This bulletin should be used by experienced personnel as a guide to the installation of the Series 26M Control. Selection
or installation of equipment should always be accompanied by competent technical assistance. We encourage you to
contact Gems Sensors or a representative if further information is required.
Specifications
Control Design: Solid-state components enclosed in a clear Lexan
plug-in style housing. Not NEMA rated.
Contact Design: 1 SPDT (1 form C), powered contacts
(input Power L1 connected to common of relay contacts)
Contact
Ratings:
10A@120/240-VAC
@120/240VAC resistive (150°F), 1/3 HP @ 120/240-VAC (120°F).
Contact Life: Mechanical -5 million operations
Electrical -100,000 operations minimum at rated load
Supply Voltage: Factory Configured: 24V, 120V, 220V, or 240V AC
+10%/-15% of nominal, 50/60 Hz. Factory Configured: 208V/240V
Model: 187V Min to 242V Max, VAC 50/60 Hz
Power Consumption: 24/120/220/240-VAC with both relays ener-
gized
4.4 VA.
~
Secondary Circuit: 2.3 VAC RMS voltage on probes, < 1 milliam-
pere source capability.
Sensitivity: Factory programmed to 4.7K, 10K, 26K, 50K, or 100K
Ohms
Operating Ambient Temperature Range: -40°F to +150°F (-40°C to
+65°C)
Terminals: All connections made with screw-clamp terminals.
Time Delays: Standard LLCO, 0.5 sec. on rising level, 3 sec. on fall-
ing level. Optional 0-90 sec. time delays in 1-sec. increments for
rising and falling.
Listings: Control carries U.L. Limit Control Listing (UL-353) for
24VAC and 120VAC Line Powered units only (220VAC, 240VAC,
208/240VAC units not rated).
Dimensional Drawing
Warrick
Installation and Operation Bulletin
resistive
(120°F),
1A
Torque all terminals and socket mounting screws to 7 in-lb max.
®
Series 26M Control
Installation
1. Install octal socket in appropriate enclosure
using two #6 or #8 screws.
2. Install rail mount socket on appropriate rail
(DIN mount) in appropriate enclosure if appli-
cable.
3. Wire control per wiring diagram following
N.E.C and local codes.
4. Install control module in socket.
Sensitivity vs. Maximum
Probe Wire Distance*
SENSITIVITY
SENSITIVITY
CHARACTER
(K-OHMS)
A
4.7
B
C
D
E
100
Based on type MTW or THHN wire,
#14 or #16 AWG
Mount the octal socket
(base) on rigid vertical
or horizontal surface
using #6 or #8 screws.
The control should be
mounted within an
enclosure of proper
NEMA integrity.
Form 261
Bulletin P/N 100204-1
Rev. K
Distance
(FT)
900
10
600
26
250
50
100
50

Advertisement

loading

Summary of Contents for Gems Sensors & Controls Warrick 26M Series

  • Page 1 Form 261 Bulletin P/N 100204-1 Rev. K ® Warrick Series 26M Control Installation and Operation Bulletin This bulletin should be used by experienced personnel as a guide to the installation of the Series 26M Control. Selection or installation of equipment should always be accompanied by competent technical assistance. We encourage you to contact Gems Sensors or a representative if further information is required.
  • Page 2 Wiring Diagram Operation AUTOMATIC RESET (Reset Switch terminals not wired) LED STATUS INDICATOR In normal operation, the LED When the liquid rises to the electrode on terminal LLCO, the on the control will either be on or off depending on the control energizes, changing state of the load contacts.