MODEL RRU-UNV INSTALLATION INSTRUCTIONS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS
SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. This product can be used with LED, ballast, tungsten, and general use loads.
2. Make sure all connections are in accordance with the National Electrical Code and local regulations.
3. To reduce the risk of electric shock, disconnect both normal and emergency power supplies before servicing.
4. This product is intended to be used to control indoor and outdoor located loads.
5. An unswitched AC power source is required (120-240VAC/277VAC).
6. Do not install near gas or electric heaters.
7. Do not attempt to service a sealed Emergency Power Control. When malfunctioning, return to the
manufacturer: LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577.
8. The use of accessory equipment is not recommended by the manufacturer and may cause unsafe condition.
9. Do not use this product for other than its intended use.
10. Servicing should be performed by qualified service personnel.
11. Equipment should be mounted in locations and at heights where it will not readily be subjected to
tampering by unauthorized personnel.
LVS, Inc. warrants to the original purchaser/user for the published warranty period from the date of shipment that should LVS instruments or
equipment prove defective by reason of improper workmanship or material, LVS will repair or replace the same equipment without charge.
This warranty does not cover defects or malfunctions arising from improper installation, operation or repair, or neglect, accident, or abuse. LVS
will honor its warranty provided the equipment has not been physically damaged or improperly installed or connected. To obtain warranty/re-
pair, the defective product should be shipped freight prepaid within the warranty period to the address below. To the extent permitted by
applicable law, all warranties extending beyond repair or replacement as described above are disclaimed, including the implied warranties of
merchantability and fitness for a particular purpose. Where applicable law prohibits disclaimers or the implied warranties of merchantability
and fitness; those warranties are limited to 12 months from date of shipment. LVS provides a 90 day money back guarantee if equipment
does not perform in accordance with LVS published specifications. The liability of LVS and its agents under all warranties is limited to repair and
replacement as described herein and under no circumstances shall there be liability for any other kind of loss, damage, or labor, either conse-
Electrical Specfications
120-240/277V Sensing Input
Form C (N.O+N.C.) Contact
20 Amp Ballast Load Rating (120-277V)
20 Amp General Use Rating (120-277V)
1200W Incandescent Load Rating (120V)
1500W Incandescent Load Rating (277V)
UL924 Listed (usUL/cUL)
LVS

! IMPORTANT SAFEGUARDS !

SAVE THESE INSTRUCTIONS
5-Year Limited Warranty
quential or for injury to person or property or otherwise.
U L
®
C
US
UL924 LISTED
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216
Phone: 510-352-9600
Web: WWW.LVSCONTROLS.COM

Mechanical Specifications

Mounts in 4-11/16" Junction Box with Extension Box
Use single gang plaster ring or blank cover
Suitable for installation in the plenum
Tested to UL2043 UL94-5VA Plastic Flame Rating
Shipping Weight: 8 oz Color : White
Temperature: -40˚C-65˚C (-40˚F - 149˚F)
Flush Mounted Size: 4-1/2" x 2-3/4" x 1/4"
Body Size: 2-7/8" x 1-3/4" x 1-7/32"
1-800-982-4587
Fax: 510-352-6707
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RRU-UNV and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for LVS RRU-UNV

  • Page 1 fitness; those warranties are limited to 12 months from date of shipment. LVS provides a 90 day money back guarantee if equipment does not perform in accordance with LVS published specifications. The liability of LVS and its agents under all warranties is limited to repair and replacement as described herein and under no circumstances shall there be liability for any other kind of loss, damage, or labor, either conse- quential or for injury to person or property or otherwise.
  • Page 2 In the past, all emergency lights were left on 24 hours a day to meet safety codes. Now you can specify & install a UL924 Listed Emergency Shunt Relay RRU-UNV, which converts up to 20A of normal light fixtures to approved emergency lights. During normal operation, the RRU-UNV switches designated emergency lights on and off.
  • Page 3 Installation In order to install the RRU in accordance with national/local code requirements, a qualified electrician should review & understand the installation instructions. Check voltage & current requirements. Verify & lock out circuit breakers on both regular (utility) power & 24 hour emergency generator or inverter circuit.
  • Page 4 A dedicated switch or line voltage dimmer controls emergency lighting in a space. Upon loss of normal power, the emergency lighting comes on at full brightness regardless of switch or dimmer position. NOTE: RRU-UNV is not for use with 0-10V DIMMER. Use RRU-X-UNV or EPC-2-D. #5 YELLOW...

Table of Contents