Download Print this page

Facility Explorer FX Series Installation Instructions

Supervisory controller lon card

Advertisement

Quick Links

FX Supervisory Controller LON Card
Application
The FX Supervisory Controller LON Option Card
provides L
W
® Free Topology Transceiver
ON
ORKS
(FTT)-10A communications capability to the FX
Supervisory Controllers (FX20, FX30E, FX60, FX60E,
and FX70). See Figure 1.
Up to two LON Option Cards may be installed. If one
LON Option Card is installed, it operates as LON1,
regardless of the slot used. If two LON Option Cards
are installed, LON1 is Option Slot 1 and LON2 is
Option Slot 2 (see Figure 3 for locations of option
slots).
For related information on FX Supervisory Controllers
mounting and wiring, refer to the FX Supervisory
Controllers Installation Instructions
(Part No. 24-10174-77).
Figure 1: FX20/FX30E/FX60/FX60E LON Card
Figure 2: FX70 LON Card
© 2014 Johnson Controls, Inc.
Part No. 24-10174-34, Rev. C
Installation Instructions
Installation Instructions
IMPORTANT: For the FX70, carefully pry up the
shield tab to install the option card under the tab. Do
not install the Option Card in slot 2 with the card
resting on top of the shield tab. Otherwise, an
electrical short or some other issue from misaligned
card header pins may result.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Issue Date April 9, 2014
www.johnsoncontrols.com
1

Advertisement

loading

Summary of Contents for Facility Explorer FX Series

  • Page 1 Installation Instructions Issue Date April 9, 2014 FX Supervisory Controller LON Card Installation Instructions Application IMPORTANT: For the FX70, carefully pry up the The FX Supervisory Controller LON Option Card shield tab to install the option card under the tab. Do provides L ®...
  • Page 2 Installation IMPORTANT: Avoid hot plug-in or removal of any option card from the FX Supervisory Controllers; that Parts Included is, do not remove any card with power applied. If the Unpack the LON Option Card and inspect the contents unit switches to battery operation, wait for all Light of the package for damaged or missing components.
  • Page 3 Carefully insert the pins of the LON card into the 12. Replace the FX Supervisory Controller cover. If socket of the appropriate option slot. The accessory modules were unplugged, plug them mounting holes on the LON card should line up back into the FX Supervisory Controller as before, with the standoffs on the FX Supervisory and secure.
  • Page 4 Operation LEDs Two LEDs are visible on the top of the LON Option Card. To see them, remove the cover from the FX Supervisory Controller. The LEDs operate as follows: • RX (green): Receive—indicates that another device is transmitting a message. ORKS •...

This manual is also suitable for:

Fx20Fx60Fx30eFx60e