Weil-McLain WTGO Series Manual page 10

Oil-fired natural draft water boiler
Table of Contents

Advertisement

Perform hydrostatic pressure test:
1. Refer to FIGURE 4 and Control Tapping Table
to install:
a. Boiler drain.
b. Water pressure gauge (test only). Be sure
gauge can handle test pressure.
c. Air vent in upper "N" tapping.
d. Plugs in remaining tappings.
2. Fill boiler. Vent all air. Pressure test boiler at
1½ times working pressure. For boilers split
and reassembled, test between 75 and 85 psig.
Do not leave boiler unattended.
Cold water fill could expand and
damage cast iron, resulting in severe personal
injury, death or substantial property damage.
3. Check for maintained gauge pressure for more
than 10 minutes. Visually check for leaks if
gauge pressure drops.
4. Drain boiler. Repair leaks if found.
Do not use petroleum-based
compounds to repair leaks.
Damage to system components can result,
causing property damage.
5. Re-test boiler after repairing leaks.
6. Remove pressure gauge, air vent and plugs
from tappings used for controls.
7. Visually check:
a. Sealing rope placement
b. Metal-to-metal contact around port openings.
c. Flue collector hood seal.
d. Burner mounting door seal.
R1
Front Section
10
Install Non-Packaged Boiler
N
E3
C
L
B1
H
Control Tapping Location
carbon monoxide emissions, which can lead to
severe personal injury or death.
Install jacket (sizes 7 through 9 only):
Before installing jacket, remove burner mounting
door. See jacket instructions for details.
Install boiler controls:
See Control Tapping Table and FIGURES 4 and 5
to install controls.
1. Install tankless heater control if tankless
heater is used. If not furnished, use operating
control with maximum 10°F differential.
2. Install limit control. If not furnished, use high
limit with maximum 220°F setting.
3. Affix CP number label(s) on jacket front panel.
CONTROL TAPPING TABLE
LOCATION
SIZE
B1
1½"
B2
1½"
C
1½"
E3
H
L
N
R1
FIGURE 4
Obtain gas-tight seal to prevent
possible flue gas leakage and
FUNCTION
Return Piping
Alternate Return Piping
for "A" WTGO
Supply Piping
¾"
Pressure-Temperature Gauge
¾"
Drain Valve
High Limit Control
¾"
(in Tankless Heater Cover Plate)
Air Vent or
½"
Expansion Tank Piping
¾"
Relief Valve
Back Section
CONTINUED