Page 4
12 - Work mode (winter/summer) / Additional equipment view (cascade, wifi...) 13 - Outside temperature 14 - Boiler working stage * - additional equipment on screen only if additional equipment is installed and enabled (fuel level sensor) Technical instructions REGULATION Cm Pelet-set...
Cm WiFi-box - not connected External control ( Cm WiFi-box - connected View/additional equipment button (All items of additional equipment Cascade are enabled) Some items of the additional equipment are disabled All items of additional equipment are disabled Technical instructions REGULATION Cm Pelet-set...
C - this menu is used to set the parameters that must be selected but there can be only one selected item example: set the type of the DHW sensor D - this menu is used to set the parameters where are many items to be adjusted example: adjust the burner working parameters on power P2 Technical instructions REGULATION Cm Pelet-set...
Page 7
5 - up/down scroll buttons NOTE: after parameter changing press the "CONFIRM" button to store new value. If you don't want to save the set value, press "BACK" button. Tehničke upute REGULACIJA Cm Pelet-set Technical instructions REGULATION Cm Pelet-set...
- Maximal adjustment value: 3000 rpm NOTE: burner cleaning option is not replacing the need for manual cleaning of the burner and burner grate. It should be manually cleaned regulary according to the technical manual. Technical instructions REGULATION Cm Pelet-set Tehničke upute REGULACIJA Cm Pelet-set...
Page 9
NOTE: in the same way you can set other schedules: BOILER, DHW, RECIRCULATION 3.1.1. SCHEDULE This option is used to select active "SCHEDULE TABLE" that you have set Possible adjustment: - Factory adjustment: OFF - Table 1 - Table 2 - Table 3 Technical instructions REGULATION Cm Pelet-set...
Page 10
3 - time and working stage (OFF) when error occured Error codes are marked with letter "E" List of all error codes are listed in the "Cm Pelet-set manual" This option is used to see the history of the occured "WARNINGS"...
- 1. Circuit / 2. Circuit - you can check working of the devices of the mixing heating circuits (pumps, motor valves open close) - Additional equipment - submenu for manual test of the installed additional equipment NOTE: Items displayed in this menu and in "Additional equipment" submenu depends of set configuration and installed additional equipment. Technical instructions REGULATION Cm Pelet-set...
Page 12
SAVE - save current settings LOAD - load saved setting LOAD SERVICE - load setting autorized serviceman saved DELETE - delete saved settings You can save multiple setting under different names and you can load and delete saved setting. Technical instructions REGULATION Cm Pelet-set...
Standard equipment, Sensors, Photocell, Circuits 5.6. STANDARD EQUIPMENT This option is used for adjusting standard equipment of Cm Pelet-set Options: - Sensors - you can set the sensor type (PT1000 - factory or NTC 5K) - Photocell - you can adjust photocell parameters - 1.Circuit / 2.
Page 14
9 - Outer temperature (outer sensor) Items 1a - 8a have the same meaning as items 1-8 (described above) which only relate to 2. heating circuit or some other circuit depend how many circuits is selected. Technical instructions REGULATION Cm Pelet-set...
Page 15
Possible selection: Factory: 1.0 Option: 0.1 - 4.0 By using this option you can set heating curve value. Possible selection: Factory: 1.0 Option: 0,1 - 5,0 By using this option you can set correction value. Technical instructions REGULATION Cm Pelet-set...
Page 16
By using this option you can set working mode of the heating circuit By using this option you can set table for working mode of the heating circuit. NOTE: you can change settings of any heating circuit in the same way. Technical instructions REGULATION Cm Pelet-set...
- Options: "To._min/Taf_min" / "Toutside" 5.9. WORK MODE This option enables to set working mode Possible adjustment: - Factory adjusted: WINTER - Options: WINTER (heating + DHW) / SUMMER (only DHW) / AUTO (DHW <> heating + DHW) Technical instructions REGULATION Cm Pelet-set...
Page 18
- Show timers - show timers on the lower part of the screen - Date & time - you can set the date and time - Sound volume - you can set the touch sound type - Sound type - you can set the touch sound volume Technical instructions REGULATION Cm Pelet-set...
