Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual 1. GENERAL SAFETY & WARNING INSTRUCTIONS Certain parts of electrical systems are inevitably live or have high operating temperatures. Observe caution at all times. Failure to observe these conditions and installation instructions can cause injury and damage.
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual 3. MODEL IDENTIFICATION Model numbering format 3.1. P S 035 035 Z – T1 Pinnacle S = Standard X = Custom (further nomenclature invalid) Nominal Height 018 = 18” 023 = 23”...
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual 5. PRODUCT DRAWINGS General configuration 5.1. Cabinet Air Ambient Air Mounting Hook Installation Gasket Cabinet Air Ambient Air Installation Gasket Cabinet Air Mounting Flange Mounting Face Cabinet Air HexFlow Pinnacle Series Product Information Manual...
Page 6
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual Cut Out and Mounting Diagrams 5.2. PS018XXX-XX series 5.2.1. Cut Out & Mounting Information for older PS023011/017/022-XX 5.2.2. series (prior to 2008) HexFlow Pinnacle Series Product Information Manual Page 6 of 14...
Page 7
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual Cut Out & Mounting Information PS023011/017/022-XX series 5.2.3. (2008 –on) Cut Out & Mounting Information PS023026-XX series 5.2.4. HexFlow Pinnacle Series Product Information Manual Page 7 of 14...
Page 8
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual Cut Out & Mounting Information PS035XXX-XX series 5.2.5. Cut Out & Mounting Information PS060XXX-XX series 5.2.6. HexFlow Pinnacle Series Product Information Manual Page 8 of 14...
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual 6. MOUNTING OF UNIT TO ENCLOSURE & OPERATION The enclosure shall be checked for correctness of cutouts, mounting holes and electrical supply. The Mounting Hook is preset to match the recommended cutout openings. If an adjustment other than the factory setting of the hook needs to be made, do so prior to fixing the gasket to the Heat Exchanger.
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual 7. DESIGN DATA: GENERAL PERFORMANCE Minimum Approx. Model # Watts/°F Voltage Full load, breaker/fuse Weight Amps size, Amps (lbs/Kg) PS018017Y 24VDC 21/9.5 PS018017Z 48VDC 1.75 2.25 21/9.5 PS023017A 115VAC 50/60 21/9.5...
Page 11
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual AC Voltage Diagram: All Models (11/17/22/35/45/55/100) A/B 8.1.1. DC Voltage Diagram: All Models (11/17/22/35/45/55) Y/Z without speed control 8.1.2. HexFlow Pinnacle Series Product Information Manual Page 11 of 14...
Page 12
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual DC Voltage Diagram: PS0XX0 (11/17/22/35/45/55) Y/Z with HX2 Speed Control 8.1.3. (up to batch date 130601) DC Voltage Diagram: PS0XX0 (11/17/22/35/45/55) Y/Z with HX2 Speed Control 8.1.4. (Batch date 130601 and newer)
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual WARRANTY DANTHERM, INC., LIMITED WARRANTY FOR HEAT EXCHANGER AND AIR CONDITIONING UNITS DANTHERM, INC.’s (“DANTHERM”) limited warranty extends to the original purchaser only of any DANTHERM heat exchanger and air conditioning unit, and to no other person or entity.
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual RETURN MATERIAL AUTHORIZATION PROCEDURE In the unlikely event of unit failure the following return procedure shall be adopted. All product returns require a Return Material Authorization number regardless of reason.