Bryant ZONE PERFECT TWO-ZONE Installation Instructions Manual page 3

Table of Contents

Advertisement

Fig. 5—Insulated Round Metal Ductwork
SUPPLY
AIR DUCT
Fig. 6—Rectangular Metal Ductwork
3. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check
your local codes.) (See Fig. 7.)
1 2
1 / " TO 2"
INSULATION
Fig. 7—Insulated Rectangular Metal Ductwork
NOTE: All zone dampers and ductwork must be properly sup-
ported according to local codes or SMACNA standards.
NOTE: There should be a minimum of 4 ft between the zone
damper and the first branch duct if more than 1 branch duct is
downstream of the zone damper.
C. Round Flexible Ductwork
1. Slip 1 end of flexible ductwork over 1 end of zone damper.
(See Fig. 8.)
2. Secure the flexible duct to zone damper using SMACNA or
other approved method.
3. Properly seal joint using duct tape, mastic, or other ap-
proved method. Do not allow mastic to come in contact
with actuator.
4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check
your local codes.) (See Fig. 9.)
/ " STEEL STRAP
1
2
A95130
S-LOCK
DRIVE
ZONE
DAMPER
A92478
A95131
FLEXIBLE
DUCT
Fig 8—Round Flexible Ductwork
NOTE: All zone dampers and ductwork must be properly sup-
ported according to local codes or SMACNA standards.
Fig. 9—Insulated Round Flexible Ductwork
D. Rectangular Fibrous Glass Ductwork
1. Insert 1 end of zone damper into 1 end of fibrous glass
ductwork approximately 2 to 3 in. (See Fig. 10.)
FIBROUS
GLASS
DUCTWORK
Fig. 10—Rectangular Fibrous Glass Ductwork
2. Screw field-supplied screws and tabs into zone damper.
3. Properly seal joint using duct tape, mastic, or other ap-
proved method. Do not allow mastic to come in contact
with actuators
4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check
your local codes.) (See Fig. 11.)
Fig. 11—Insulated Rectangular Fibrous Glass Ductwork
V. INSTALL BAROMETRIC BYPASS DAMPER
NOTE: The barometric bypass damper is a critical part of the
Zone Perfect Two-Zone System for control of minimum airflow
and noise reduction. It is recommended that the bypass be
installed.
—3—
ZONE
DAMPER
/ " STEEL STRAP
1 2
FIELD
SUPPLIED
SCREWS
2" TO 3"
1 / " TO 2"
1 2
INSULATION
A95132
A95133
ZONE
DAMPER
A92480
A95134