In this mode boiler will be exluded from cascade, external control etc. and work only according boiler temperature. Also in this mode modulation temperatures are lower so burner will modulate later, to enable longer measurement on set power. Technical instructions REGULATION Cm Pelet-set...
- (burner tries to establish normal work after power supply failure PFON230 - and return of the power supply) stage of full intake tube filling sensor (burner tries to establish normal work correction of the transporter F1 - working) - only CPPL-90 Technical instructions REGULATION Cm Pelet-set...
Page 21
Configurations 13. CONFIGURATIONS 13.1. CONFIGURATION A-0-0 EKO-CK P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way themostatic mixing valve + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
Page 22
Configurations 13.3. CONFIGURATION A-0-2 EKO-CK P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way themostatic mixing valve + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp. sensor (BUFFER2) 6 - Mixing heating circuit (2x) 7 - 1.
Page 23
Configurations 13.5. CONFIGURATION A-1-1 EKO-CK P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way themostatic mixing valve + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp. sensor (BUFFER2)
Page 24
Configurations 13.7. CONFIGURATION A-2-0 EKO-CK P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way themostatic mixing valve + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp. sensor (BUFFER2)
Page 25
13.9. CONFIGURATION A-2-2 EKO-CK P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way themostatic mixing valve + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp. sensor (BUFFER2)
Page 26
Configurations 13.11. CONFIGURATION A-7-1 EKO-CKB P 1 - Boiler EKO-CKB P + Cm Pelet-set 2 - 2 - Accumulation tank 3 - 3-way thermostatic mixing valve + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
Page 27
Configurations 13.13. CONFIGURATION A-8-0 EKO-CKB P 1 - Boiler EKO-CKB P + Cm Pelet-set 2 - 2 - Accumulation tank 3 - 3-way thermostatic mixing valve + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
Page 28
Configurations 13.15. CONFIGURATION A-8-2 EKO-CKB P 1 - Boiler EKO-CKB P + Cm Pelet-set 2 - 2 - Accumulation tank 3 - 3-way thermostatic mixing valve + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
Page 29
Configurations 13.17. CONFIGURATION B-0-1 EKO-CK P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
Page 30
Configurations 13.19. CONFIGURATION B-1-1 EKO-CK P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
Page 31
Configurations 13.21. CONFIGURATION B-2-1 EKO-CK P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
Page 32
Configurations 13.23. CONFIGURATION B-7-1 EKO-CKB P 1 - Boiler EKO-CK P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
Page 33
Configurations 13.25. CONFIGURATION B-8-1 EKO-CKB P 1 - Boiler EKO-CKB P + Cm Pelet-set 2 - Accumulation tank 3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1) (return flow protection) 4 - Accumulation tank upper temp. sensor (BUFFER1) 5 - Accumulation tank lower temp.
For more informations contact administrator of your home network For detailed configuration of the Cm WiFi-box please refer to the Cm WiFi- box manual received with the Cm WiFi box. Technical instructions REGULATION Cm Pelet-set...
Electric scheme ELECTRIC SCHEME 1/6 Technical instructions REGULATION Cm Pelet-set...
Page 74
Electric scheme ELECTRIC SCHEME 2/6 Technical instructions REGULATION Cm Pelet-set...
Page 75
Electric scheme ELECTRIC SCHEME 3/6 BURNER2 K EY E X T1 E X T 2 01 0 2 5 V IN Technical instructions REGULATION Cm Pelet-set...
Page 76
Electric scheme ELECTRIC SCHEME 4/6 Technical instructions REGULATION Cm Pelet-set...
Page 77
Electric scheme ELECTRIC SCHEME 5/6 - CPPL 14-50 Technical instructions REGULATION Cm Pelet-set...
Page 78
Electric scheme ELECTRIC SCHEME 6/6 - CPPL 90 Technical instructions REGULATION Cm Pelet-set...
Page 79
Notes NOTES Technical instructions REGULATION Cm Pelet-set...
Page 80
50°C Centrometal d.o.o. assumes no responsibility for possible inaccuracies in this book originated typographical errors or rewriting, all the pictures and diagrams are principal and it is necessary to adjust each actual situation on the field, in any case the company reserves the right to enter their own products such modifications as considered necessary.