RotorFlow units monitor dynamic fluid flow. The rotor reacts to
turbulence, pulsation, entrained air, and other flow anomalies induced in
the flow stream by other process hardware. For optimum performance,
install RotorFlow units where nominal flow conditions exist, with ports
located at the top. Incoming flow may be placed to either port. A
minimum of 8" of straight pipe on the inlet side is recommended.
Low Flow Applications
A low flow adapter is supplied with all RotorFlow units. It is used to produce accurate response at low flow rates. Press fit the
adapter as shown above, in the port selected for incoming flow. See Flow Range Chart below.
Body
Port Size
Material
NPT
.25"
Polypropylene
.50"
.25"
.50"
Brass
.75"
1.0"
9/16"-18**
.50"
316 Stainless
Steel
.75"
1.0"
Input
Part
Power
Number
12 VDC
155424
24 VDC
155425
110 VAC
155876
12 VDC
155484
24 VDC
155485
110 VAC
155886
12 VDC
156264
24 VDC
156265
110 VAC
156266
12 VDC
156267
24 VDC
156268
110 VAC
156269
12 VDC
180394
24 VDC
180395
110 VAC
180396
24 VDC
181688
115 VAC
181689
24 VDC
165073
110 VAC
165074
24 VDC
165077
4.0 to 20.0
110 VAC
165078
24 VDC
181691
115 VAC
181692
24 VDC
181693
115 VAC
181694
RFS-2500 Series
®
RotorFlow
Sensors
Flow Range-GPM
Standard
Low Flow*
Range
Range
0.5 - 5.0
0.1 - 1.0
4.0 - 20.0
1.5 - 12.0
0.5 - 5.0
0.1 - 1.0
4.0 - 20.0
1.5 - 12.0
5.0 - 30.0
N/A
8.0 - 60.0
N/A
0.5 - 5.0
0.1 to 1.0
1.5 to 12.0
5.0 - 30.0
N/A
8.0 - 60.0
N/A
Instruction Bulletin No.
157261
Rev. G
Adapter
Part Number
* With use of low flow
adapter supplied
152147
151832
152147
151832
N/A
N/A
152147
** Straight thread with O-
151832
ring seal
N/A
N/A

Advertisement

loading

Summary of Contents for Gems RotorFlow RFS-2500 Series

  • Page 1 ® RotorFlow Sensors (For Additional Information, See Gems' "Level, Flow and Pressure Catalog) RotorFlow units monitor dynamic fluid flow. The rotor reacts to turbulence, pulsation, entrained air, and other flow anomalies induced in the flow stream by other process hardware. For optimum performance, install RotorFlow units where nominal flow conditions exist, with ports located at the top.
  • Page 2 Installation: RotorFlow sensors connect to piping via NPT mating threads forms. The following guidelines are provided to assist with installation for a leak-free seal, without damage to the unit: 1) Apply pipe thread sealant to male pipe threads. 2) Thread RotorFlow unit onto male pipe thread until hang-tight . 3) Tighten pipe 1 to 1/2 additional turns. 4) If improper seal results, continue turning pipe into unit in 1/4 turn increments.
  • Page 3: Specifications

    Switch Set Point Calibration with LED Signal With the unit installed in the line and power supplied, complete the following steps to calibrate switch actuation point with proper flow rate. A small flat-blade screwdriver is all that is required. 1. Adjust liquid flow in the line to the rate at which actuation is desired.
  • Page 4: Electrical Data

    Contact GEMS if life cycle testing is Flow switches must not be field repaired. required. Physical damaged sustained by the product may render it unserviceable. Gems Sensors & Controls | One Cowles Road | Plainville, CT 06062-1198 Telephone: 1-800-378-1600 | Email: info@gemssensors.com | www.GemsSensors.com...