5.5
Drain Water Treatment
Drain water is discharged during heating and defrosting operation. (Rain water is also discharged.)
Pay attention to the followings.
(1) Choose a place where well drainage is available, or provide a drain ditch.
(2) Do not install the unit over the walkways. Condensation water may fall on people.
In case of installing the unit in such a place, provide the additional drain pan.
(3) When drain piping is necessary for the outdoor unit, use the drain boss set (Optional, DC-01Q).
Do not use drain boss and drain pan kit in the cold area. The drain water in the drain pipe may be
frozen and then the drain pipe may crack.
<76 KBtu/h to 96 KBtu/h>
Bottom Base
98
227
300
Refrigerant Piping Connection
(235 x 113 Square Hole)
Drain Boss (Optional Parts)
The drain boss is for the drain pipe connection in order to use outdoor unit bottom base as a drain pan.
Name
Drain Boss
Component Formation of Drain Boss
Model
DBS-26
< Installation Position >
Example: AVWT-96UESRX
Drain Pipe
(Field-Supplied)
227
Drain Hole ( 26 x 2)
Drain Boss Position (Option)
Drain Hole ( 26 x 2)
Drain Cap Position (Option)
Power Source Connection
( 52 Knock-out Hole)
Control Circuit Connection
( 26 x 2 Knock-out Hole)
Model
DC-01Q
Parts Name
Material / Color
Drain Boss
PP / Black
Drain Cap
PP / Black
Rubber Cap
CR / Black
Drain Cap Position
(2 places)
Drain Boss Position (2 Places)
(Outdoor Unit Rear Side)
<114 KBtu/h to 154 KBtu/h>
Bottom Base
98
227
Refrigerant Piping Connection
(235 x 113 Square Hole)
Q'ty
1
Connecting for Drain Piping
1
Embolization for Drain Hole
4
Sealing for Boss and Cap
< Side View >
(247)
(91)
(Rear Side)
52
(73)
Drain Boss
Drain Hole ( 26 x 2)
560
227
Drain Boss Position (Option)
Drain Hole ( 26 x 2)
Drain Cap Position (Option)
Power Source Connection
( 52 Knock-out Hole)
Control Circuit Connection
( 26 x 2 Knock-out Hole)
Application
(Front Side)
Bottom Base
Drain Cap
Unit: mm
17