Orbit Merret OM 402PID Manual

4 digit programmable universal pid regulator input dc/pm/ohm/pt/ni/tc/potentiometer

Advertisement

Quick Links

WA R R A N T Y
Y E A R S
OM 402PID
4 DIGIT PROGRAMMABLE
UNIVERSAL PID REGULATOR
INPUT
DC/PM/OHM/PT/NI/TC/POTENTIOMETER
TECHDOK - OM 402PID - 2015 - 3v0 - en

Advertisement

Table of Contents
loading

Summary of Contents for Orbit Merret OM 402PID

  • Page 1 WA R R A N T Y Y E A R S OM 402PID 4 DIGIT PROGRAMMABLE UNIVERSAL PID REGULATOR INPUT DC/PM/OHM/PT/NI/TC/POTENTIOMETER TECHDOK - OM 402PID - 2015 - 3v0 - en...
  • Page 2 Supply of energy from the main line has to be isolated from the measuring leads. ORBIT MERRET, spol. s r.o. Vodnanska 675/30 198 00 Prague 9 Czech Republic Tel: +420 - 281 040 200 Fax: +420 - 281 040 299 e-mail: orbit@merret.eu www.orbit.merret.eu 2 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 3: Table Of Contents

    6.1.3 Setting the Real Time ....55 6.1.4 External input function selection ..55 6.1.5 Optional accessory functions of the keys . . 56 INSTRUCTIONS FOR USE OM 402PID | 3...
  • Page 4: Instrument Description

    Type OM 402PID is a multifunction instrument with the option of confi guration for 8 various input options, easily confi gurable in the instrument menu. In its basic confi guration the OM 402PID has two regulatory relays and two relay alarm outputs. Desired value can either be constant, or defi ned by one of 14 programmes.
  • Page 5 The operation program is freely accessible (www.orbit.merret.eu) and the only requirement is the purchase of OML cable to connect the instrument to PC. It is manufactured in version RS 232 and USB and is compatible with all ORBIT MERRET instru- ments. Another option for connection is with the aid of data output RS 232 or RS 485 (without the need of the OML cable).
  • Page 6: Instrument Connection

    5-6 connect L- to (-) source terminalconnected do not disconnect RS 485 line should have a linear structure - wires (ideally shielded and twisted) should lead from one device to another. 6 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 7: Instrument Connection

    Maximum of 250 mA may be connected to “INPUT - I” (bracket no. 21) , i.e. 10-times range overload. Mind the correct connection/mistaking of current - voltage input. Destruction of measuring resistance in current input (15R) may occur. INSTRUCTIONS FOR USE OM 402PID | 7...
  • Page 8 Example connection of a 3-wire sensor with current signal output powered by instrument’s excitation Supply (+) Output (+) GND (-) 14 15 16 17 18 19 20 21 Excitation INPUT - I Supply (+) Output (+) 8 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 9 By connecting resistor R* we elimintate error message E. I.Ov. (input overflow) when the measured resistance is disconnected Terminals for the measured resistance 14 15 16 17 18 19 20 21 * resistor 100...1000 Ohm INSTRUCTIONS FOR USE OM 402PID | 9...
  • Page 10: Instrument Setting

    Linear menu structure SETTING USER For user operation Menu items are set by the user (Profi/Light) as per request Access is not password protected Optional menu structure either tree (PROFI) or linear (LIGHT) 10 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 11 The operation program is freely accessible (www.orbit.merret.eu) and the only requirement is the purchase of OML cable to con- nect the instrument to PC. It is manufactured in version RS 232 and USB and is compatible with all ORBIT MERRET instruments.
  • Page 12: Symbols Used In The Instructions

    Setting the minus sign is performed by the key on higher decade. When editing the item substraction must be made from the current number (e.g..: 013 > , on class 100 > -87) 12 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 13: Control Keys Function

    SHOW  item will not be displayed in USER menu item will be displayed in USER menu with the option of setting SHOW item will be solely displayed in USER menu INSTRUCTIONS FOR USE OM 402PID | 13...
  • Page 14: Setting "Light" Menu

