Installation and operation manual
for mixing set BM mini

Advertisement

Table of Contents
loading

Summary of Contents for Laing BM mini Series

  • Page 1 Installation and operation manual for mixing set BM mini...
  • Page 2 Installation and operation manual BM mini Design BM mini 1. Version KF = Remote sensor thermostat (8-6°C, 5 m) or Version RT = thermoelectric drive for the connection of a room thermostat (not included in delivery) or Version KR = thermoelectric drive, pre-wired with pump including a constant temperature control (A1-11 R, 0-70°C) for the connection of a room thermostat (not included in delivery) . Laing circulating pump with spherical motor A1-11 resp. A1-11 R 3. Venting device 4. Supply radiator-/boiler circuit 5. Return radiator-/boiler circuit 6. Supply floor heating circuit 7. Return floor heating circuit 8. Adjustable mixing valve 9. Adjustable bypass for the radiator-/boiler circuit (recommended to be closed) 10. ON-OFF-switch for pump 11. Flow temperature setting (KR version only) www.laing.de...
  • Page 3: Table Of Contents

    Table of contents Design BM mini ................... Technical Data ....................3 Application ....................4 Mounting instructions..................4 Hydraulic connection ..................5 Filling and priming the UFH system.............. 6 Starting of operation without given values ..........1 Starting of operation with given values (pre-setting) ........13 Assembly of wall bracket ................15 Dimensional drawing .................. 16 Pump curve ....................16 Product range, accessories and spare parts ..........17 Electrical connection................... 18 Technical Data Max. system pressure 1 Mpa (10 bar) Max. system temperature 110°C (boiler circuit), 55°C (floor heating) Max. differential pressure 100 kPa (1 bar) in the radiator-/boiler circuit Electrical connection 1 x 30 V / 50 Hz Power consumption 5 Watt (circulating pump) www.laing.de www.laing.de...
  • Page 4: Application

    • Three versions are available: BM mini KF: Mixing set with room temperature guided control, made of thermostat (10-6°C + frost protection) with remote sensor (5 m). BM mini RT: Mixing set for temperature guided control, made of thermoelectric drive for the connection of a room thermostat (room thermostat not included in delivery- see accessories in product range). BM mini KR: Mixing set with integrated constant temperature control (0-70°C) for the connection of a room thermostat (room thermostat not included in delivery- see accessories in product range). • The BM mini is provided with a temperature protection system that restricts the supply temperature in the floor heating circuit to max. 55°C. Mounting instructions • BM mini will be connected directly to the existing radiator-/boiler circuit. • When two circuits are connected to the BM mini, the shortest circuit must be balanced by using an adjustable return screw connection. • The BM mini has to be mounted in a horizontal position (see page ). Left or right connection to the radiator-/boiler circuit is possible (see page 9). • The BM mini has to be installed on a higher level than the floor heating installation. www.laing.de...
  • Page 5: Hydraulic Connection

    • Before running the BM mini please check, that the floor heating system is filled, completely vented, and proved against leakage. • Since the circulation pump might create under certain circumstances some flow noise, the BMmini should be placed away from noise sensitive areas (i.e. sleeping rooms). • The water temperature in the supply radiator-/boiler circuit should be at least 10 K higher than in the floor heating supply. • The maximum length of each pipe must not be longer than 100 m for floor heating design with spread of 10 K when using pipes 12 mm i.d. (i.e. pipe 16x). Smaller diameter pipe results in a shorter pipe length. • BM mini KF: Assemble the thermostatic head and mount the sensor in an appropriate position in the room and about 1,7 m above the floor. Use a vacant pipe if possible. • BM mini RT: Wiring of the electrical actuator and the room thermostat BM mini KR: only by a qualified electrician. Hydraulic connection of two-pipe systems Bypass valve closed. Allen key ,5mm. www.laing.de www.laing.de...
  • Page 6: Filling And Priming The Ufh System

    Installation and operation manual BM mini Filling of the system It is mandatory to flush the floor heating loops before putting the system in operation, because otherwise malfunction or damage to the pump may result. We recommend using two fill valves on the primary side of the BM mini as shown in picture 2. Alternatively, the system can be filled using fill valves installed elsewhere in the system. In any case, it is necessary to positively flush the system since otherwise the air in the system will not be purged completely. Filling the system via the integrated manual air vent (see picture 7) is not possible! Please observe the position of the ball valve in the bypass. If this is in the vertical position, the floor heating loops are hydraulically uncoupled from the boiler loop. This position is ideal for nor- mal operation (see picture 1) since the pump in the heating loop does not influence the floor heating loop. With the valve in this position, however, the floor heating system cannot be filled from the primary side. To fill the floor heating loops from the heating loop side, this ball valve must be closed (horizontal) – see pictures 2 through 6. After filling, the valve must be opened again (vertical position). Please observe that when filling from the primary side radiator valves on that side should be closed in order to have maximum pump pressure available for purging the floor heating loops. www.laing.de...
  • Page 7 Installation and operation manual BM mini Picture 1 ! ! ! Normal operation. Ball valve position open (vertical) Picture  ! ! ! Recommended filling of the system. Two fill valves on the primary side of the BM mini allow for an easy filling and purging of air in the floor heating loops. The ball valve position must be closed (horizontal). www.laing.de www.laing.de...
  • Page 8 Installation and operation manual BM mini Picture 3 ! ! ! Good filling option. Two existing fill valves on the primary side allow for good filling and air purging. The ball valve position must be closed (horizontal). Picture 4 ! ! ! Possible filling option, albeit a little complicated. One fill valve on the primary flow side allows for filling and air purging. The integrated ball valve must be closed (horizontal). Caution: The floor heating return at the BM mini must be closed during the fill operation. Filling a wall heating loop is impossible in this way. www.laing.de...
  • Page 9 Installation and operation manual BM mini Picture 5 ! ! ! Possible filling option, albeit a little complicated. One fill valve on the primary return side allows for filling and air purging. The integrated ball valve must be closed (horizontal). Caution: The floor heating flow at the BM mini must be closed during the fill operation. Filling a wall heating loop is impossible in this way. www.laing.de www.laing.de...
  • Page 10 Installation and operation manual BM mini Picture 6 ! ! ! The direction of flow shown is only possible if there is no check valve installed at the primary heating circulator. If a check valve is present, filling in accordance with picture 3 is recommended. www.laing.de...
  • Page 11 Installation and operation manual BM mini Picture 7 Filling the system in this way is impossible since no forced flushing can be assured. www.laing.de www.laing.de...
  • Page 12: Starting Of Operation Without Given Values

