1.- Introduction
MODBUS card is designed to be installed in SNMP port of all of our Online UPS. This card
is able to provide communication for the UPS under following protocol:
- Implements MODBUS RTU protocol
- Provides MODBUS functions including read holding register and write registers.
- Provides RS232 & RS485 interface
2.- Product Description
1. RS-485 port
2. RS-485/RS232 port
3. Connector to the UPS
4. Address switch
3. Installation
1. Configure Modbus ID (according to section 4)
2. Configure communication format (according to section 4)
3. Configure RS-485 (according to section 4)
4. Insert Modbus card into the intelligent slot in the UPS (/according to figure 1)
5. Connect AC input to the UPS
6. Connect Modbus card to the computer (an external converter could be necessary)
MODBUS RS-485 CARD
REFERENCE MANUAL
5. Communication setting
6. Resistance switch
7. Jumpers
Figure 1: Remove slot cover & Insert Modbus card into the slot
4. Configuration
4.1. Configure Modbus ID:
Configure using SW1:
Switch down = ON = 1.
Switch up = OFF = 0.
First bit is in the right switch.
4.2. Configure Communication format:
Configure using switches from 1 to 4 in SW2
Function
Baud rate
Parity
check
1
MODBUS RS-485 CARD
Bit Setting
Configuration
# 1
# 2
OFF
OFF
2400bps
OFF
ON
4800bps
ON
OFF
9600bps
ON
ON
19200bps
# 4
# 3
OFF
OFF
Even parity
OFF
ON
Odd parity
No parity check
ON
OFF
1 stop bits
No parity check
ON
ON
2 stop bits
REFERENCE MANUAL
2

Advertisement

loading
Need help?

Need help?

Do you have a question about the Xmart MODBUS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Integra Xmart MODBUS

  • Page 1 MODBUS RS-485 CARD MODBUS RS-485 CARD REFERENCE MANUAL REFERENCE MANUAL ENGLISH Figure 1: Remove slot cover & Insert Modbus card into the slot 1.- Introduction MODBUS card is designed to be installed in SNMP port of all of our Online UPS. This card is able to provide communication for the UPS under following protocol: - Implements MODBUS RTU protocol - Provides MODBUS functions including read holding register and write registers.
  • Page 2 MODBUS RS-485 CARD MODBUS RS-485 CARD REFERENCE MANUAL REFERENCE MANUAL 5. Mode Setting 4.3. Interface Pin-out: SERIAL COMMUNICATION: LEFT RIGHT For using serial communication with multiple RS485 cards, external converter must be used. Function Function There are 2 types: (1) RS485 to RS232 converter or (2) RS485 to Modbus/TCP converter as RS-485-B TXD to PC indicated in below figures.
  • Page 3 MODBUS RS-485 CARD MODBUS RS-485 CARD REFERENCE MANUAL REFERENCE MANUAL For using only one (1) RS485 card with remote panel with distance shorter than 1.5 NETWORK TOPOLOGY & RESISTOR CONFIGURATION: meters, a RJ-45 to DB9 cable converter can be used: For using only one (1) RS485 card with remote panel with distance longer than 1.5 meters, special converter must be used: RS485 to RS232 converter...