    Only items necessary for instrument setting Access is password protected Possibility to arrange items of the USER MENU Linear menu structure Preset from manufacture Password “0” Menu LIGHT USER menu Setting the items 14 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 15 Identifi cation SW: version Input Return to measuring OM 402PID IDENT. 78-001 142. 8 mode Upon delay exceeding 60 s the programming mode is automatically discontinued and the instrument itself restores the measuring mode INSTRUCTIONS FOR USE OM 402PID | 15...
  • Page 16 RTD-Cu Thermometer for sensors Cu Type “PM” Example MODE  Type „DC“  Type “PM”  Type “OHM“  Type “RTD-Pt“  Type “RTD-Ni“  Type “T/C“  Type “DU”  Type “RTD-Cu“ 16 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 17 SETTING LIGHT 5. INSTRUCTIONS FOR USE OM 402PID | 17...
  • Page 18 - the DP is automatically shifted after the value is - range of the setting: -99999…999999 confirmed - position of the DP does not affect display projection Example Projection for 0 mV > MIN A = 0 MAX A 18 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 19 FORM. A   decimal point - positioning of the DP is set here in the measuring = 000.o mode Projection of DP on display > 0000 Example 000. o 0000 SETPO.   INSTRUCTIONS FOR USE OM 402PID | 19...
  • Page 20 - the DP is automatically shifted after the value is - range of the setting: -99999…999999 confirmed - position of the DP does not affect display projection Projection for 0 mA > MIN A = -25 Example MAX A 20 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 21 Setting projection of the decimal point - positioning of the DP is set here in the measuring = 000.o mode Projection of DP on display > 0000 Example 000. o 0000 SETPO.   INSTRUCTIONS FOR USE OM 402PID | 21...
  • Page 22 - the DP is automatically shifted after the value is - range of the setting: -99999…999999 confirmed - position of the DP does not affect display projection Projection for 0 Ohm > MIN A = 0 Example MAX A 22 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 23 Setting projection of the decimal point - positioning of the DP is set here in the measuring = 0000 mode Projection of DP on display > 000.o Example 0000 000. o SETPO.   INSTRUCTIONS FOR USE OM 402PID | 23...
  • Page 24 Selection of the type of CONNEC.   sensor connection Menu Connection 2-WIRE 2-wire = 2- WIRE 3-WIRE 3-wire 4-WIRE 4-wire Type of connection - 3 wire > CONNEC. = 3-WIRE Example 2-WIRE 3-WIRE FORM. A 24 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 25 Setting projection of the decimal point - positioning of the DP is set here in the measuring = 0000 mode Projection of DP on display > 000.0 Example 0000 000. 0 SETPO.   INSTRUCTIONS FOR USE OM 402PID | 25...
  • Page 26 Selection of the type of CONNEC.   sensor connection Menu Connection = 2- WIRE 2-WIRE 2-wire 3-WIRE 3-wire 4-WIRE 4-wire Type of connection - 3 wire > CONNEC. = 3-WIRE Example 2-WIRE 3-WIRE FORM. A 26 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 27 Setting projection of the decimal point - positioning of the DP is set here in the measuring = 0000 mode Projection of DP on display > 000.0 Example 0000 000. o SETPO.   INSTRUCTIONS FOR USE OM 402PID | 27...
  • Page 28 C. J . TEM. For thermocoule type “B” the items CONECT. Method and procedure of setting the cold and C.J. TEM. are not available junctions is described in separate chapter on page 90 28 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 29 Setting projection of the decimal point - positioning of the DP is set here in the measuring = 0000 mode Projection of DP on display > 000.0 Example 0000 000. o SETPO.   INSTRUCTIONS FOR USE OM 402PID | 29...
  • Page 30 - range of the setting: -99999…999999 - position of the DP does not affect display projection = 100 Projection for the end > MAX A = 5000 Example 0000 1000 2000 3000 4000 5000 FORM. A 30 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 31 - positioning of the DP is set here in the measuring = 000.o mode Projection of DP on display > 000.o Example 000. o SETPO. Calibration of the beginning and the end of range   of linear potentiometer is on page 43 INSTRUCTIONS FOR USE OM 402PID | 31...
  • Page 32 Selection of the type of CONNEC.   sensor connection Menu Connection 2-WIRE 2-wire = 2- WIRE 3-WIRE 3-wire 4-WIRE 4-wire Type of connection - 3 wire > CONNEC. = 3-WIRE Example 2-WIRE 3-WIRE FORM. A 32 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 33 Setting projection of the decimal point - positioning of the DP is set here in the measuring = 0000 mode Projection of DP on display > 000.o Example 0000 000. o SETPO.   INSTRUCTIONS FOR USE OM 402PID | 33...
  • Page 34 Selecting a type of control TYP. C.   Menu Controls PROP. Proportional = PID Proportional - Integral Proportional - Integral - Derivative Selecting a type of control - PID > TYP. C. = PID Example PROP. 34 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 35 Setting of integral 1. 0 0  constant INTEG.   Setting of integral constant range of the setting: 0,00001…999999 = 1.00 Setting of integral constant > INTEG. = 1.2 Example 1. 0 DERIV. INSTRUCTIONS FOR USE OM 402PID | 35...
  • Page 36 “Requested value” program Selection of function during a power failure - j / OUTAGE = CONTIN. Example CONTIN. LIM. L. 1   36 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 37 SETTING LIGHT INSTRUCTIONS FOR USE OM 402PID | 37...
  • Page 38: Setting Limits

