Installation At Seaside - LG THERMA V AHBW036H0 Quick Manual

Air conditioner with air-to-water heat pump
Hide thumbs Also See for THERMA V AHBW036H0:
Table of Contents

Advertisement

General Information

Installation at Seaside

CAUTION
1. Unit should not be installed in areas where corrosive gases, such as acid or alkaline gas, are
produced.
2. Do not install the unit where it could be exposed to sea wind (salty wind) directly. It can result
corrosion on the unit. Corrosion, particularly on the condenser and evaporator fins, could
cause unit malfunc-tion or inefficient performance.
3. If unit is installed close to the seaside, it should avoid direct exposure to the sea wind.
Otherwise itneeds additional anticorrosion treatment on the heat exchanger.
Selecting the location
1) If the unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the unit on the opposite side of the sea wind direction.
Sea wind
2) In case, to install the unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
Sea wind
3) Select a well-drained place.
1. If you can't meet above guide line in the seaside installation, please contact your supplier for
the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat
exchanger by using water
10 Air-to-Water Heat Pump
Sea wind
- It should be strong enough like concrete to pre-
vent the sea wind from the sea.
- The height and width should be more than 150%
of the unit.
- It should be keep more than 700 mm of space
between unit and the windbreak for easy air flow.