Installation manual water-cooler
1 or multiple water cooled Opticlimates can be connected to 1 water cooler. The water cooler is a
super efficient way to recirculate water or a glycol-mix in a closed loop system. The fan(s) and the
circulation-pump are the only parts that consume energy. The water cooler makes it possible to
prepare water for the Opticlimates at outside temperatures over 40°C.*
Setting up the system starts with a good design of the system. Pump-size, piping diameter and
layout are the most important items when designing the system.

The pump:

The circulator pump must supply a pre defined flow at a given pressure. The flow is determined by
the energy that must be circulated (KW) and the pressure depends on the pressure-drop of the
complete system (Opticlimate(s) + piping + water-cooler) We always calculate the correct pump for
your setup. We suggest to place the pump indoor.

The piping:

We suggest to use PE-piping with quick connectors. Prevent knees or other fittings that reduce
water-flow. We supply all the fittings for PE piping in the package. Supplying the piping is also
possible.

The water cooler:

The stock water coolers come as Industrial heavy duty and Ultra light /compact. The stock versions
are all vertical models (roof/floor or wall mount). Both models can also be ordered as a horizontal
model (roof /floor mount)

The fittings:

Supplied fittings are for PE piping applications. We supply automatic bleeders, air separators, ball
valves, treated fittings depending on your setup.
© TCF 2019
© TCF 2019

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3500pro3 and is the answer not in the manual?

Questions and answers

Summary of Contents for TCF 3500pro3

  • Page 1 (roof/floor or wall mount). Both models can also be ordered as a horizontal model (roof /floor mount) The fittings: Supplied fittings are for PE piping applications. We supply automatic bleeders, air separators, ball valves, treated fittings depending on your setup. © TCF 2019 © TCF 2019...
  • Page 2 After bleeding, let the pump run full power, the air seperator will remove any air bubbles that remain in the system. This can take a few minutes, hours or even days depending on the layout of the piping. © TCF 2019...
  • Page 3 The flow in this setup must be manualy adjusted with a valve in the piping between pump and water cooler. The flow needs a periodic adjustment depending on outside temperatures. ΔT between water-in and water-out of the Opticlimate needs to be 5K. More flow loweres ΔT, less flow increases ΔT. © TCF 2019...
  • Page 4 The current clamp can be opened to clamp around the cable. Plug the other end into the controller. The cable is labeled CO2 or T-spot. A current transformer labeled CO2 must be connected to the controller CO2 port. A current transformer labeled T-spot must be connected to the INFRARED port of the controller. © TCF 2019...
  • Page 5 RH. The settings on the controller are pre-set. Do not change them without consultation. Power both the controller and fan-aux-box. The fan and pump go on for a few seconds, this is normal at first startup. © TCF 2019...
  • Page 6 20% glycol / water mix. (antifreeze protection -10°C) or more depending on outside conditions. To determen how much glycol must be added, you need to know the total volume of water in the system. The specification sheets below help to determen how much volume your system contains. © TCF 2019...
  • Page 7 -A water glycol mix prevents corrosion -Use an automotive antifreeze tester and a sample of the glycol/water mix to check the freezing- point of the mix. Make sure the mix is correct for weather conditions in your area. © TCF 2019...
  • Page 8 Design sheet Number of Opticlimates on 1 water cooler_______________________________________ Opticlimate model (s)___________________________________________________pro3/pro4 Distance between Opticlimates and water cooler_________________________________mtr Heat load Opticlimates (KW)_________________________________________________KW Max. outside temperature ____________________________________________________°C Min. outside temperature ____________________________________________________°C Sketch of the situation © TCF 2019...