    = 40 - contingent modification of hysteresis or delay „Hystresis”=0, „Delay”=0 may be performed in “PROFI” menu Setting limit 2 > L 2 = 53.1 Example 0531 00531 000531 000531. 00053. LIM. L. 3 38 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 39 - contingent modification of hysteresis or delay „Hystresis”=0, „Delay”=0 may be performed in “PROFI” menu Setting limit 4 > L 4 = 103 Example * subsequent item on the menu depends MENU on instrument equipment INSTRUCTIONS FOR USE OM 402PID | 39...
  • Page 40 - range of the setting: -99999…999999 Display value for the beginning of the AO range > MIN A.O. = 0 Example MAX A. O . Items for “Analog output” are accessible only if incorporated in the instrument. 40 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 41 Decrease the controlled value, inverse output OBOJ. I. Increase/decrease the controlled value, zero in the middle, inverse output = INCREA. Setting of analogue output mode - DECREA. > MOD. A.O. = DECREA. Example INCREA. DECREA. MENU INSTRUCTIONS FOR USE OM 402PID | 41...
  • Page 42: Restoration Of Manufacture Setting

    Restoration of manufacture setting > RE. SET. Example  Type “RTD-Ni“ RE. SET. TYPE LANG. * subsequent item on the menu depends  Type “T/C“ on instrument equipment  Type “DU”  Type “RTD-Cu“ 42 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 43 - prior confirming the flashing “YES” sign the potentiometer traveller has to be in given idle position Calibration of the end of the range > C. MAX Example LANG. INSTRUCTIONS FOR USE OM 402PID | 43...
  • Page 44 - range of the number code 0…9999 - upon setting the password to “0000” the access to menu LIGHT is free without prompt to enter it New password - 341 > PAS. LI. = 341 Example IDENT. 44 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 45 SW number, SW version and current the measuring mode input setting (Mode) - if SW version contains a letter in first position, then it is a customer SW 142. 8 Return to measuring mode INSTRUCTIONS FOR USE OM 402PID | 45...
  • Page 46 • password protected access (unless set as follows under the item SERVIC. > N. PASS. > LIGHT =0) • for access to LIGHT menu passwords for LIGHT and PROFI menu may be used 46 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 47 SETTING PROFI INSTRUCTIONS FOR USE OM 402PID | 47...
  • Page 48 - resetting memory for the storage of minimum SERVIC. EXT. IN. and maximum value achieved during measurement PROG. KEYS CL. MEM.   Resetting the instrument memory - resetting memory with data measured in the “RTC” mode 48 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 49   Ohmmeter AD. RES.   RTD-Pt Thermometer for Pt xxx LEADS RTD-Ni   Thermometer for Ni xxxx RTD-Cu   Thermometer pro thermocouples   Display for linear potentiometers RTD-Cu   Thermometer for Cu xxx INSTRUCTIONS FOR USE OM 402PID | 49...
  • Page 50 NO  CHAN. A.  FIL. A  MAT. FN. .  MIN  MAX.  LIM. 1  P. TARE  COLD. J. ENTER MNU. LE. LIM. 1  LIM. 2.  LIM. 3  LIM. 4  SETPO. 50 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 51 0%  25%  50%  75% 100% Upon delay exceeding 60 s the programming mode is automatically discontinued and the AUXIL. 0%  25%  50%  75% 100% instrument itself restores the measuring mode INSTRUCTIONS FOR USE OM 402PID | 51...