    Installation and operation manual BM mini Hydraulic connection of one-pipe systems This pipe system is not longer standard. Connection scheme on request. Starting of operation without given values 1. Remove protection cap / or thermostatic head / or electric drive from the BM mini (see page 14, picture 1). . Increase the supply temperature from the radiator-/boiler circuit to the designed value (normally 55-60°C). 3. To perform the adjustment check, the room temperature has to be at least 0°C. If it is not, the system has to be run until the temperature increases. 4. Check the floor heating supply temperature. It should be about 35-40°C. If it is too high, the flow from the primary supply has to be adjusted (reduced), see page 14 picture 3. The BM mini will be delivered from factory with fully opened mixing valve. We recommend an adjustment in small steps (1/ turn). After each adjustment the floor heating supply temperature should be checked after an appropriate waiting period. www.laing.de...
  • Page 13: Starting Of Operation With Given Values (Pre-Setting)

    Installation and operation manual BM mini Starting of operation with given values (pre-setting) E.g. Given values: Heat requirement of underfloor heating system 2000 W Supply temperature of radiator-/boiler system 70°C. Return temperature of underfloor heating system 40°C Difference pressure of the radiator-/boiler circuit 10 kPa Specific heat capacity of water 1,163 (Kg x K) Wanted values: Flow from the radiator-/boiler circuit = m = Q/(c x dT) = 000 W / (1,163 x 30 K) = 58 l/h (kg x K) Pre-setting: If the difference pressure from the radiator-/boiler circuit at the inlet and outlet of the BM mini is 10 kPa and the flow requirement of the BM mini is about 60 l, the mixing valve pre-setting has been opened by 1,6 turns. Turns to open www.laing.de www.laing.de...
  • Page 14 Installation and operation manual BM mini Remove protection cap Remove valve insert Use enclosed tool to adjust Screw valve insert in again the pre-setting of the mi- xing valve Room Temperature Setting (approx. values for BM mini KF only) 6°C 10°C 14°C 18°C 0°C °C 4°C 6°C www.laing.de...
  • Page 15: Assembly Of Wall Bracket

    Installation and operation manual BM mini Assembling of wall bracket The BM mini can be mounted to the wall bracket with radiator-/boiler connections to the left of to the right side. The screws for the mounting of the BM mini to the wall bracket are enclosed. Installation of the BM mini only with horizontal pump. Mixing valve and venting device have to show upwards. For a silencing of the sound the enclosed rubber bumpers have to be used between mounting bracket and wall, or - if mounted in a cabinet - between mounting bracket and fixation rails. www.laing.de www.laing.de...
  • Page 16: Dimensional Drawing

    Installation and operation manual BM mini Dimensional drawing 65mm Depth 90 mm Pump curve www.laing.de...
  • Page 17: Product Range, Accessories And Spare Parts

    Installation and operation manual BM mini Electrical connection BM mini KF 230 V~ Room-stat Laing Black brown 230 V~ Pump 230 V~ blue green/yellow www.laing.de www.laing.de...
  • Page 18: Electrical Connection

    Installation and operation manual BM mini Electrical connection BM mini RT - continuous operating of pump Room-stat Laing Room-stat Electrical Laing actuator Electrical actuator 230 V~ 230 V~ Electrical connection BM mini RT - pump also switched off by room thermostat...
  • Page 19 Installation and operation manual BM mini Electrical connection BM mini KR - continuous operating of pump Room-stat Laing Black brown 230 V~ Pump 230 V~ blue green/yellow Electrical connection BM mini KR - pump also switched off by room thermostat...
  • Page 20 About us Laing have been active since 1950 in the research and the development of pumps and heating products. More than 1000 patents have been registered world wide. The original R&D institute located in Southern Germany has over the years evolved into an international company with additional locations in the US, Japan and Hungary and with worldwide nearly 500 employees. Today, our production range includes: Pumps (shaftless spherical motor pumps) Heating controls   Floor heating system connection Electrical heaters   Special OEM-products  We are your flexible and competent partner for pumps and heating products. Try the high standard of our quality production. Laing GmbH · Systeme für Wärmetechnik Klingelbrunnenweg 4 · D-71686 Remseck - Germany · Phone: +49(0) 7146/93-0 Fax: +49(0) 7146/93-33 · E-Mail: info@laing.de · Internet: www.laing.de...