Three-way Mixing Globe Valves
USE
3F.. series valves are used to control fl uids belonging to the
group showed in the table in accordance to article 9 of 97/23/
CE (PED) directive, in air-conditioning, thermoventilation and
heating plants and in industrial processes; therefore, they cannot
be used as safety valves.
MANUFACTURING CHARACTERISTICS
They consist in a 3-way valve body to be assembled on electrical
bidirectional actuator.
MOTORIZED VALVES TECHNICAL CHARACTERISTICS AND PERFORMANCES
Model
Technical data
Construction
Body
Seat
Plug
Stem (D 9mm)
Control characteristic
Stem packing
Max. fl uid temp. °C
Min. fl uid temp. °C
Fluid
(6)
Connections
(8)
max Kvs leakage %
1
(
) For applications with possible ice formation on stem and packing,
see 248 accessory.
2
(
) Graphite packing for high temperatures; forced lubrication on extended
neck. Tefl on packing for low temperatures, see (
3
(
) Due to the bellows presence, the max applicable pressure must not
be higher than 5 bar
4
(
) For applications on fl uids from -10 to -20 °C replace letter P with the
T, e.g. 3FAA50T. In such case the max temperature is 230°C
st
1
Issue rev. c
ISO 9001
3FGB
DN 25÷150
DN 25÷80
PN16
cast iron
spheroidal cast iron
cast iron
stainless steel
forged brass
stainless steel
stainless steel
stainless steel
direct way =
direct way = equal
equal perc. (DN25÷65)
perc.
linear (DN80)
Angle way = linear
angle way = linear
EPDM O-Ring
(5)
Tefl on V-ring
150
-10
(1)
Group 2
Group 2
Flanged PN16
Flanged PN25
direct way 0,03
angle way 2
4
).
02/12
CONTROLLI S.p.A.
16010 SANT'OLCESE Genova - Italy
Tel.: +39 01073061
E-mail: info@controlli.eu
3FSA
3FSAS
DN 25÷80
PN25
PN25
spheroidal cast iron
stainless steel
stainless steel
stainless steel
direct way =
equal perc. (DN25÷65)
linear (DN80)
angle way = linear
stainless steel bellows
230
300
-10
(1)
-10
(1)
Group 1
Flanged PN25
0,02
0,02
(
5
) Double O-ring and graphite tefl on scraper ring.
(
6
) Group 1: water, overheated water, steam, diathermic oil.
For different fl uids belonging to group 1, please contact our Sales
Support.
Group 2: water, overheated water, steam.
For different fl uids belonging to group 2, please contact our Sales
Support
(
7
) PN25 only for 3FAA125 and 3FAA125P.
(
8
) Leakage is measured according to the EN1349 standard.
1
Fax: +39 0107306870/871
Web: www.controlli.eu
3FAA
DN 25÷125
DN 25÷125
(3)
PN40
(7)
acciaio
stainless steel stainless steel
stainless steel stainless steel
stainless steel stainless steel
linear
Tefl on V-ring
230
-10
(1)
Group 2
Flanged PN40 Flanged PN40
0,02
3F..
3FAAP
PN40
(7)
acciaio
linear
(2)
350
-20
(1) (4)
Group 1
0,02
DBL317e
Need help?
Do you have a question about the 3F Series and is the answer not in the manual?