  • Page 52 6. 2 -1k T/C S T/C E T/C J 5. 0 -10k T/C T T/C K T/C N 6. 2 -10k T/C L T/C R T/C S T/C T T/C L LIN. P OT. 52 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 53 - when using compensation box Method and procedure of setting the cold junctions is described in separate chapter on page 90 For thermocoule type “B” the items CONECT. and C.J. TEM. are not available INSTRUCTIONS FOR USE OM 402PID | 53...
  • Page 54 - prior confirmation of the displayed prompt “ YES“ OUTPUT. MODE it is necessary to substitute the sensor at the end of the conduct by a short-circuit SERVIC. EXT. IN. CONNEC. PROG. KEYS. AD. RES. LEADS 54 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 55 “Setpoint” here, see chapter 6.5 EXT. 1 > HOLD EXT. 2 > LOCK. K. Procedure identical for EXT. 2 and EXT. 3 EXT. 3 > TARE INSTRUCTIONS FOR USE OM 402PID | 55...
  • Page 56 Preset values of the control keys STAR. A   Launch of control process to input “Setpoint” LEFT Show Tare Show Max. value DOWN Show Min. value Setting is identical for LEFT, DOWN, UP ENTER w/o functione and ENTER 56 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 57   TARE Temporary projection of “TARE” value P. TARE   Temporary projection of “P. TARE” value   Temporary projection of COLD. J. “CJC” value Setting is identical for LEFT, DOWN, UP and ENTER INSTRUCTIONS FOR USE OM 402PID | 57...
  • Page 58 Direct access to item “LIM 3” PROG. KEYS. SETPO.   Direct access to item LIM 4 “LIM 4”   SETPO. Direct access to item “SETPO.” Setting is identical for LEFT, DOWN, UP and ENTER 58 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 59 SETTING PROFI INSTRUCTIONS FOR USE OM 402PID | 59...
  • Page 60 FORM. A P. T AR. A does not show the “T” symbol - range of the setting: -99999…999999 LOG. A SERVIC. MIN. M AX PROG. Setting is identical for CHAN. A and CHAN.B 60 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 61 Floating filter Constant F.A = 5.0 - this menu item is always displayed after selection of particular type of filter Exponential filter Constant F.A = 5.0 Setting is identical for CHAN. A and CHAN.B INSTRUCTIONS FOR USE OM 402PID | 61...
  • Page 62 Setting is identical for CHAN. A and CHAN.B   FROM A Setting the initial interval value - setting range: -99999…999999   Setting the final interval TO A value - setting range: -99999…999999 62 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 63 CHAN. A - selection of input, from which the real value will be evaluated CHANNE. CHAN. B ACTUAL. FIL. A OUTPUT. CONTR. TYP. C. SERVIC. MIN. M AX PROP. PROG. INTEG. DERIV. SATUR. OUTAGE INSTRUCTIONS FOR USE OM 402PID | 63...
  • Page 64 Setting of proportional constant INPUTS CHAN. A SETPO. 1. 0 0 - setting range: 0…999999 = 1.00 CHANNE. CHAN. B ACTUAL. OUTPUT. CONTR. TYP. C. SERVIC. MIN. M AX PROP. PROG. INTEG. DERIV. SATUR. OUTAGE 64 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 65   Setting of integral constant SERVIC. MIN. M AX PROP. - setting range: 0,00001…999999 PROG. INTEG. = 1.00 DERIV. DERIV.   Setting of derivative SATUR. constant OUTAGE - setting range: 0…999999 = 1.00 INSTRUCTIONS FOR USE OM 402PID | 65...
  • Page 66 OUTAGE of power loss   STEP Control process will be resumed from the beginning of the last step PROG.   Control process will be resumed from the beginning of the last program 66 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 67 CHAN. B CHAN. A OUTPUT. CONTR. FIL. A   Evaluation of min/max value is off SERVIC. MIN. M AX   From “Channel A” CHAN. A PROG.   FIL. A From “Channel A” after digital filters processing INSTRUCTIONS FOR USE OM 402PID | 67...
  • Page 68: Setting Data Logging

