Heatmaker H, HP and HW Operating, Installation TRIANCO & Maintenance Instructions HEATMAKER THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODES BY A QUALIFIED INSTALLER. To the Installer: After installation these instructions must be given to the homeowner or left on or near the boiler.
LOCATING UNIT WITH INSTALLATION RESPECT TO VENTILATION CHIMNEY VENTING (USA Only) ALTERNATE VENTING METHOD (Canada Only) Figure 3. HW-M2. Figure 4. H-M2. SUPPLY 3.5" deep DOMESTIC RETURN...
Page 5
Table 1. Table 2. Type B Double Connector Diameter to be used with Vent and Connector Diameter (A & D) chimney areas within the size limits at bottom Height Lateral Height Lateral 4" 5" 6" 7" 8" Appliance Rating in MBH Appliance Rating in MBH Fan Assist Fan Assist...
THE DIRECT VENT KITS AIR SOURCE FOR COMBUSTION (WHEN NOT DIRECT VENTED) & INSTALLING DIRECT VENT KITS LOCATING THE VENT ON AN OUTSIDE WALL Figure 11. 3" VENT PLUG INTAKE AIR SCREEN 4" MIN. DIA 5" TEE H, HP or HW with Separate Air Source.
GAS CONNECTION TO HEATMAKER NSTALLATIONS WITH WATER CONTAINING GRAINS OF HARDNESS OR HIGHER MUST BE INSTALLED WITH APPROPRIATE WATER TREATMENT Figure 12. & Table 4. Capacity of Pipe in MBTU / HR Length (.6 Specific Gravity) Pipe ½" ¾" 1" 1¼"...
ELECTRICAL CONNECTIONS Figure 18. Single Zone. Set Thermostat Anticipator to 0.9 amp Figure 19. Zoning with Zone Valves. Figure 20. Zoning with 3 wire Zone Valves. LEGEND Disconnect Switch 24-Volt Thermostats. Figure 21. Zoning with Circulators. Zone Circulators - Max 5 AMP 120 VAC.
HYDRONIC SYSTEMS CONNECTIONS WALL MOUNTING INSTRUCTIONS PALOMA/HYTECH REPLACEMENT PLUMBING ACCESSORIES INSTALLATION & NEW WALL MOUNT INSTALLATION GAS SUPPLY CONNECTION...
Page 15
VENTING THE HP-M2-SERIES ELECTRICAL CONNECTIONS & HP WIRING BOX WHT/RED PALOMA PAK/HYTECH TRANSFORMER RELAY BLACK CONTROL PAK BLUE SYSTEM PUMP(S) WHITE 120VAC H O T NEUTRAL I N P U T...
BOILER CONTROL DHW COIL REPLACEMENT STACK SWITCH TRANSFER TANK AND DOMESTIC HOT WATER COIL (HW-M2 Series Only) TANK REPLACEMENT THERMOSTATIC UNION (H(P)-M2-Series Boilers Only) TIME DELAY RELAY (TDR)
SEQUENCE OF OPERATION TROUBLE SHOOTING (DETAILED FLOW CHARTS ON PAGES 26-32). CODE NORMAL NOTE: If the stack switch contacts OPERATION are closed for any reason when the blower isnt operating a sequence will not occur and after 45 seconds the control will lock out ...
GENERAL TROUBLE SHOOTING RESET BOILER CONTROL BY INTERUPTING POWER AT SIDE OF UNIT FOR 15 SECONDS ê 1. IS SERVICE SWITCH ON? GREEN LIGHT COMES ON è 2. IS CIRCUIT ON? 3. ARE FUSES OR CIRCUIT BREAKER OK? ê ê ê...
Page 27
TESTING LIMIT CIRCUIT (YOU MUST COMPLETE PAGE 26 FIRST) VIOLET 1. SWITCH BOILER ON 2. CHECK FOR 24V AT PIN #6 "CONTROL" NOTE: PLUG ORIENTATION MAY DIFFER FROM DIAGRAM NO - UNPLUG CN6 FROM BOILER CONTROL AND TEST AS INDICATED ê...
Page 28
RED "PURGE" LIGHT FLASHING (YOU MUST COMPLETE PAGE 26 FIRST) RESET BOILER CONTROL BY SWITCHING POWER OFF FOR 15 SECONDS AND THEN ON AGAIN ê WITH A CALL FOR HEAT / HOT WATER AFTER APPROX. TWO SECONDS GREEN LIGHT COMES ON AND BLOWER STARTS ê...
Page 29
CHECKING BLOWER (YOU MUST COMPLETE PAGE 28 FIRST) RESET BOILER CONTROL BY SWITCHING BOILER SWITCH OFF FOR 15 SECS, THEN BACK ON. ê WITH A CALL FOR HEAT / HOT WATER, AFTER TWO SECONDS DOES GREEN POWER LIGHT COMES ON. ê...
Page 30
CHECKING STACK SWITCH (YOU MUST COMPLETE PAGE 29 FIRST) 1. TURN OFF BOILER SWITCH 2. REMOVE BOTH TUBES FROM STACK SWITCH AND DISCONNECT ELECTRICAL WIRES 3. CHECK FOR CONTINUITY ACROSS SWITCH TERMINALS NO CONTINUITY CONTINUITY OHMS) (0 OHMS) ê ê REPLACE STACK 1.
Page 31
RED "VALVE/FLAME" LIGHT FLASHING (YOU MUST COMPLETE PAGE 26 FIRST) ARE GAS VALVES AND GAS METER TURNED ON. IS THERE GAS IN LP TANK (LP UNITS). ê ê RESET BOILER BY INTERUPTING POWER FOR TURN ON VALVES, FILL LP TANK ON LP 15 SECONDS - WHEN "VALVE/FLAME"...
Page 32
CHECKING PUMP WITH A CALL FOR HEAT RESET BOILER CONTROL BY SWITCHING OFF BOILER SWITCH FOR 15 SECS. AND THEN ON AGAIN. ê AFTER TWO SECONDS DOES GREEN POWER LIGHT COME ON? ê ê PUMP OPERATES? REFER TO GENERAL TROUBLE SHOOTING SECTION PAGE 26 ê...
Page 34
Installer: Date of Installation: Serial Number: NOTES:...
Figure 23. H(P) Wiring Diagram. Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify Proper Operation After Servicing! Figure 24. H(P) Ladder Diagram. FUSE...
Page 37
Figure 25. HW Wiring Diagram. Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify Proper Operation After Servicing! Figure 26. HW Ladder Diagram. FUSE...
Page 38
Quick Reference Trouble Shooter S9301A CONTROL MODULE...
Page 39
QUICK REFERENCE TROUBLE SHOOTER FOR MORE INFORMATION SEE INDEX...
Page 40
Installer's Leave It Right Check List VENTING Ö Ö Ö Ö PIPING Ö Ö Ö Ö ELECTRICAL Ö Ö Ö Ö IMPORTANT Ö Ö Ö Ö TRIANCO-HEATMAKER, Inc. 111 York Avenue Randolph, Massachusetts 02368 Part No. 1 - 510 Telephone (781) 986-9100 2 M - 11/19/97 Fax (781) 986-9907...