Page 5
Disconnect all connectors before opening! Warning! If device is damaged disconnect it from power supply! Send it to the manufacturer for inspection. Warning! Connect to earth before attaching power supply! Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
STR 100 - Signal Transducer STR 100 SYSTEM DESCRIPTION STR 100 is modular system of communication devices that can be used for various of tasks such as: distance protection criteria transfer disconnector and circuit breaker statuses transfer between substations ...
One light indicator indicates power supply voltage, others indicate communication and IOs activity. TYPICAL APPLICATION Typical application is transfer of trip command and circuit breaker status between two substations. CONSTRUCTION Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019 Picture 2: STR 100 typical application...
STR 100 - Signal Transducer All devices from STR 100 system are based on various boards. There are three groups of boards. One main board, one or two communication boards and one IO board is used in one device : main board with power supply ...
DEVICE DEVICE APPEARANCE Other types of device are same except communication interface connectors are different. Picture 3: STR 100 / x.232.NON.x front view (left), bottom view (right) Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1...
Singlemode Fiber Optic (ST connector) board Ethernet board Although STR 100 device can have two interfaces it can communicate only with one at the time. Data is always received and transmited to both interfaces (ports). 4.2.1 RS232 INTERFACE BOARD Description Single, nonisolated, full duplex, RS232 port with DB9 female connector.
The stabilization on RS485 bus may be set on one device only! Switches at the lower side of connector: Switch Description RS485 stabilisation RS485 termination RS485 stabilisation Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
Page 12
STR 100 - Signal Transducer Picture 5: RS485 BUS schematic Switches at the upper side of connector: BAUD rate BAUD rate Switch Interface 5 Interface M Interface L 19200 4800 38400 9600 57600 19200 1200 115200 38400 2400 BAUD rate setting 19k2 (bps) is valid for all standard communication protocols, that do not request special timings.
Switch SW1 Light in idle state OFF ON OFF ON Positive logic Negative logic ON OFF ON OFF Picture 8: Versatile link fiber optic interface board appearance Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
STR 100 - Signal Transducer 4.2.4 MULTIMODE FIBER OPTIC INTERFACE BOARD Description Single, full duplex, multimode, fiber optic port with ST connectors with positive or negative logic. Hardware settings For proper functioning of that board, optic logic must be set:...
For using this interface Installer program is needed. It can be obtained from www.ediseja21.com\STR100-4channel-signal-transucer.htm. Installer program is needed for setting IP, network mask,... Software can be obtained from www.lantronix.com. Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
STR 100 - Signal Transducer 4.2.6.1 LANTRONIX INSTALLER SETTINGS Picture 11: Start program and press "Search" to find device, then select device to be set, press icon Assign IP, type request IP number and press button Assign Picture 12: Press "Web Configuration"...
Page 17
Picture 14: Use „IP Configuration/Use the following IP configuration:“ settings and set IP according to your needs. Picture 15: Set as shown on both STR devices Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
Page 18
STR 100 - Signal Transducer Picture 16: Hostlist settings on both STR devices Picture 17: Serial Settings on both STR devices Page: Company: Device: Document: Code: Date: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
Page 19
Pack Control / Idle Gap Time 12 ms NOTE! This are default factory settings. Do not change any of this settings, otherwise device can stop working correctly! Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
Page 20
STR 100 - Signal Transducer Picture 18: Connection Settings Setting Left picture - settings on Right picture - settings on the first STR device the second STR device Connect Mode / Active Connect "Auto Start" "None" Endpoint Configuration / Local Port...
Page 23
LED ready signalize when device normaly operates. If power is on and green LED ready: blinks or does not light; device does not operate correctly lights; device operates normally Switches at the bottom of the device - valid EXCEPT for STR 100 / x.ETH.x.x Switch Description BAUD rate selection BAUD rate Trans.
Page 24
If change during operation is made, disconnect power supply for a few moments (until power LED stops emitting) and connect power supply back. New settings are then accepted. Switches at the bottom of the device - valid for STR 100 / x.ETH.x.x devices only Switch...
Page 25
On the bottom side of device are switches for device setting and ISP connector which is intended for upgradeing software. Do not connect anything to that connector. For further technical data see chapter „TECHNICAL DATA“. Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
DO1 works as „ready“ indicator. For further details see chapter „HARDWARE DESCRIPTION/IO BOARDS“. STR 100 / x.x.NON.IOx x - means any type, for types description see chapter Ordering. Picture 21: STR 100 / x.x.NON.IOx schematic Page: Company: Device:...
5 mm. Protective earthing wire must be terminated with tinned copper ear terminal. The prescribed bending radius of the optical fibre cables must be observed. Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
STR 100 - Signal Transducer Picture 24: left. installation, right: deinstallation DEVICE SETTING It is recommended, that device setting is made before device is powered up. Some device settings are not regarded during operation, but only once after power up! If change during operation is made, disconnect power supply for a few moments (until power LED stops emitting) and connect power supply back.
Avoid eye exposure to direct or indirect radiation. MAINTENANCE The device is maintenance-free. Disconnect power supply before cleaning it. Use moist cloth. Do not use liquids. Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
STR 100 - Signal Transducer TECHNICAL DATA Power supply Type HI Type MD Type LO 110 - 250 V 48 - 60 V 24 V Rated input voltage 230 V 48 V 18 V 88 - 350 V 38 - 72 V...
Page 33
200 μm HCS Distance (approx.) 600 m 2000 m 1800 m -18 dB Optical output power -24 dB Reciver sensitivity Laser class I (IEC 60825-1) Direction full duplex Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
Page 34
STR 100 - Signal Transducer Communication port Multimode Fiber Optic (interface type FOT) Speed up to 115200 BAUD 1 receiver (grey connector) Input Output 1 transmitter (white connector) light ON or OFF in idle state set by switch Logic (see table) Connector type Communication port Singlemode Fiber Optic (interface type FOS, FOF &...
Page 35
10 ms 38400 BAUD 9 ms 57600 BAUD 8 ms 76800 BAUD 115200 BAUD 7 ms Valid for devices except STR 100/x.ETH.x.x. For device STR 100/x.ETH.x.x transition time depends on network latency. Company: Device: Document: Code: Date: Page: Ediseja 21 STR 100 User manual STRMUED1 09.08.2019...
Page 36
STR 100 - Signal Transducer Device Weight 0,35 kg Dimensions (see picture) 105 mm 111 mm + connectors 70 mm 0 °C to +55 °C Temperature range up to 95 % (noncondensing) Humidity operating Material Enclosure Mount type standard DIN 35 rail (acc. to DIN EN 50022-35)
STR 100 - Signal Transducer ORDERING ORDERING NUMBER: STR 100 / Power supply: 110 - 250 V DC or 230 V AC................HI 48 - 60 V DC or 48 V AC ................... MD 24 V DC ......................LO Interfaces: none ....