    - selection of the mode in the event of full instrument memory CHANNE. LIMITS START   Rewriting values prohibited OUTPUT. DATA STOP SERVIC. AN. OUT. PERIOD.   Rewriting values permitted, the oldest get rewritten by PROG. DISP. the latest 68 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 69 Recordings can take place either inside or outside of selected time intervals. The duration of re-writing can be determined by the number of channels recorded as well as by the recording rate. INSTRUCTIONS FOR USE OM 402PID | 69...
  • Page 70 Z < 0 - Switch-on relay TYPE > SWITCH-OFF LED signalization Z > 0 - Switch-off relay TYPE > SWITCH-ON LED signalization Z < 0 - Switch-off relay TYPE > SWITCH-OFF LED signalization 70 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 71 TIM. L. 1   Limit evaluation from “Min. value” T. TOT.   Limit evaluation from  T. OFF “Max. value” T. ON INSENS. Setting is identical for LIM 1, LIM 2, LIM 3 and LIM 4 INSTRUCTIONS FOR USE OM 402PID | 71...
  • Page 72 “0”, otherwise it is activated for a period specified in “TIM. L.1” Setting is identical for LIM 1, LIM 2, LIM 3 and LIM 4 72 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 73: Setting Limits

    - negative time > relay switches off after crossing the limit (LIM. L.1) and the set negative time (TIM. L.1) Setting is identical for LIM 1, LIM 2, LIM 3 and LIM 4 INSTRUCTIONS FOR USE OM 402PID | 73...
  • Page 74 LIM 3 TYP. L. 1 SERVIC. AN. OUT. LIM 4 LIM. L. 1 PROG. DISP. HYS. L. 1 ON L. 1 OFF L. 1 TIM. L. 1 T. TOT. T. OFF T. ON INSENS. 74 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 75 CHANNE. LIMITS ADDR. OUTPUT. DATA ADR. P. B . ADR. P. B .   Setting instrument address SERVIC. AN. OUT. PROT. - PROFIBUS PROG. . DISP. - setting in range 1…127 = 19 INSTRUCTIONS FOR USE OM 402PID | 75...
  • Page 76 MAX. filters processing ACTION.   MAT. FN. AO evaluation from  “Math. functions”   AO evaluation from  “Min. value”   AO evaluation from “Max. value”   ACTION. Analogue output is controlled by controller’s output 76 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 77: Setting Analog Output

    MOD. A. O . AO range - range of the setting: -99999…999999   Assigning the display value MAX A. O . to the end of the AO range - range of the setting: -99999…999999 = 100 INSTRUCTIONS FOR USE OM 402PID | 77...
  • Page 78 A” SERVIC. AN. OUT. MAX.   Projection of values FIL. A from “Channel A” after PROG. DISP. digital filters processing   Projection of values from “Min. value”   Projection of values from “Max. value” 78 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 79 Selection of the two small AUXIL. displays’ brightness - green LED   Display brightness - 25 %   Display brightness - 50 %   Display brightness - 75 %   Display brightness - 100 % 100% INSTRUCTIONS FOR USE OM 402PID | 79...
  • Page 80: Light"/„Profi

    - linear menu > items one after another IDENT. PROFI   Active PROFI menu - complete programming menu for expert users - tree menu Change of setting is valid upon next access into menu 80 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 81: Restoration Of Manufacture Setting

    LIGHT menu   deletes data stored in FLASH   cancels or linearization tables   clears tare   restore manufacture calibration   restore manufacture setting INSTRUCTIONS FOR USE OM 402PID | 81...
  • Page 82: Calibration - Input Range (Du)

    LIGHT and PROFI menu. OUTPUT. CALIB. - numerci code range: 0…9999 - universal passwords in the event of loss: SERVIC. LANG. LIGHT Menu > „8177“ PROFI Menu > „7915“ PROG. N. PASS. IDENT. 82 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 83: Instrument Identification

