethernet Port” on page 12., open a web browser on the PC and enter the IP Address of the QuickServer; the default address is 192.168.1.24.
  • Page 23: Figure 15. Changing Ip Address Via Fs-Gui

    QuickServer should be set to the IP Address of that managed switch/router. •Click the “System Restart” button at the bottom of the page to apply changes and restart the QuickServer. •Unplug Ethernet cable from PC and connect it to the network switch or router.
  • Page 24: How To Start The Installation Over: Clearing Profiles

    How To Start The Installation Over: Clearing Profiles 1. After setting a local PC to the same subnet as the QuickServer (“Connect The PC To QuickServer Via The Ethernet Port” on page 12), open a web browser on the PC and enter the IP Address of the QuickServer.
  • Page 25: Appendix A: Troubleshooting

    Ethernet port Figure A-1. Ethernet Port Location 3. Connect a standard CAT5 Ethernet cable between the user’s PC and QuickServer. 4. Double click on the FS Toolbox Utility and click Discover Now on the splash page. 5. Check for the IP Address of the desired gateway.
  • Page 26: Viewing Diagnostic Information

    Figure A-2), then click Network Settings, change the IP Address and click Update IP Settings to save. Viewing Diagnostic Information 1. Type the IP Address of the QuickServer into the web browser or use the FieldServer Toolbox to connect to the QuickServer.
  • Page 27: Led Diagnostics For Communications Between Quickserver And Devices

    Configurator” on page 13.). • Field COM problems: If Ethernet protocols are used, observe Ethernet LEDs on the QuickServer (See “LED Diagnostics For Communications Between QuickServer And Devices” below). Check DIP switch settings (using correct baud rate and device instance)
  • Page 28: Take Diagnostic Capture With The Fieldserver Toolbox

    Sierra Monitor Resource Center Software Downloads. Reference Figure A-1. • Extract the executable file and complete the installation. • Connect a standard CAT5 Ethernet cable between the PC and QuickServer. • Double click on the FS Toolbox Utility.
  • Page 29: Figure A-7. Selecting Start Diagnostic For Selected Device

    Appendix A Take Diagnostic Capture With The FieldServer Toolbox c.Click on ‘Start Diagnostic’. Figure A-7. Selecting Start Diagnostic For Selected Device d.When the capture period is finished, the “Diagnostic Test Complete” window will appear 2. Send Log a.Once the diagnostic test is complete, a zip file is saved on the PC. Figure A-8.
  • Page 30: Update Firmware

    Securing QuickServer With Passwords Access to the QuickServer can be restricted by enabling a password on the FS-GUI Passwords page – click Setup and then Passwords in the navigation panel. There are 2 access levels defined by 2 account names: Admin and User.
  • Page 31: Figure A-9. Fs-Gui Passwords Page

    Appendix A Securing QuickServer With Passwords Figure A-9. FS-GUI Passwords Page Figure A-10. Password Recovery Page...
  • Page 32: Appendix B: Vendor Information - Veeder-Root

    The ProtoNode provides capability to support any Veeder-Root serial command by defining customized map descriptors for any command or data type. Refer to Appendix A of the 577014-368 QuickServer Industrial Protocol Gateway Installation And Setup manual. Appendix A (Security Code) of the same manual also contains instructions on using a Security Code for the TLS communications port.
  • Page 33: Table B-3. Tank Veeder-Root Interface To Bacnet And Modbus

    Tank X Tank Low Temperature Warning x034 10X34 Tank X Density Offset Warning x035 10X35 Table B-4. Liquid Sensor Veeder-Root Interface Mappings To BACnet And Modbus Point Name BACnet Object Type BACnet Object ID Modbus Register Sensor X Setup Data Warning...
  • Page 34: Table B-5. Input Veeder-Root Interface To Bacnet And Modbus

    Input X Generator On X005 10X05 Input X Input Out Alarm X006 10X06 Table B-6. Type A Sensor Veeder-Root Interface To BACnet And Modbus Point Name BACnet Object Type BACnet Object ID Modbus Register Type-A Sensor X Setup Data Warning...
  • Page 35: Table B-10. Mag Sensor Veeder-Root Interface To Bacnet And Modbus

    Appendix B Interface To BACnet & Modbus Tables Table B-10. MAG Sensor Veeder-Root Interface To BACnet And Modbus Point Name BACnet Object Type BACnet Object ID Modbus Register MAG Sensor X Setup Data Warninq X001 10X01 MAG Sensor X Communication Alarm...
  • Page 36: Appendix C: "A" Bank Dip Switch Settings

    Appendix C: “A” Bank DIP Switch Settings Table C-1. A Bank DIP Switch Settings For Addresses 26-50 Address...
  • Page 37 Appendix C Table C-2. A Bank DIP Switch Settings For Addresses 51 - 75 Address...
  • Page 38 Appendix C Table C-3. A Bank DIP Switch Settings For Addresses 76 - 100 Address...
  • Page 39 Appendix C Table C-4. A Bank DIP Switch Settings For Addresses 101-125 Address...
  • Page 40 Appendix C Table C-5. A Bank DIP Switch Settings For Addresses 126 - 150 Address...
  • Page 41 Appendix C Table C-6. A Bank DIP Switch Settings For Addresses 151 - 175 Address...
  • Page 42 Appendix C Table C-7. A Bank DIP Switch Settings For Addresses 176 - 200 Address...
  • Page 43 Appendix C Table C-8. A Bank DIP Switch Settings For Addresses 201 - 225 Address...
  • Page 44 Appendix C Table C-9. A Bank DIP Switch Settings For Addresses 226-255 Address...
  • Page 45: Appendix D: Reference

    5 - 90% RH (non-condensing) Compliance With UL Regulations For UL compliance, the following instructions must be met when operating QuickServer. • The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.
  • Page 46: Certifications - Btl Mark - Bacnet® Testing Laboratory

    • This device must not be connected to a LAN segment with outdoor wiring. Certifications - BTL Mark - BACnet® Testing Laboratory The BTL Mark on QuickServer is a symbol that indicates that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing.
  • Page 47 For technical support, sales or other assistance, please visit: www.veeder.com...

Table of Contents