    - if the SW version reads a letter on first position, OUTPUT. CALIB. it is a customer SW SERVIC. LANG. Pos. Description PROG. N. PASS. type of instrument SW: number - version IDENT. the input type INSTRUCTIONS FOR USE OM 402PID | 83...
  • Page 84 - this setting is identical for all external inputs (1…3) If another function is assigned to either a front panel button or the external input, it will also be executed (chapter 6.1.5a/6.1.4a) 84 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 85 INPUTS PROG. 1 STR. 1 00. 0 0. 0 0 CHANNE. PROG. 2 DAY. 1 OUTPUT. PROG. 3 DAT. 1 SERVIC. PROG. 4 TIM. 1 PROG. PROG. 5 PGM. 1 PROG. 1 4. INSTRUCTIONS FOR USE OM 402PID | 85...
  • Page 86 Setting the date when the program is to be launched - setting in range: 01.01.00…31.12.99 TIM. 1   Setting the time when the program is to be launched - setting in range: 00.00.00…23.59.59 86 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 87 SETTING PROFI INSTRUCTIONS FOR USE OM 402PID | 87...
  • Page 88: Setting Items Into "User" Menu

     return to item SHOW  item will not be displayed in USER menu item will be displayed in USER menu with editing option SHOW item will be solely displayed in USER menu 88 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 89 Limit one. You can exit the setting by pressing the button by which you store the latest setting and pressing the button will take you back to the measuring mode INSTRUCTIONS FOR USE OM 402PID | 89...
  • Page 90 – when measuring without reference thermocouple set in the instrument menu to – when measuring temperature without reference thermocouple the error in measured data may be as much as 10°C CONECT. EXT. 1 TC (applies for setting 90 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 91: Error Statements

    E. CLR Memory was empty (presetting carried out) possible failure in calibration E. . OUT. Analogue output current loop disconnected check wire connection INSTRUCTIONS FOR USE OM 402PID | 91...
  • Page 92: Data Protocol

    (D) (D) (D) (D) (D) <ETX> <BCC> Command confirmation (instrument) <CR> <CR> Messbus No - data is transmitted permanently <CR> <CR> <DLE> <NAK> Instrument identification <CR> HW identification <CR> One-time transmission <CR> Repeated transmission <CR> 92 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 93 Confirm error statement format >HH <CR>, where HH is value in HEX format and range 00 …FF . The lowest bit stands for „Relay <BCC> Check sum -XOR 1“, the highest for „Relay 8“ INSTRUCTIONS FOR USE OM 402PID | 93...
  • Page 94: Technical Data

    2x relays with switch-off contact (Form C) (250 VAC/50 VDC, 5 A)* or 2x SSR (250 VAC/ 1 A)* Relay: 1/8 HP 277 VAC, 1/10 HP 125 V, Pilot Duty D300 * values apply for resistance load 94 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 95 5,00 2,50 1,25 1,00 0,62 0,38 0,22 0,09 0,05 (Type: OHM, RTD, T/C) No.of channels: 2 3,33 1,066 0,83 0,66 0,42 0,26 0,14 0,06 0,03 PI - Primary insulation, DI - Double insulation INSTRUCTIONS FOR USE OM 402PID | 95...
  • Page 96: Instrument Dimensions And Instalation

    3. press the travellers close to the panel INSTRUMENT DISASSEMBLY 1. slide a screw driver under the traveller wing 2. turn the screw driver and remove the traveller 3. take the instrument out of the panel 96 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 97: Certificate Of Guarantee

    - unavoidable event - una - other unprofessional interventions - other unp The manufacturer performs guarantee and post.guarantee repairs unless provided for otherwise. ms guarantee and post.guaran for otherwise. Y E A R S INSTRUCTIONS FOR USE OM 402PID | 97...
  • Page 98 NOTE 98 | INSTRUCTIONS FOR USE OM 402PID...
  • Page 99 NOTE INSTRUCTIONS FOR USE OM 402PID | 99...
  • Page 100 ORBIT MERRET, spol.s r.o. and that our company has taken all measures to ensure conformity of all products of the types referred-to hereunder, which are being brought out to the market, with technical documentation and requirements of the appurtenant Czech statutory orders.